Permit Number: D09-0006
Parcel: 12112056C

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D09-0006
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/16/2009 TERRY STEVENS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: D09-0006
Quiktrip Store No.1452
5151 E. Speedway Blvd.
Development Package Plan

TRANSMITTAL: 06/16/2009

DUE DATE: 05/29/09

COMMENTS:

1. The Zoning Review Section approves the development plan and grading plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

2. DS 2-01.3.8.B The indicated easements that are to be abandoned or vacated by separate instruments, are to be abandoned or vacated prior to approval of this plan. Provide recording docket and page information of the abandonment on the site plan for each easement.

3. This site contains four (4) separate tax parcels therefore you will need to show how the parcels can work as stand alone parcels if sold separately or provide a Pima County Tax Parcel Combo and a recorded covenant regarding development and use of real property. Provide copies of the documents at the next submittal for review.

4. DS 2-01.3.9.W The indicated billboard does not appear to be located within the indicated easement. A new easement may be required to be recorded or relocation of the billboard.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961
TLS C:\planning\cdrc\developmentplan\D09-0006dpca.doc
06/17/2009 JASON GREEN ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 06/17/2009,TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: Quick Trip #1452
D09-0006, T14S, R14E, SECTION 02

RECEIVED: Development Plan, Grading Plan Landscape Plan and Drainage Report on June 03, 2009


The subject submittal has been reviewed. The Development Plan Package submittal can not be approved at this time. Address the following comments before review can continue. Prepare a detailed response that explains the revisions that were made and references the exact location on the Development Plan Grading Plan and SWPPP, where the revisions were made:

DRAINAGE REPORT:

1. Provide offsite runoff HEC RAS analysis for pre and post development conditions. Address the impact of the offsite runoff on the subject development and the impact of the development on the runoff (check for encroachment). Revise the report and all applicable drainage exhibits accordingly.

DEVELOPMENT PACKAGE:

1. Revise the Development Package in accordance with the Drainage Report revisions.

For any questions or to schedule a meeting, call Jason Green, Senior Engineer Associate, at 837-4929.


RESUBMITTAL REQUIRED: Revised Drainage Report and Development Plan package
06/17/2009 JWILLIA5 ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

June 17, 2009

Richard Cordova
DOWL HKM
166 West Alameda Street
Tucson, Arizona 85701

Subject: D09-0006 Quicktrip Store #1452 Development Package

Dear Richard:

Your submittal of February 27, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 3 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

3 Copies Revised Development Package (Engineering, Zoning, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)

2 Copies Lot Combo Form (Zoning, DSD)


Should you have any questions, please call me at 837-4919.

Sincerely,



John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (520) 624-0384