Permit Number: D08-0044
Parcel: 13711429H

Address: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D08-0044
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
04/17/2009 JASON GREEN ENGINEERING REVIEW Approv-Cond DATE: April 17, 2009
SUBJECT: Hanson's Good To Go Development Plan- 3rd Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 137-11-429H, T155S R13E Sec03 Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: D08-0044


SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised Development Plan, Drainage Report (Olsson Associates, Inc., 09SEP08 revised 04NOV08, 06APR09) and Geotechnical Engineering Evaluation and Addendum #1 (Pattison Evanoff Engineering, LLC, 03SEP08, 06APR09). Engineering Division recommends conditional approval of the Development Plan at this time. The Drainage Report was reviewed for Development Plan purposes only. The following item needs to be addressed prior to Mylar approval:


DEVELOPMENT PLAN:

1) Complied.

2) Complied.

3) Complied.

4) Complied.

5) Complied.

6) Complied.

7) Complied.

8) Complied.

9) Complied.

10) Complied.

11) DS Sec.2-05.2.4.K: Acknowledged. However the 3rd submittal shows that the 2 onsite handicap access ramps adjacent to the driveway access of Midvale Park Road are per keynote #5 (Standard Detail #207) not the required ANSI detail per keynote #37. Revise to reflect that all onsite ramps meet the required ANSI handicap requirements. Comment can be addressed with Mylar submittal.

12) Complied.

13) Complied.

14) Complied.

15) Acknowledged.

16) Complied.

17) Complied.

a) Complied.

b) Complied.

c) Complied.

d) Complied.

18) Complied.


DRAINAGE STATEMENT:

19) Complied.

20) Complied.


GEOTECHNICAL REPORT:

21) DS Sec.10-01.3.5.1.3.a and 10-02.14.2.6: Provide a revised Geotechnical Report evaluation or addendum that addresses the following requirements that were not fully addressed with this submittal:

a) Complied.

b) Acknowledged. The Development Plan now shows a basin bleed pipe and the Drainage Report has been updated to show that the basin drains within the allotted time limit.

c) Complied.

d) Complied.


GRADING PLAN:

22) A grading permit application (T08BU02067) has been submitted for this project and comments will be posted under that activity for grading plan review comments. A grading permit may not be issued prior to stamped Development Plan approval.

23) Please ensure that the grading plan will be consistent with the Development Plan, Drainage Report, and Geotechnical Report.

24) Arizona Pollutant Discharge Elimination System (AZPDES) is applicable to this project. Stormwater Pollution Prevention Plans (SWPPP) and text addressing stormwater controls for all areas affected by construction activities related to this development has been submitted with the grading plan and will be reviewed under that activity. For further information, visit www.adeq.state.az.us/environ/water/permits/stormwater.html.


GENERAL COMMENTS:

Provide the above corrections at Mylar submittal. The final Development Plan Mylar will not be approved until the above comment is addressed. If any department requires additional changes that significantly change the design of the plan Engineering will require an additional review.

For any questions or to schedule meetings call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services
04/30/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207


JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: D08-0044 HANSON’S GOOD TO GO/REVISED DEVELOPMENT PLAN
DATE: 4/29/09



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
05/04/2009 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Hanson's Good To Go
D08-0044
Development Plan (2nd Review)

TRANSMITTAL DATE: May 4, 2009

DUE DATE: May 6, 2009

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

2. D.S. 2-05.2.4.P The proposed landscape planters along the east parking area cannot encroach into the 18'-0" vehicle parking space more than 2'-6", see D.S. 3-05.2.3.C.2 and Figure 5.

3. D.S. 2-05.2.4.P The vehicle parking space located to the north of the proposed trash enclosure is required to be 10'-0" see D.S. 3-05.2.1.B.3.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\cdrc\developmentplan\D08-0044dp.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
05/08/2009 CDRC1 UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#204001 May 1, 2009


Olsson Associates
Attn: Cardell Andrews
3025 W Ina Rd.
Tucson, AZ 85741

To Cardell Andrews :

SUBJECT: Hanson's Good To Go - Resubmittal
D08-0044


Tucson Electric Power Company has reviewed and approved the development plan submitted April 24, 2009. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. The customer is responsible for the new trenching to relocate them as well as the relocation cost.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Rich Harrington
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-918-8726

Please call the area Designer Mike Kaiser at 520-918-8244, should you have any questions.



Sincerely,



Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
cc: City of Tucson, (Email only)
Mike Kaiser, Tucson Electric Power
05/13/2009 CDRC1 ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

May 13, 2009

candrews@oaconsulting.com

Subject: D08-0044 Hanson's Good to Go Development Plan

Dear Cardell :

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off:

One rolled bond copy of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). Please include applicable sheets from any other concurrent reviews.

Two Copies revised Geotechnical Report Evaluation or Addendums and 1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

Additional file copies will be made from the complete set. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form The print company will deliver the rolled plans to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK.

The link to the stamp is: http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html.

PLANS WITHOUT THE STAMP WILL BE RETURNED FOR CORRECTION.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/