Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D09-0023
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
09/30/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approved September 29, 2009

To: JAMIE BITLER
SWAIM ASSOCIATES

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6719), representing the Pima County
Departments of Regional Wastewater Reclamation Department and Environment Quality

Subject: THE SALVATION ARMY HOSPITALITY HOUSE
Dev. Plan –2nd Submittal
D09-023


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above-mentioned comments, please contact me.
09/30/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO: CITY PLANNING
FROM: AUDREY FARENGA, ADDRESSING REVIEW
SUBJECT: D09-0023 THE SALVATION ARMY HOSPITALITY/REVISED DEVELOPMENT PLAN
DATE: 09/30/09



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1. Include the lots and portions of lots on all Title Blocks.
10/05/2009 JOSE ORTIZ COT NON-DSD TRAFFIC Denied The right of way vacation and possible exchange of land needs to be finalized wirth real estate before an approval can be issued.
10/09/2009 RONALD BROWN ZONING HC REVIEW Approv-Cond Insure signage at all accessible parking spaces
10/14/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department - Plans Coordination Office
FROM: Bianca Ramirez
Engineering Associate

PROJECT: The Salvation Army Hospitality House
Development Plan (2nd Review)
D09-0023

TRANSMITTAL DATE: September 21, 2009

DUE DATE: October 19, 2009

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Engineering Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Complied

2. Complied

3. Complied

4. Complied

5. D.S. 2-05.2.3.B - Verify that all easements have been indicated on plan along with recordation information including location, width and purpose indicated on the plan. Specify on plan as to whether they will be or are public or private.

Response: General note has been read and acknowledged. Comment will remain until recordation process has been completed.

6. Complied

7. All Public Right of Ways adjacent to a site are to have the name, right of way width, recordation data, type, and dimension width of paving, curbs, curb cuts, and sidewalks - verify that both are dimensioned and labeled throughout plan.

Response: Please provide dimensions for future sidewalk on plan.

8. D.S. 2-05.2.3.C Based on the existing "60' ½" right-of-way (ROW) shown on the plan and a "FUTURE TAPERED R.O.W." there appears to be a dedication of ROW that includes taking back ROW along the taper. Please clarify what is proposed. If dedication is planned the dedication must be approved prior to approval of the development plan.
Response: General note has been read and acknowledged. Comment will remain until recordation process has been completed.

9. D.S. 2-05.2.3.I and D.S. 2-05.2.3.I .3 - Provide all floodplain information including the location of the 100-year floodplain limits and associated information such as the water surface contours.

Response: Use different lines to differentiate between Floodplain and Water Surface Elevations. Add floodplain limits symbol and water surface elevation symbol to legend.

10. Aerial does not match the plan submitted. Any lot modifications will need to meet zoning requirements. See Zoning Comments.

Response: General note has been read and acknowledged. Comment will remain until recordation process has been completed.

11. Complied

12. Complied

13. D.S. 2-05.2.4.D.3 - Provide a dimension for the "SANITATION VEHICLE CIRCULAITON" access lane. Provide the radii for the fire circulation lane.

Response: Verify that the radii for fire circulation is correct outside = 50' and inside = 36' or provide approval from fire department.

14. Complied

15. Complied

16. D.S. 2-05.2.4.S - Call out fire circulation radii on plan.

Response: Verify that the radii for fire circulation is correct outside = 50' and inside = 36' or provide approval from fire department.

17. Per Special Exception Condition 2 indicate the required ROW dedication on the site plan and label.

Response Label as ROW dedication.

16. D.S. 2-05.2.4.E South and east of parcel 117-02-3510 there is ROW that appears will be abandoned. Provide a copy of the documents for the abandonment and show the recordation information on the plan.

Response: General note has been read and acknowledged. Comment will remain until recordation process has been completed.


17. D.S. 2-05.2.4.E - N portions of Alder Ave. are to be abandoned. Provide a copy of the documents for the abandonment and show the recordation information on the plan.

Response: General note has been read and acknowledged. Comment will remain until recordation process has been completed.


18. D.S. 2-05.2.4.E - It appears that portions of the alley are to be abandoned along the northeast corner of this project. Provide a copy of the documents for the abandonment and show the recordation information on the plan.

Response: General note has been read and acknowledged. Comment will remain until recordation process has been completed.

19. D.S. 2-05.2.4.O - Demonstrate on the plan how access to the northern most loading spaces is provided and that it meets LUC Section 3.3.7.3.

20. Complied

21. Complied

22. Complied

23. Complied

24. Complied

25 Complied

26. D.S. 2-05.3.2.A - A report which includes the proposed solution for any land with unusual topography, soils, or other geographical hazard to life, health, or property shall be prepared to the City Engineer's specifications ad will be submitted to the City's Engineer's Office.

27. Note that a grading plan and a floodplain use permit will be required for further development of the property.

Response: This is a general comment that will remain until all comments have been addressed.

28. Add a general note indicating that scuppers will be used when the roof scupper locations have been designed and located. Also indicate that they will be identified on future grading plan. OR Provide scupper information on plan with next submittal to show that 100% of the 10 - year flow is conveyed under the sidewalks along with any other drainage.

29. Please show the proposed roof drainage patterns along with flow arrows and downspouts.

30. Geotechnical report calls out concrete and pavement specifications. Provide detail and appropriate notes on the Development Plan. Add Geotechnical information on Development Plan. Include professional information along with contact information and any project numbers associated with the geotechnical report that would assist the geotechnical engineer locating or referencing the report in the future.

