Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: DEVELOPMENT PLAN
Permit Number - D09-0022
Review Name: DEVELOPMENT PLAN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2009 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 07/01/2009 | FERNE RODRIGUEZ | COT NON-DSD | REAL ESTATE | Passed | |
| 07/02/2009 | RONALD BROWN | ADA | REVIEW | Passed | NOT A COT OWNED/OPERATED PROPERTY |
| 07/09/2009 | TIM ROWE | PIMA COUNTY | WASTEWATER | Denied | July 8, 2009 To: JAMES R. WATSON JAMES R. WATSON ARCHITECT PLC Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department ___________________________ From: Tom Porter, Sr. CEA (520-740-6719), representing the Pima County Departments of Regional Wastewater Reclamation Department and Environment Quality Subject: NEW BUILDING FOR GOSPEL RESCUE MISSION Dev. Plan –1st Submittal D09-022 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. This project will be tributary to the Roger Road Wastewater Treatment Faciltiy via the South Rillito Interceptor. Obtain a letter from the PCRWRD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at: http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf. The development plan for this project cannot be approved until a copy of this letter has been received by this office. Sheet 1: Add a General Note that states: THIS PROJECT WILL HAVE ______ EXISTING AND______ PROPOSED WASTEWATER FIXTURE UNIT EQUIVALENTS PER TABLE 13.20.045(E)(1) IN PIMA COUNTY CODE 13.20.045(E). And fill in the blanks with the appropriate values. Sheet 1: Add a Permitting Note that states: A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT. Sheet 4: The values shown for FUE for the existing construction does not appear to match values per Table 13.20.045(E)(1) of the Pima County Ordinance. Please revise. This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents. Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet. The next submittal of this project will be the second(2nd) submittal. A check for the review fee of this submittal in the amount of $100.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter. If the number of sheets changes, please adjust the review fee accordingly. If you have any questions regarding the above-mentioned comments, please contact me. |
| 07/14/2009 | DAVID MANN | COT NON-DSD | FIRE | Denied | Please identify the extent of the care and rehabilitation provided in each building. Any building that is changing use from R-1 or R-2 to I-1 or R-4 will be required to have automatic fire sprinklers. Please see IFC Chapter 2 and the local amendments to IFC Chapter 9. |
| 07/14/2009 | JENNIFER STEPHENS | PIMA COUNTY | ADDRESSING | Denied | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 JENNIFER STEPHENS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL SUBJECT: D09-0022 NEW BUILDING FOR GRM/DEVELOPMENT PLAN DATE: 7/14/09 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval: Delete 707 W. Miracle Mile on all applicable pages. Include legal description and Section, Township and Range on all Title Blocks. Delete all adjacent tax codes. Delete N. from N. 15th Ave and spell out Ave. Label all buildings numerically, no letters. |
| 07/17/2009 | STEVE SHIELDS | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Lead Planner PROJECT: New Building for GRM Development Plan (1st Review) D09-0022 TRANSMITTAL DATE: July 17, 2009 DUE DATE: July 30, 2009 DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is May 07, 2010. 2. Based on the information provided on the development plan and a building expansion of 24.88% this review is for full code for the area of expansion only. Provide a copy of the last approved site plan so that the cumulatively expansions can be verified. 3. D.S. 2-05.2.1.D The provided location map does not shown the section grid correctly. The east section grid line runs along Oracle Road and the north section grid line runs along Forth Lowell Road. 4. D.S. 2-05.2.1.D.3 Identify the sections corners on the location map. 5. D.S. 2-05.2.1.G.2 Provide a brief legal description within the title block. 6. D.S. 2-05.2.2.B.3 Provide the subject to: "SEC. 3.5.7.8.A, .C.4, .D, AND .H" following the proposed use listed in General Note 4. 7. D.S. 2-05.2.2.B.10 Revise General Note 5 to include the LUC Section 2.8.3 for the Major Streets and Routes (MS&R) Setback Zone. 8. D.S. 2-05.2.3.B If applicable all easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. 