Permit Number: D09-0023
Parcel: 117023490

Address:
1002 N MAIN AV

Review Status: Completed

Review Details: REVISION - DEV PLAN

Permit Number - D09-0023
Review Name: REVISION - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2012 CPIERCE1 START PLANS SUBMITTED Completed
11/20/2012 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
11/20/2012 RONALD BROWN ADA REVIEW Passed
11/21/2012 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: The Salvation Army Hospitality House
Development Plan (Revision)
D09-0023

TRANSMITTAL DATE: November 26, 2012

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. D.S. 2-05.2.4.C As it appears that some of the vehicle parking spaces are now going to be provided in Phase 2 provide a phased vehicle parking calculations.

2. D.S. 2-05.2.4.C As it appears that some of the vehicle parking spaces are now going to be provided in Phase 2 provide a phased lot coverage calculation.

3. D.S. 2-05.2.4.D.3 As it appears that some of the vehicle parking spaces are now going to be provided in Phase 2 demonstrate on the plan how vehicles will be prevented from accessing the unimproved area at the east end of the south parking area. A back-up spur will be required.

4. D.S. 2-05.2.4.M The following general notes need to be revised to reflect the proposed changes to building square footage, 2B & 2E

5. D.S. 2-05.2.4.M If the "ASPHALT" area shown north of the "Hospitality House" is vehicle use area show that area as included in the lot coverage calculation.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/ D09-0023

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan.
11/23/2012 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed Defer to Rezoning.
11/23/2012 GARY WITTWER COT NON-DSD TDOT Approv-Cond I have reviewed the above noted plan and only have one comment.

Please add a note to the landscape plans that stated:

The contractor is required to obtain a Right-of-Way permit for work in the ROW.

I could not find it. All other required notes are there.
11/30/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter and backflow preventer
b. the location of the gas meter (if one exists or is planned)
c. the location, invert, and rim elevation of the upstream manhole
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
12/03/2012 RONALD BROWN ZONING HC REVIEW Denied SHEET DP1.0
1. At details 5 and 7: Show max slope in all directions not to exceed 2%, reference ICC A1171. Section 502.5.
2. At detail 4, change the 5'-0" dimension to 7'-0". Adjust the 6'-8" dimension accordingly.
SHEET DP1.1
3. Zoning may required a pedestrian access to the 1st Street pedestrian way. If so, this pedestrian must be accessible. Please verify with Zoning.
4. Assure that all slopes of all accessible routes comply with ICC A117.1, Section 403.3; 5% max running slope and 2% max cross slope.
END OF REVIEW
12/04/2012 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved DATE: December 3, 2012
TO: Jeff Hunt, P.E.
REVIEWER: Elizabeth Leibold, PE
SUBJECT: Salvation Army Engineering Review - Revision #1
ADDRESS: 1002 N Main Av
LOCATION: T14S R13E Sec12
FLOODPLAIN STATUS: X-unshaded zone, 2276L
CASE NUMBER: D09-0023

SUMMARY: The Revision to development plan for the Salvation Army was submitted with changes to zoning related items (ie. Building square footage) as well as changes to the proposed finished floor elevations. Engineering Division of Planning & Development Services Department has received and reviewed the revision for the Development Plan including plan sheets dp1.0, dp1.1, dp1.2, landscape plans, and Drainage Statement for Salvation Army Hospitality House (Cyprus Civil Development, Jeffrey P. Hunt, P.E. 10.11.2012). The Transitional Family Apartments on the east side of the project (labeled as Building #2) was approved previously with a minimum finished floor of 2363.0. The Revision set of plans show a FFE of 2362.0. Due to adjacent jurisdictional floodplain limits showing a base flood elevation of 2360.6 (extrapolated), the proposed FFE is acceptable. Engineering Division recommends approval of the Revision #1 of the approved Development Plan with the following suggestions for the grading submittal. Please be aware that a grading permit application will be needed to be submitted, reviewed and approved prior to commencement of construction activity. Building permits are also required.

GRADING PERMIT CONSIDERATIONS:
1) Submit Floodplain Use permit application with grading permit application.
2) Submit Drainage Statement clarifying that elevation certificates will be required for each structure.
3) Provide additional proposed spot elevations in the sidewalk areas adjacent to building structure and within accessibility stalls and routes to clarify that maximum slopes have not been exceeded.

If you have questions, call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
12/04/2012 KBROUIL1 COT NON-DSD FIRE Denied Would you please indicate the location of the existing or proposed fire hydrants for this project? If they are already noted on a page, then please tell me what page number.
12/06/2012 PGEHLEN1 COT NON-DSD TUCSON POLICE DEPARTMENT Denied I cannot approve this until I view the plans for the lighting. I failed to find any plans of lighting in the Development Review.

CSO Becky Noel #37968
Tucson Police Dept
837-7428
12/07/2012 JOE LINVILLE NPPO REVIEW Approved
12/07/2012 JOE LINVILLE LANDSCAPE REVIEW Approved
12/07/2012 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied This review has been completed. Revision is required.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/01/2013 CPIERCE1 REJECT SHELF Completed