Permit Number: D08-0048
Parcel: 13815005D

Address: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D08-0048
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/07/2009 MATT FLICK ENGINEERING REVIEW Denied DSD Engineering recommends DENIAL of the development plan until an acceptable conservation easement (or other agreement or form of document) is worked out. The submitted document appears to put the onus for maintenance upon the City and does not give the City sufficient means of access to the property.

DSD Engineering has no objection to the form and content of the development plan and drainage report.

RESUBMITTAL REQUIRED: Conservation Easement
07/07/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
07/09/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Denied July 7, 2009

To: GREGORY CARLSON
GREG CARLSON ENGINEERING, LLC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6719), representing the Pima County
Departments of Regional Wastewater Reclamation Department and Environment Quality

Subject: MEDINA ROAD INUSTRIAL PROPERTY
Dev. Plan – 2nd Submittal
D08-048


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

We will send to your office via e-mail, a .pdf file containing a Sewer Service Agreement for the proposed number of fixture unit equivalents. Upon receiving Owner(Applicant) or Title Company with address and Trust # information from you we will generate the SSA. Three originals will need to be printed out from this file for notarized signatures by the Owner of Record. The three signed originals of the Agreement must be returned to this office in order to satisfy the necessary requirements needed to approve the Mylars of the development plan.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents. Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the third(3rd) submittal. A check for the review fee of this submittal in the amount of $39.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.
If the number of sheets changes, please adjust the review fee accordingly. If you have any questions regarding the above-mentioned comments, please contact me.
07/20/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: D08-0048 MEDINA ROAD INDUSTRIAL PROPERTY/REVISED DEVELOPMENT PLAN
DATE: 7/15/09



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Fill in all Dockets and Pages.
Delete Site Address 225 E. Medina Rd. Tucson, AZ 85756.
Include legal descriptions on this Development Plan.
07/21/2009 FERNE RODRIGUEZ UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#205173 July 21, 2009




Dear Mr McMurtrie :

SUBJECT: Medina Road Industrial Property
D08-0048


Tucson Electric Power Company has reviewed and approved the development plan submitted July 17, 2009. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. All relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Richard Harrington
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8726

Please call the area Designer Warren McElyea at (520) 918-8268, should you have any questions.


Sincerely,



Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
City of Tucson (Email only)
cc:W. McElyea
07/22/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. The pedestrian access to the dumpsters are not required to be accessible. Please delete the detectable warnings in these four locations.
2. The marked crossing from Medina Road does not comply with ICC/ANSI 405.12, "Detectable warnings shall be 24" wide in the direction of travel..." Relocate the crossing futher West and position the crossing to be perpendicular to the traffic flow.
3. The concrete pedestrian refuge areas behind the buildings may be considered "not for pedestrian circulation" pending the following modifications and considerations:
a. The marked crossing from Buldings 1 and 2 must be relocated to the West crossing area at the front of the buildings.
b. All Stairs are required to comply with the 2006 IBC, Section 1009 including handrails. Please provide a large scale detail showing compliance and configuration.
c. Please provide a statement on the drawings to the effect that if a future tentant is required by code to have a rear exit, that all modifications to the concrete refuge areas will be made for to comply with 2006 IBC, Section 1104 and ICC/ANSI 117.1, Section 402, Accessible Routes.
4. Sheet 4 of 4, TYPICAL CURB ACCESS RAMP detail: As per ICC/ANSI 117.1, Section 406.3, curb ramp flared sides shall be no steeper than 1:10. Please note such on detail.
07/28/2009 TERRY STEVENS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: D08-0048
Medina Road Industrial Property
Development Plan

TRANSMITTAL: 07/28/2009

DUE DATE: 07/31/09

COMMENTS:

1. The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

2. DS 2-05.2.3.B & DS 2-05.2.4.G Provide recording docket and page information for the PRA / NUOS easement.

Provide recording docket and page information for the new or proposed water easement (keynote #14).

Both easements must be recorded and docket and page information provided on the development plan prior to approval


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\developmentplan\D08-0048dpca.doc
07/30/2009 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
07/30/2009 ANDY VERA ENV SVCS REVIEW Approved
07/31/2009 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Revise sheets 1-3 to eliminate or revise the references to a "vegetative Screening barrier" to distinguish these areas from the required screening per LUC 3.7.2-I. The screening requirement for the site is met by the proposed 5' cmu wall located behind the street landscape border in accordance with LUC 3.7.3.2.C.

2) Fifty (50) percent or more of the area of the street landscape border must be covered with shrubs or vegetative ground cover. The required ground coverage must be achieved within two (2) years from the date of planting. LUC 3.7.2.4.A.5
Trees are not included in the calculation per
DS 2-06.3.4.D.2, only shrubs and vegetative groundcover are counted. Revise as necessary.

3) Revise the landscape plan to correct the landscape border area calculation for LUC purposes.

Determine Area: The width of the street landscape border is a minimum of ten feet in width and includes all of the area (even rip-rap) between the street property line and the required street screening. The border is greater than ten feet in width in some areas. DS 2-06.3.4.C.2

The length is the linear feet of street frontage, except for the width of the ingress/egress location.

300'-35' for driveway=265 X at least 10' and up to 15+'

The actual area per the development plan dimensions likely exceeds 3200 sq. ft. and includes rip-rap areas that may not be directly planted.

4) Provide the recording information for the PRA/NUOS conservation easement in the reserved space on the Development Plan.

5) The vehicular use area must be provided with a barrier designed to prevent parked vehicles from extending beyond the property lines; damaging adjacent landscaping, walls, or buildings and to prevent vehicles from driving onto unimproved portions of the site. per DS 3-05.2.3.C. Revise the plans as necessary to protect the walls that are adjacent to the vehicular use area along Medina street.

6) Slopes for basins less than three feet are to be no steeper than 3:1 for unprotected slopes and 2:1 for protected slopes in order to comply with the Technical Requirements of DS 10-01.4. which can be modified with a DSMR where appropriate. LUC 3.7.4.3.A.
08/03/2009 JWILLIA4 ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

August 3, 2009

James McMurtrie
Greg Carlson Engineering, LLC
1521 East Broadway Blvd.
Tucson, Arizona 85719

Subject: D08-0048 Medina Road Industrial Property Development Plan

Dear James:

Your submittal of October 17, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 7 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

6 Copies Revised Development Plan (Engineering, Wastewater, Addressing, HC Site, Landscape, DSD)

3 Copies Revised Landscape Plan (Landscape, Engineering, DSD)

2 Copies Conservation Easement Documentation (Engineering, DSD)


Should you have any questions, please call me at 837-4919.

Sincerely,




John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/