Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: DEVELOPMENT PLAN
Permit Number - D10-0005
Review Name: DEVELOPMENT PLAN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/05/2010 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 02/05/2010 | RONALD BROWN | ADA | REVIEW | Passed | Not a COT owned/operated property |
| 02/09/2010 | DAVID MANN | COT NON-DSD | FIRE | Denied | Fire Comments: If the building was originally permitted as unlimited area the neww addition cannot extent closer than 60 feet to the property line. |
| 02/24/2010 | STEVE SHIELDS | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Lead Planner PROJECT: Irvington Plaza Building 7 Development Plan (1st Review) D10-0005 TRANSMITTAL DATE: February 24, 2010 DUE DATE: March 05, 2010 DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is February 07, 2011. 2. This development plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the area of expansion only. 3. There is a Special Exception T09SE00072 has been applied for this site. The site plan for the Special Exception shows a change in parking configuration along the north side of the main building. If the Goodwill is still planned for this site why have the parking changes not been shown on this plan? 4. Provide a copy of the plan that approved the "EXIST. STORAGE UNITS" shown to the west of Building 10. 5. D.S. 2-05.2.1.K List the following case numbers in the lower right corner near the title block on all sheets, D01-0008, C9-73-55, C10-01-18, T09SE00072, DSMR 01-07. 6. D.S. 2-05.2.2.A.1 List the names, addresses, and telephone numbers of the developer of the project on the development plan. 7. D.S. 2-05.2.2.B.2 Place the D10-0005 development plan number in the lower right corner next to the title block. 8. D.S. 2-05.2.2.B.3 List the existing use as "GENERAL MERCHANDISE SALES "28", SUBJECT TO: SEC. 3.5.9.2.C" 9. D.S. 2-05.2.2.B.10 Provide a general note stating that "THE PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE CRITERIA: SEC. 2.8.3, MAJOR STREETS AND ROUTES (MS&R) SETBACK ZONE." 10. D.S. 2-05.2.2.B.11 Based on the last approved development plan D01-0008 the gross site square footage is 326,870. On this development plan "General Note 3 & Area of Site Revisions" show 326,370 and the "F.A.R. Calculation Land Area shows 326,870. Please clarify what the correct gross site square footage is. 11. D.S. 2-05.2.4.A Show all existing property lines along with distance and bearings on the development plan. 12. D.S. 2-05.2.4.B All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing. Provide the existing zoning for the parcels on the north side of Irvington and east side of Campbell. 13. D.S. 2-05.2.4.D.3 If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Sec. 3.3.0 of the LUC and Development Standard 3-05.0. Provide a fully dimensioned vehicle use area. 14. D.S. 2-05.2.4.D.3 Per D.S. 3-05.2.2.B.3 A minimum distance of two (2) feet must be maintained between a PAAL and any wall, screen, or other obstruction, provided pedestrian activity is directed to another location. The additional area is necessary to provide clearance for fire, sanitation, and delivery vehicles. That said a two (2) foot setback is required at the southwest end of the proposed "CONCRETE LOADING DOCK RETAINING WALL WITH STEEL RAILING ON TOP" to the PAAL. 15. D.S. 2-05.2.4.D.3 Demonstrate on the plan how the requirements of D.S. 3-05.2.2.B.3 are met for the EXIST. STORAGE UNITS" shown to the west of Building 10, to the PAAL. 16. D.S. 2-05.2.4.I Provide the height of the proposed "NEW METAL DOCK ENCLOSURE" from grade to the top of wall so that setback requirements to the south property line can be verified. 17. D.S. 2-05.2.4.K Approved development plan D01-0008 shows a required pedestrian circulation/accessible route that connects Building 10 to Building 7, demonstrate on the plan how this pedestrian circulation/accessible route is provided. 18. D.S. 2-05.2.4.M The provided "Existing Building Data" square footage listed for "Buildings 7 & 8 does not match the square footage listed on the last approved development plan D01-0008, please clarify. 19. D.S. 2-05.2.4.P Per D.S. 3-05.2.1.3 When the side(s) of a parking space abuts any vertical barrier over six (6) inches in height, other than a vertical support for a carport, the required width for the space is ten (10) feet to provide extra width to allow passengers to enter and exit the vehicle on the side where the barrier exists. That said there is a proposed refuse enclosure west of Building 3 directly adjacent to a vehicle parking space. Demonstrate on the plan how the requirements for D.S. 3-05.2.1.3 are met. 20. D.S. 2-05.2.4.Q Show, on the drawing, off-street bicycle parking locations, including materials for lighting and paving, type of security, dimensions, specific type of rack and the number of bicycles it supports, and the location and type of directional signage. When adjacent to pedestrian paths, indicate the width of clearance available for the pedestrian area. For specifics, refer to Development Standard 2-09.0. 21. D.S. 2-05.2.4.Q The bicycle calculation is based on 377 vehicle parking spaces provided but the vehicle parking calculation shows 378 vehicle parking spaces provided. Clarify the total vehicle parking spaces provided. 22. D.S. 2-05.2.4.T Demonstrate the maneuvering area for all proposed refuse collection area. 23. If applicable ensure all changes are made to the grading and landscape plans. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com Sshield1 on DS1/planning/New Development Package/ D10-0005 RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan & copy of the last approved development plan or site plan. |
| 02/25/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
| 03/01/2010 | JOE LINVILLE | LANDSCAPE | REVIEW | Approv-Cond | Subject to approval of Special Exception case T09SE00072 and any applicable conditions of approval. |
| 03/04/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | 3/4/09 Called applicant to request pump calcualtions. Please submit requested documentation for further review. Bianca |
| 03/05/2010 | JOHN WILLIAMS | ZONING-DECISION LETTER | REVIEW | Denied | COMMUNITY DESIGN REVIEW COMMITTEE PLANNING & DEVELOPMENT SERVICES March 5, 2010 Anthony Capps AGC Architecture Inc. 1373 W. Hopbush Way Tucson, Arizona 85704 Subject: D10-0005 Irvington Plaza Building 7 Development Plan Dear Anthony: Your submittal of February 4, 2010 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 4 DETAILED cover letters explaining how each outstanding requirement has been addressed: ALL BLACKLINES MUST BE FOLDED 4 Copies Revised Development Plan (Fire, Zoning, Engineering, Landscape, PDSD) 2 Copies Pump Calculations (Engineering, PDSD) 2 Copies Existing Approved Site Plan showing Storage Units (Zoning, PDSD) Should you have any questions, please call me at 837-4919. Sincerely, John Williams Planning Technician All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: (520) 623-8145 |