9. D.S. 2-05.2.4.B Show all existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. Provide the zoning for the parcel(s) located to the north Miracle Mile. 10. D.S. 2-05.2.4.D.3 Provide the 3'-0" radius on the proposed backup spur shown at the south end of the west parking area. See D.S. 3-05.2.2.D 11. D.S. 2-05.2.4.Q The proposed Class 2 Bicycle parking does not meet the requirements of D.S. 2-09.2.4.1 Proximity to Main Entrances. Class 2 bicycle parking facilities will be located no more than 50 feet from the main building entrance(s) and will be along the front side of the building. Relocate the proposed Class 2 bicycle parking so that it is located along the front side of the building. 12. D.S. 2-05.2.4.Q Once the Class 2 bicycle parking has been relocated to meet the requirements as stated above demonstrate on the plan how lighting to the parking area will provided. 13. Per LUC Section 3.5.7.8.H Provide a lot coverage calculation on the plan. See LUC Section 3.2.9. 14. Per the Special Exception Conditions revise the DEVELOPMENT PLAN CRITERIA, MAX ALLOW HT to = 35'. 15. Additional comments may be forth coming depending on how each comment has been addressed. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com Sshield1 on DS1/planning/New Development Package/ D09-0022 RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents. |
| 07/20/2009 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Approved | 4350 E. Irvington Road, Tucson, AZ 85714 Post Office Box 711, Tucson, AZ 85702 WR#213687 July 17, 2009 Gospel Rescue Misson Attn: James Watson 3026 N Country Club Rd Tucson, Arizona 85716 Dear Mr. Watson : SUBJECT: New Building for GRM D09-0022 Tucson Electric Power Company has reviewed and approved the development plan submitted July 2, 2009. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development. This property is currently being served with Primary Metering. Customer will either have to upgrade the Primary Metering system so that existing load plus the new load can be served by it. If customer wants to convert to a TEP system for the property then they will have to completely do away with the existing primary metering system and re-feed all existing buildings and new buildings with the new TEP system. Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer. In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to: Tucson Electric Power Company Attn: Mr. Richard Harrington New Business Project Manager P. O. Box 711 (DB-101) Tucson, AZ 85702 520-917-8732 Should you have any technical questions, please call the area Designer Lorraine Ruiz at (520) 918-8241. Sincerely, Elizabeth Miranda Office Support Specialist Design/Build lm Enclosures cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email) L. Ruiz, Tucson Electric Power |
| 07/20/2009 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Denied | We have reviewed the Development Plans for the additional 5020 sq. ft. building at the Gospel Rescue Mission located on State Route (SR) 77 at 707 W. Miracle Mile. The existing driveways will serve the development. Our records indicate that ADOT's right-of-way at this location is 50 feet from the centerline on Miracle Mile. The plans show 75 feet of right-of-way from the centerline on Miracle Mile and the existing 50 feet of right-of-way. Please clarify the 75 feet of right-of-way notation on the plans. We appreciate the opportunity to comment on the Development Plans. Maria Deal Southern Regional Traffic Engineering ADOT 1221 S. 2nd Ave. Tucson, AZ 85713 Phone #: 520-388-4235 ________________________________ Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments. 2009 |
| 07/20/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Denied | Need to review the pre-fab ramp and landing submittals or shop drawings or catalog cuts. |
| 07/21/2009 | FERNE RODRIGUEZ | OTHER AGENCIES | PIMA ASSN OF GOVTS | Approved | CASE: D09-0022 NEW BUILDING FOR GRM: DEVELOPMENT PLAN COMMENT: NO OBJECTIONS OR ADVERSE COMMENTS Vehicle Trip Generation: Daily: N/A PM Peak: N/A Please call if you have questions or need additional information. ------------------------------------------- KoSok Chae, Ph.D. 177 N. Church Ave., Suite 405 Tucson, AZ 85701 520-792-1093 x487 [tel] 520-620-6981 [fax] www.PAGnet.org |