31. Identify heavy duty and light duty pavement information along with concrete specification information. Provide details.

30. Additional comments may be forth coming depending on how each comment has been addressed.

DRAINAGE REPORT: DENIED

1. Reference to West University Neighborhood Drainage Study (WUNDS) is being made throughout report. Add statement within Drainage Report of acceptance of WUNDS Drainage Study OR prove assumptions and data.

2. Hydrologic Data Sheets are showing 2.71 for (60-rain) per COT data standard of 3.0 should be utilized (table 4.3) OR provide supporting information for rainfall aerial map.

3. Additional comments may be forthcoming.

GEOTECHNICAL REPORT: APPROVED

If you have any questions about this transmittal, please Bianca Ramirez, (520) 837-4928 or Bianca.Ramirez@tucsonaz.com


RESUBMITTAL OF THE
10/15/2009 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Planning and Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: The Salvation Army Hospitality House
Development Plan (2nd Review)
D09-0023

TRANSMITTAL DATE: October 15, 2009

DUE DATE: October 19, 2009

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section conditionally approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

All easement, dedication, abandonment and lot split/combination recordation information, Docket and Page must be provided on the final DP:

2. D.S. 2-05.2.3.B If applicable all easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated.

3. D.S. 2-05.2.3.C Based on the existing "60' ½" right-of-way (ROW) shown on the plan and a "FUTURE TAPERED R.O.W." there appears to be a dedication of ROW that includes taking back ROW along the taper. Please clarify what is proposed. If dedication is planned the dedication must be approved prior to approval of the development plan.

4. D.S. 2-05.2.4.A The proposed lot split/combination will need to be processed and approved by the City of Tucson prior to approval of the development plan.


5. D.S. 2-05.2.4.E South and east of parcel 117-02-3510 there is ROW that appears will be abandoned. Provide a copy of the documents for the abandonment and show the recordation information on the plan.

6. D.S. 2-05.2.4.E Zoning acknowledges that portions of Alder Ave. are to be abandoned. Provide a copy of the documents for the abandonment and show the recordation information on the plan.

7. D.S. 2-05.2.4.E It appears that portions of the alley are to be abandoned along the northeast corner of this project. Provide a copy of the documents for the abandonment and show the recordation information on the plan.

8. D.S. 2-05.2.4.G Per Special Exception Condition 7 a turn around area is required for residential properties located to the north. An easement will be required for this turn around. Show this easement on the plan and label the purposed and whether it will be public or private along with the recordation information.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/ D09-0023

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan
10/15/2009 JOE LINVILLE LANDSCAPE REVIEW Denied Revise the landscape plan to include (or identify) the future sight visibility triangles and revise plant locations or species to ensure a clear line of sight between 30 and 72 inches.
10/16/2009 ANDY VERA ENV SVCS REVIEW Approved
10/19/2009 FERNE RODRIGUEZ COT NON-DSD REAL ESTATE Denied Real Estate has completed the circular process for the requested right of way vacation and exchange. Numerous conditions need to be resolved regarding the exchange of this right of way before Real Estate will approve the development plan.

Sincerely,

Jim Stoyanoff
Property Agent
Real Estate Division
City of Tucson
201 N. Stone Ave. 6th Fl.
Tucson, Arizona 85701
(O) 520.837.6719
(F) 520.791.5641
Jim.Stoyanoff@tucsonaz.gov
10/20/2009 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

October 20, 2009

Jamie Bitler
Swaim Associates
7350 E. Speedway Blvd, #210
Tucson, Arizona 85710

Subject: D09-0023 - The Salvation Army Hospitality House Development Plan

Dear Jamie:

Your submittal of July 1, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 7 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

7 Copies Revised Development Plan (Addressing, Traffic, Engineering, Zoning, Landscape, Real Estate, PDSD)

5 Copies Revised Landscape Plan (Landscape, Engineering, Zoning, Planning, PDSD)

2 Copies Revised Drainage Report (Engineering, PDSD)

Should you have any questions, please call me at 837-4919.


Sincerely,




John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (520) 326-1148
10/20/2009 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied PLANNING & DEVELOPMENT SERVICES COMMENTS - CDRC
Land Use Plan Compliance

D09-0023, The Salvation Army Hospitality: DP and LP
Submittal # 2

Items Reviewed:
" Development Plan (DP) & Landscape Plan (LP)
" SE-04-08, ZE decision 10/7/04

Comments: The plans are not approved. Please address the following, and resubmit the DP and LP.

1) Per special exception conditions # 10 and #14, a 6-foot high wall is to be provided along the northern site boundary, to prohibit access between the site and the neighborhood to the north. The revisions that have been made to the DP are acceptable. The LP needs to be revised to be consistent with the DP. On the LP, please delete the 6-foot wall along the eastern and northeastern site boundaries.

2) Per special exception condition #20, perimeter screen walls are to incorporate a decorative treatment for improved visual quality. The varied wall alignment along the southern property boundary will satisfy this condition, however, please provide a decorative treatment for the perimeter wall in the northwest portion of the site, and please indicate that treatment on the development plan.


Please feel free to contact this reviewer to discuss any of the above.


Reviewed by: J. Hershenhorn, 10/19/09