Permit Number: D09-0005
Parcel: 13311008A

Review Status: Completed

Review Details: CORE REVIEW

Permit Number - D09-0005
Review Name: CORE REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
02/24/2009 JIM EGAN COT NON-DSD FIRE Approved
03/02/2009 ROGER HOWLETT COT NON-DSD URBAN PLANNING & DESIGN Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D09-0005 Lowe's Staging

Reviewed:
(X) Development Plan
(X) Landscape Plan

CROSS REFERENCE: D04-0003 & C9-03-023

GATEWAY/SCENIC ROUTE: Kolb Road (gateway)

COMMENTS DUE BY: March 23, 2009

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

(XX) Proposal Complies with Rezoning/SE Conditions





REVIEWER: drcorral 791-4505 DATE: 02/27/09
03/05/2009 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. Add the CDRC Development Plan case number, the rezoning case number (C9-08-09), and any other related case numbers to the lower right corner of all sheets.

2. Revise the north arrow to be oriented correctly on all sheets.

3. Add a detail on sheet L3 of the staging area wall to demonstrate compliance with rezoning condition #10. Provide information on the wall detail regarding materials of construction and dimensions, including height of wall, so that the maximum allowed height of stacked items within the staging area may be determined in accordance with rezoing condition #13.
03/09/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approv-Cond March 6, 2009

To: THOMAS SAYLER-BROWN
SBBL ARCHITECTURE AND PLANNING

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), representing the Pima County Departments of Wastewater Management and Environment Quality

Subject: LOWE'S HOME IMPROVEMENT STAGING AREA
Dev. Plan - 1st Submittal
D09-005


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

Sheet 1: Remove General Notes #10 and #12 and add a General Note that states:

THE ON-SITE SEWERS ARE EXISTING AND PRIVATE. NO NEW SEWERS ARE PROPOSED.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above-mentioned comments, please contact me.
03/09/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
03/12/2009 FERNE RODRIGUEZ COT NON-DSD TUCSON POLICE DEPARTMENT Approved >>> Rebecca Noel 03/11/2009 5:12 PM >>>
I have no issues with this request.

CSO Becky Noel #37968
Tucson Police Dept
837-7428
03/12/2009 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
03/17/2009 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 03/17/2009,

TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: Lowe's Home Improvement, Staging Area
D09-0005, T14S, R15E, SECTION 05
Reference: D04-0003

RECEIVED: Development Plan, Landscape Plan on February 23, 2009

The subject submittal has been reviewed. We offer the following comments. Prepare a detailed response that explains the revisions that were made and references the exact location on the Development Plan where the revisions were made:

1. Provide the assigned D (yr)-______ subdivision case number, on both sheets, as required by D.S. 2-05.2.2.B.2.
2. The staging area drainage pattern appears to have changed from the previously approved drainage scheme. Address this issue and clarify, if the drainage patterns have changed, how this will affect the overall site drainage. Additionally, clarify if the proposed wall around the staging area shall have wall opening to allow runoff to drain through.

Landscape Plan:

Address Landscape Review comments.


RESUBMITTAL REQUIRED: Revised Development Plan and Landscape Plan
03/18/2009 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Lowes Staging Area - Kolb Road & Speedway
Development Plan (1st Review)
D09-0005

TRANSMITTAL DATE: March 18, 2009

DUE DATE: March 23, 2009

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is February 22, 2010.

2. D.S. 2-05.2.2.B.2 Provide the D09-0005 development plan number in the lower right hand corner adjacent to the title block of all plans.

3. D.S. 2-05.2.4.K Provide a dimension from the proposed north wall of the staging area to the parking area access lane. Per D.S. 3-05.2.2.B.1 A minimum setback distance of five (5) feet for a pedestrian refuge area must be maintained between any enclosed structure and a PAAL. Per the proposed landscape plans it appears that there are trees that will encroach into the required pedestrian refuge.

4. D.S. 2-05.2.4.P Based on the last approved development plan it appears that four (4) vehicle parking spaces have been removed from the plan. The vehicle parking calculation shown on sheet DP1 shows 597 spaces provided the same number shown on the last approved development plan. If these vehicle parking spaces have been relocated clarify the new location. If the four (4) vehicle parking spaces have been removed from the plan provide a copy of the parking study that shows that these spaces are not required and revised the provided number to reflect the number provided on the plan.

5. As Rezoning Case C9-08-09 includes the Special Exception revise the "REZONING CONDITIONS (C9-08-09) to read "REZONING/SPECAIL EXCEPTION CONDITIONS (C9-08-09)

6. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ D09-0005

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents.
03/19/2009 ANDY VERA ENV SVCS REVIEW Approved Expanded staging area will not impact solid waste disposal requirements. Existing conditions and previously approved DP demonstrates adequate solid waste disposal/collection services.

If you have any questions you may contact Andy Vera at (520) 791-5543 ext 1212 or e-mail: Andy.Vera@tucsonaz.gov
03/25/2009 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR# 208972 March 24, 2009



SBBL Architecture & Planning
Attn: Thomas Sayler-Brown
1001 N. Alvernon Way #105
Tucson, Arizona 85711

Dear Mr. Sayler-Brown:

SUBJECT: Lowes Staging Area
D09-0005

Tucson Electric Power Company (TEP) has reviewed the plan submitted March 17, 2009. TEP is unable to approve the plan at this time. There are existing electrical facilities within the boundaries of this project. In order for TEP to approve the plan the facilities and easements must be depicted on the plans. The TEP PM transformer is in the proposed staging area. TEP requires 10’ clear space in front of transformer and clear access to the transformer for Maintenance.

Enclosed is a copy of a TEP facility map showing the approximate location of the existing facilities. All costs associated with the relocation of the facilities in conflict will be billable to the developer.

Please resubmit two revised bluelines to City of Tucson Development Services Department for TEP’s review. You may contact the area Designer, Nancy DiMaria at 918-8267 should you have any technical questions.

Sincerely,



Henrietta Noriega
Office Specialist

hn
Enclosure
cc: City of Tucson (by e-mail)
N. DiMaria, Tucson Electric Power
04/03/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: D09-0005 LOWE’S STAGING AREA/REVISED DEVELOPMENT PLAN
DATE: April 2, 2009




The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Label project number on all sheets.
Delete book and page legal from Location Map.
Spell out Boulevard for Speedway on sheet 2 and top right of sheet 3.
Delete Pad 3 from sheets 3 and 8.
04/06/2009 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

April 6, 2009

Thomas Sayler-Brown
SBBL Architecture + Planning
1001 North Alvernon Way, Suite 105
Tucson, Arizona 85711

Subject: D09-0005 Lowe's Staging Area Development Plan

Dear Thomas:

Your submittal of February 23, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 6 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

6 Copies Revised Development Plan (Landscape, Engineering, Zoning, TEP, Addressing, DSD)

4 Copies Revised Landscape Plan (Landscape, Engineering, Zoning, DSD)






Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 620-0535
dp-resubmittal