| 07/24/2009 | PETER MCLAUGHLIN | LANDSCAPE | REVIEW | Denied | 1. Add the CDRC Development Plan case number (D09-0022) and any other related case numbers to the lower right hand corner of all sheets of the development plan and landscape plan. DS 2-03.2.2.B.1 2. Demonstrate compliance (graphically and a note) on the landscape plan with Special Exception condition #22 regarding rainwater harvesting. 3. Any changes made to the development plan based on other reviewers comments must also be reflected on the landscape plan. 4. The native plant preservation application for exception is approved as submitted. |
| 07/27/2009 | GLENN HICKS | COT NON-DSD | PARKS & RECREATION | Approved | DATE: July 24, 2009 TO: DSD_CDRC@ tucsonaz.gov FROM: Glenn Hicks Parks and Recreation 791-4873 ext. 215 Glenn.Hicks@tucsonaz.gov SUBJECT: D09-0022 New Building for GRM: Development Plan Review(7/2/09) Staff has no comments. |
| 07/29/2009 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | The Engineering Division recommends approval of this development plan. However, if it is determined that the project constititutes a substantial expansion and a full code compliance review is required, the engineering division will require additional review. |
| 07/29/2009 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Approved | DEPARTMENT OF PLANNING AND DEVELOPMENT SERVICES COMMENTS Regarding SUBJECT: Community Design Review Committee Application CASE NUMBER: CASE NAME: DATE SENT D09-0022 Gospel Rescue Mission () Tentative Plat (X) Development Plan () Landscape Plan () Revised Plan/Plat () Board of Adjustment () Other - Elevations CROSS REFERENCE: SE-08-17 - Gospel Rescue Mission NEIGHBORHOOD PLAN: General Plan GATEWAY/SCENIC ROUTE: NO COMMENTS DUE BY: 7/30/09 SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS: () No Annexation or Rezoning Conditions, Not an RCP - No Comment (X) Proposal Complies with Rezoning (Special Exception) Conditions () RCP Proposal Complies With Plan Policies () See Additional Comments Attached () No Additional Comments - Complies With Planning Comments Submitted on: REVIEWER: msp 791-5505 DATE: 07/27/09 |
| 07/30/2009 | ANDY VERA | ENV SVCS | REVIEW | Denied | 1. Move gate post to face of CMU wall and position it so it is separate (1 to 2 inches) from wall to avoid enclosure wall damage. 2. Gates must be equipped with the ability to be secured in the open position per DS 6-01.4.2.C.4...annotate and show within detail. Recommend "Positive locking and (Bayonet) anchors, Qty-4, 1 in. Dia. x 6 in. long galvanized pipe flush in concrete/foundation." 3. Access and approach to enclosure area is good. Please provide corrections on resubmittal. If you have any questions you may contact Andy Vera at (520) 791-5543 ext 1212 or e-mail: Andy.Vera@tucsonaz.gov |
| 07/30/2009 | JOSE ORTIZ | COT NON-DSD | TRAFFIC | Approved | |
| 08/03/2009 | JWILLIA4 | ZONING-DECISION LETTER | REVIEW | Denied | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES August 3, 2009 James R. Watson Gospel Rescue Mission 3026 N. Country Club Road Tucson, Arizona 85716 Subject: D09-0022 New Building for GRM Development Plan Dear James: Your submittal of July 1, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 10 DETAILED cover letters explaining how each outstanding requirement has been addressed: ALL BLACKLINES MUST BE FOLDED 10 Copies Revised Development Plan (Wastewater, Fire, Engineering, Addressing, Zoning, HC Site, ADOT, Landscape, ESD, DSD) 4 Copies Revised Landscape Plan (Landscape, Zoning, DSD) Should you have any questions, please call me at 837-4919. Sincerely, John Williams Planning Technician All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: N/A (jim@jrw-arch.com) |
| 08/03/2009 | PGEHLEN1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Approved | |
| 08/03/2009 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Passed | |
| 08/04/2009 | FERNE RODRIGUEZ | COT NON-DSD | TUCSON AIRPORT AUTHORITY | Approved | Thank you for the opportunity to comment on the subject development plan (D09-0022) Gospel Rescue Mission Oracle/ Miracle Mile. The site is not within the TIA Public Disclosure Area. The Tucson Airport Authority does not oppose this request. Respectfully, Jordan D. Feld, AICP Director of Planning Tucson Airport Authority 7005 S. Plumer Ave. Tucson, AZ 85756 jfeld@tucsonairport.org www.tucsonairport.org (520) 573-5115 office (520) 573-8006 fax |