Permit Number: D09-0008
Parcel: 14016003F

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D09-0008
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/03/2009 FRODRIG2 LANDSCAPE REVIEW Denied 1. Add the new CDRC development plan case number (D09-0008) for this proposed revision in the lower right hand corner of all sheets of the development plan, landscape plan and irrigation plan. DS 2-05.2.2.B.2

2. The Native Plant Preservation Application for Exception is approved as submitted.

Per Peter Mclaughlin
06/03/2009 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
06/03/2009 FRODRIG2 ZONING REVIEW Denied Add the new CDRC development plan case number (D09-0008) for this proposed revision in the lower right hand corner of all sheets of the development plan, landscape plan and irrigation plan. DS 2-05.2.2.B.2
Per Peter Mclaughlin
06/03/2009 TIM ROWE PIMA COUNTY WASTEWATER Denied
06/03/2009 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#209090 March 27, 2009

Physical Resource Engineering
Attn: Daniel White
P.O. Box 36985
Tucson, Arizona 85740

Dear Mr. White:

SUBJECT: Portales High School
D09-0008

Tucson Electric Power Company has reviewed and approved the development plan submitted March 11, 2009. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.

If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Should you have any technical questions, please call the area Designer, Mike Kaiser at (520) 918-8244.

Sincerely,


Elizabeth Miranda
Office Support Specialist
Design/Build
lm
Enclosures
cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email)
M. Kaiser, Tucson Electric Power
06/03/2009 FRODRIG2 ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: March 24, 2009
CDRC/Zoning Manager
SUBJECT: Los Portales High School, 5040 S. Campbell Ave.
Development Plan D09-0008 (D01-0028) (First Review)
T15S, R14E, Section 06

RESUBMITTAL REQUIRED: Development Plan and Drainage Report.

The Development Plan (DP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. It is not clear if all the key notes are from the prior DP or if they are intended for this DP.
3. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207. This shall be noted on the plans.
4. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. Campbell Ave. is a designated arterial street with a future width of 120' and the future face of curb is located 9' from the right-of-way line. Therefore the existing and future SVT's are not shown correctly. The correct lengths of the SVT's are the nearside is 345' long and the farside is 125' long. Revise as required.
5. Key note no. 23 will need to be revised per comment no. 4.
6. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
7. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DP.
8. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
9. Show Development plan number (D09-0008) on all sheets per D.S. 2-02.2.1.29.
10. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
11. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
12. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
13. Add note: "Depress all landscaped areas 6" maximum for water harvesting". Call-out on the plans that the exist. parking islands shall also be depressed for water harvesting.
14. "A grading permit may be required for this project. Submit 2 sets of grading upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans".

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. Addendums to any Drainage Reports and Hydrology Reports etc. are not accepted. The new layout or revisions must be incorporated into the approved Drainage Report or a new DR may be submitted.
3. If the prior DR data is used in the new DR, than a statement that the data was reviewed and accepted must be included in the new DR.
4. Add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DR.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/5040 S.Campbell Ave DP
06/03/2009 FRODRIG2 ZONING-DECISION LETTER REVIEW Denied DEVELOPMENT SERVICES

April 1, 2009

Daniel White
Physical Resource Engineering, Inc.
PO Box 36985
Tucson, Arizona 85740

Subject: D09-0008 Portales High School Development Plan

Dear Dan:

Your submittal of March 11, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 4 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Development Plan (DUPD, Engineering, Wastewater, DSD)

2 Copies Revised Landscape Plan (Engineering, DSD)

2 Copies Dimensioned, color building elevations (DUPD, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)


Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 690-1769
dp-resubmittal
06/03/2009 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D09-0008 Portales High School (REVISION)

Reviewed: (X) Development Plan
(X) Landscape Plan

CROSS REFERENCE: C9-95-12 & D01-0028

NEIGHBORHOOD PLAN: Kino Area Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: 03/25/09

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

(XXXX) Resubmittal Required:
(XXXX) Development Plan


1. Per rezoning condition #8 which reads "all new construction shall utilize earthtone colors and materials. Bright colors may be used for accent. Please provide elevations and color palette demonstrating how this condition will be met. Also, demonstrate how new addition will be compatible with existing development.


REVIEWER: drcorrral 791-4505 DATE: 03/19/09
06/03/2009 FERNE RODRIGUEZ COT NON-DSD TUCSON POLICE DEPARTMENT Approved >>> Rebecca Noel 03/24/2009 3:24 PM >>>
I have no issues with this proposal.
CSO Becky Noel
Tucson Police Dept