Permit Number: D08-0049
Parcel: 140292000

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D08-0049
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
01/21/2009 JIM EGAN COT NON-DSD FIRE Approved
01/30/2009 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: American Red Cross - Regional Blood Distribution Center
D08-0049
Development Plan (2nd Review)

TRANSMITTAL DATE: January 30, 2009

DUE DATE: February 18, 2009

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is October 15, 2009.

2. Zoning acknowledges that a lot combo is required. Provide documentation that shows that the lot split, the 46.96 feet of lot 9, was approved by The City of Tucson. The lot combo and split will need to be approved prior to approval of the development plan. D.S. 2-05.2.4.A It appears that some type of lot split is proposed. Sheets C1.1 and C1.3 appear to show forty seven (47) of parcel 140-29-202A as part of this project, please clarify. If a lot split is proposed it must be processed and approved by The City of Tucson prior to approval of this development plan.

3. This comment was not addressed. Zoning acknowledges that detail 12, sheet CD1.2 has been provided for the "NEW SECURITY SWINGING GATES" called out under keynote 27 on sheet C1.1. This comment was in regards to the "NEW SLIDING GATE" called out under keynote 22 on sheet C1.1.Provide the required dimensioned backup spur, or provided a note on the plan that the gate will remain open during regular business hours on the plan, for the proposed security gate called out under Keynote 22, both the east and west side. See D.S. 3-05.2.2.D for requirements.

4. D.S. 2-05.2.4.P The "ACCESSIBLE PARKING" calculation is not correct. Per the International Building Code (IBC) Section 1106.5 for every six or fraction of six accessible parking spaces, at least one shall be van-accessible. This said the number required for 8 accessible parking spaces is two (2). Based on detail 4 sheet CD1.2 all of the provided accessible parking meets the requirement for van-accessible there for the provided van-accessible would be eight (8).

5. Sheet C1.1 please clarify what the circles are that are shown just west of the proposed electrical transformer. If these are bollards or some type of vertical obstruction over 6" in height the adjacent parking space must be 10'-0" wide, see D.S. 3-05.2.1.3


6. Ensure that all changes to the development plan are reflected on the landscape plans.

7. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\cdrc\developmentplan\D08-0049dp-2nd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents.
01/30/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approv-Cond January 30, 2009

To: SCOTT EISENFELD
GLHN ARCHITECTS & ENGINEERS, INC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Chandubhai C. Patel, P.E., Civil Eng. Manager
Development Review Division ( Wastewater )

Subject: AMERICAN RED CROSS REGIONAL BLOOD DISTRIBUTION CENTER
Dev. Plan – 2nd Submittal
D08-049


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

Sheet 1: In the LEGEND, Add PRIVATE between NEW and SEWER to show that this symbol is for private sewers. This correction may be shown on the Mylar without having to resubmit the bluelines.

SUBJECT TO THE ABOVE, the PDEQ and the PCRWRD hereby CONDITIONALLY APPROVE the above referenced submittal of the Development Plan as received by us on January 16, 2009.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above comments, please do not hesitate to contact me.
01/30/2009 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D08-0049 Red Cross Regional Distribution 01/26/09

Reviewed: Development Plan

CROSS REFERENCE: Co9-82-106 & C15-88-01

NEIGHBORHOOD PLAN: General Plan

COMMENTS DUE BY: February 18, 2009

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

No Additional Comments - Complies With Planning Comments
Submitted on: November 13, 2008

REVIEWER: drcorral 791-4505 DATE: October 21, 2008
02/02/2009 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. The location of the 6-foot wrought iron fence is labeled incorrectly on the landscape plan (within the right-of-way at the street curb location) and the development plan. Note that, depending on the design of the fence, and due to the fact that when viewed at an angle the fence may appear as a nearly or completely opaque view obstruction, the fence may not be allowed within the sight visibility triangle as shown on the d.p. LUC 3.7.3.4, DS 3-01.5

2. Revise the Section numbers and the Township number to be correct for the location map on sheet G-1.
02/09/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
02/17/2009 LAITH ALSHAMI ENGINEERING REVIEW Approv-Cond Laith Alshami, Engineering and Floodplain Review, 02/17/2009,

TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: Red Cross Regional Dist.
D08-0049, T15S, R14E, SECTION 09

RECEIVED: Development Plan, Landscape Plan and Drainage Report on January 20, 2009

The subject submittal has been reviewed. The Drainage Report is acceptable for Development Plan purposes and it is herby approved. Additional drainage related information may be required with the grading plan submittal. The Landscape Plan is acceptable pertaining to Engineering and Floodplain Review. The Development Plan is recommended for conditional approval, pertaining to Engineering and Floodplain Review, subject to providing the following information on the Development Plan Mylar:

1. Keeping the 18" CMP proposed to drain the loading dock debris free may be difficult due to the length of the pipe. Provide a clean out or a manhole in the middle of the pipe to facilitate its maintenance.
2. Detail 4 on Sheet CD 1.3 has two different pipe slopes. Revise as needed.
3. Revise Detail 2 on Sheet CD 1.3 to show the 6" Orifice Plate on the inlet of the bleeder pipe.
4. Provide the tie between the basis of bearing and one of the subject parcel corners.
5. The refuse area detail (Detail 10 on Sheet CD 1.2) does not have the standard dimensions. Revise the detail according to the City's Standard Detail. A copy of the Standard Detail may be obtained from this Office.


RESUBMITTAL REQUIRED: Development Plan Mylar
02/23/2009 ANDY VERA ENV SVCS REVIEW Denied 1. CD1.2.10 - Refuse area detail
Require a minimum 10 ft x 10 ft inside clear container service area between the rear and side bollards and the front enclosure gates. DS 6-01.4.1.B
Add one additional side wall bollard (to each side) spaced 4 ft from front/existing side bollard.
The 1 ft dimension must be measured from the inside face of the bollard to the inside face of the CMU wall, not to center as currently shown.

2. The 4 ft side opening of the enclosure must be equipped with a gate to complete required screening. DS 6-01.4.1.M

Please provide corrections/revisions on resubmittal.

If you have any questions you may contact Andy Vera at (520) 791-5543 ext 1212 or e-mail: Andy.Vera@tucsonaz.gov
02/25/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: D08-0049 RED CROSS REGIONAL DISTRICT/REVISED DEVELOPMENT PLAN
DATE: 2/23/09



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Legal description in Title Block on sheet 1 needs to match all sheets.
Delete address from Title Block , sheet 6.
Delete “under construction”, bottom of sheets 8 and 9.

NOTE: Due to access off of Hemisphere Loop, address for this Development Plan will change upon approval.
02/25/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207


JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: D08-0049 RED CROSS REGIONAL DISTRICT/REVISED DEVELOPMENT PLAN
DATE: 3/11/09



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
02/26/2009 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES


February 26, 2009

Scott Eisenfeld
GHLN Architects and Engineers
2939 East Broadway Blvd.
Tucson, Arizona 85716

Subject: D08-0049 Red Cross Regional Distribution Center Development Plan

Dear Scott:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off.

1 Rolled blueline COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). Please include applicable sheets from any other concurrent reviews.
AND
1 Rolled blueline set of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra rolled blueline set that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the rolled bluelines to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html. BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

PRIOR TO SUBMITTING THE FINAL PLANS TO THE CDRC OFFICE, THE PLANS MUST BE REVIEWED AND APPROVED BY ESD AND PC ADDRESSING. THE APPROVALS MUST BE IN WRITING (E-MAIL IS OKAY).

Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 795-182