Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: D08-0046
Parcel: 119215910

Address:
1740 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D08-0046
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/06/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207


AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO: CITY PLANNING
FROM: AUDREY FARENGA, ADDRESSING REVIEW
SUBJECT: D08-0046 WALGREENS/REVISED DEVELOPMENT PLAN
DATE: 09/30/09



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.





***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***
10/08/2009 LOREN MAKUS ENGINEERING REVIEW Approved October 8, 2009
The Engineering Division recommends approval of this Developemnt Plan.
10/16/2009 ANDY VERA ENV SVCS REVIEW Approved
10/16/2009 RONALD BROWN ZONING HC REVIEW Approved
10/22/2009 TERRY STEVENS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: D08-0046
Walgreens
Development Plan

TRANSMITTAL: 10/22/2009

DUE DATE: 10/21/09

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is 10-02-09.

2. DS 2-05.2.3.B & DS 2-05.2.4.G Provide recording information (docket and page for all new easements and the abandonment of any easements. Must be completed and provided on the development plan prior to approval of the development plan.

In order to approve this plan conditionally concerning abandonment of the easements provide letters from TEP and the City of Tucson Water confirming that they are aware of and in agreement with the future abandonment.

3. DS 2-05.2.4.A This site contains three (3) separate parcels (Lots 2,3 &7) therefore you will need to show how the parcels can work as stand alone parcels if sold separately or provide a Pima County Tax Parcel Combo. Provide copies of documents with the next submittal.

Once the tax parcel combo has been completed remove from the plans the indicated property lines for lots 2,3,&7

In order to approve this plan conditionally concerning the lot combo, a copy of the tax parcel combo and recording a Covenant Regarding Development and Use of Real Property will be required prior to issuing of any building permits. Provide on the plan the recording docket and page for the covenant. A copy of the required covenant can be obtained on line at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/applications.html.

An application for a building permit must be completed and an activity number secured in order to be able to place a hold on the project until the above is completed.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\developmentplan\D08-0046-3dp.doc
10/23/2009 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES


October 23, 2009

Josh Fonger
Evergreen Devco
2390 E. Camelback Road #410
Tucson, Arizona 85016

Subject: D08-0046 Walgreens Development Plan

Dear Josh:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per ZONING, please submit the following documents for sign-off.

1 Rolled blue line COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). Please include applicable sheets from any other concurrent reviews.

1 Rolled blue line set of the Development Plan.

1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra rolled blue line set that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. The printing company will deliver the original rolled blue line to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html.
BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

Should you have any questions, please call me at 837-4919.



Sincerely,





John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (602) 567-7176