Permit Number: D09-0013
Parcel: 10509546C

Address:
68 W RIVER RD

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D09-0013
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/24/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
06/29/2009 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
07/02/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Denied June 26, 2009

To: JESUS ORTIZ
DOWL HKM

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________________
From: Tom Porter, representing the Pima County Departments of Regional Wastewater Reclamation Department and Environment Quality

Subject: QUIKTRIP STORE NO. 1450
Dev. Plan – 2nd Submittal
D09-0013

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD).This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

Sheet 4: Fill in the blanks of the Dkt and Page for the private sewer easement shown on plan. Call out the easement as vacated instead of abandoned.

Sheet 15: The building can not encroach upon the public sewer easement shown on plan. The proposed new alignment of the public sewer is not acceptable due to the inability to access the proposed new public sewer manhole. If you would like to discus this with PCRWRD contact Mr. Don Wilhoit @ (520)740-6779.

Sheet 15: Call out the public sewer easement on site with width and recordation information.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.
Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.


The next submittal of this project will be the third(3rd) submittal. A check for the review fee of this submittal in the amount of $78.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.
07/09/2009 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Quick Trip Store 1450
Development Package (2nd Review)
D09-0013

TRANSMITTAL DATE: July 9, 2009

DUE DATE: July 23, 2009

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is April 5, 2010

2. This project was review for full code compliance of the City of Tucson Land Use Code, Development Standard 2-01.0 and Development Package Submittal Requirements Draft dated 12-20-07.

3. Zoning acknowledges that a demo plan was provided with this submittal. A separate demolition permit will be required.

4. D.S. 2-01.3.3 Zoning acknowledges that a Development Standard Modification Request (DSMR) has been approved and that the DSMR Number DS09-0015 has been added to the plan, also provide the date of approval, what was approved and any conditions of approval.

5. D.S. 2-01.3.8.B There is a Public Drainage and a 20' Sewer easement shown on the Final Plat, Bk. 44 Pg. 62. Show these easements on the development plan. The proposed building appears to be over the 20' sewer easement. This easement will need to be abandoned prior to approval of the development plan.

6. D.S. 2-01.3.8.B Based on discussions with the adjacent tenants there are CC&R's in place for this development. Within the CC&R's there are cross access easements shown across the proposed site that run directly under the proposed fuel canopy and around the existing building to the north. Provide documentation that these CC&R's have been amended and that the easements have been abandoned.

7. Based on discussions with the adjacent tenants there are CC&R's in place for this development. This said if the cross access is to be amended provide a copy of the amended CC&R's. D.S. 2-01.3.9.H.5.a Provide a copy of the cross access agreement between this parcel and the parcels to the west.

8.See comment 4. D.S. 2-01.3.9.H.5.d It does not appear that the proposed Class 2 bicycle parking meets the requirements of D.S. 2-09.4.1. Provide a dimension from the proposed Class 2 bicycle parking to the main entrance of the proposed building. If the location of the Class 2 bicycle parking does not meet the requirements of D.S. 2-09.4.1 and you propose to leave the bicycle parking as shown on the plan a Development Standard Modification Request (DSMR) is required. If the DSMR is approved provide on the plan the DSMR case number, date of approval, what was approved and any conditions of approval.

9. Stone Loop is not shown on the Major Streets and Routes map therefore there is not a future curb proposed for this street. Remove the reference to future curb for Stone Loop in the Land Use Requirements. D.S. 2-01.3.9.O The perimeter yard requirements shown for the east and north perimeter yards are not correct. Based on the size of the apartment complex located north of W. Stone Loop the Average Daily Traffic is greater than 1000 therefore the required perimeter yard is 21' or the height of the proposed exterior building wall, which ever is greatest, measured from the back of curb. Zoning acknowledges that the proposed development meets these requirements, revise the perimeter yard requirements under the "LAND USE REQUIREMENTS" sheet 1 and show the perimeter yard dimensions correctly on sheet 4.

10. D.S. 2-05.3.9.R Zoning acknowledges that this comment should have been made on the last review. The proposed striped crosswalk running west from the proposed building needs to be re-routed so that it does not run parallel with the PAAL that connects to the adjacent parcels.

11. D.S. 2-01.3.9.H.5.a. The proposed vehicle parking spaces located along the south property line may not be located within the 30' Scenic Corridor buffer.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ D09-0013

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package and additional requested documents.







CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Quick Trip Store 1450
Grading Plan (2nd Review)
T09BU00493

TRANSMITTAL DATE: July 9, 2009

DUE DATE: July 23, 2009

GRADING PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning cannot approve the grading plan until the development plan has been approved.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package and additional requested documents.















CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Quick Trip Store 1450
T09SA00178
Overlay Zone Review (1st Review)

TRANSMITTAL DATE: July 9, 2009

DUE DATE: July 23, 2009

COMMENTS:
1. This development is subject to the review and approval of the special application for the Scenic Corridor Overlay. Provide a general note stating: "The Special application case number is T09SA00178.The special application has been reviewed and approved, approval date __________, without conditions."

2. LUC Sec. 2.8.2.3.C Add the 400-foot SCZ corridor boundary from River Road on site plan. Zoning acknowledges that the 400-foot SCZ corridor boundary from River Road is off site provide a dimension to the line and show as not to scale.

3. LUC Sec. 2.8.2.4.A Label the required thirty (30) foot buffer as "30 FOOT UNDISTURBED NATURAL BUFFER TO BE PRESERVED AND MAINTAINED IN IT'S NATURAL STATE".

4. LUC Sec. 2.8.2.6.B Provide the view corridor calculation on the plan.

5. Please add the following notes to the site plan.
a. Maximum height of structures will be 1/3 the distance of the structure from the future right-of-way of River Road, not to exceed 30 feet for commercial development from design grade.

b. No grading beyond what is necessary for siting of buildings, drives, private yards, and structural improvements. All viable vegetation with a caliper of 4 inches or greater and all saguaro cacti will be preserved or relocated on the site per the Native Plant and Preservation Ordinance.

c. All new utilities for development on private property or public right-of-way along River Road will be underground. Trenching is permitted for the placement of utilities lines, if area is revegetated in accordance with Land Use Code Sec. 3.7.5.2.D

d. Building or structure surfaces, which are visible from River Road will have colors, which are, predominate within the surrounding landscape such as desert and earth tones.

e. Fencing and freestanding walls facing River Road. will meet material restrictions in Land Use Code Sec. 3.7.3, Screening Requirements.

f. All areas between the MS & R right-of-way line and the existing street right-of-way that are disturbed by development shall be revegetated with native vegetation.

g. All disturbed areas on the site that are visible from River Road and are not covered by permanent improvements shall be revegetated with native plants, plants from the Drought Tolerant Plant List, or a combination of both.

6. Provide the overlay number T09SA00178 in the lower right hand corner, near the title block on all sheets of the development plan.

7. The proposed vehicle parking spaces located along the south property line may not be located within the 30' Scenic Corridor buffer.

8. All requested information will be provided on the development plan or as attachments to the development plan

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com
07/14/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: D09-0013 QUIKTRIP STORE 1450/REVISED DEVELOPMENT PLAN
DATE: 7/13/09



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Addresses are not required to be on Development Plans. Please remove 68 W. River Road on all locations.
This Development Plan does not show the entire portion of lot 1 of Northmall Centre 44/62. Please correct legal description on all Title Blocks.
07/14/2009 JOE LINVILLE LANDSCAPE REVIEW Approved
07/15/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
07/16/2009 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved >>> Tom Martinez <TMartinez@azdot.gov> 07/15/2009 12:27 PM >>>
ADOT recommends approval of this development.
07/24/2009 LOREN MAKUS ENGINEERING REVIEW Approved
07/24/2009 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D09-0013 Quiktrip Store 1450

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE:

NEIGHBORHOOD PLAN: General Plan

SCENIC ROUTE: YES

COMMENTS DUE BY: July 23, 2009

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Comments Below
(X) No Additional Comments - Complies With Planning Comments Submitted on: April 27, 2009







REVIEWER: msp 791-4505 DATE: June 25, 2009
07/29/2009 JWILLIA4 ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 29, 2009

J. Lorenzo Ortiz, P.E.
DOWL HKM
166 W. Alameda Street
Tucson, Arizona 85701

Subject: D09-0013 Quicktrip Store #1450 Development Package

Dear Lorenzo:

Your submittal of April 3, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 4 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Development Package (Zoning, Addressing, Wastewater DSD)

Should you have any questions, please call me at 837-4919.


Sincerely,




John Williams
Planning Technician