Permit Number: D08-0040
Parcel: 13317062G

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D08-0040
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
09/12/2008 MARTIN BROWN COT NON-DSD FIRE Approved
09/17/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. All lettering and dimensions shall be the equivalent of 12 point (0.12") or greater in size. Revise the text for the lot dimensions and bearings on the landscape and irrigation plans (sheet L-1 and L-2) to meet this minimum standard.
DS 2-05.2.1.C

2. An unpaved area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree. Two trees to be located in front (north side) of the building are shown planted in concrete pavers. Revise to provide minimum planting area and dimension to demonstrate compliance.
LUC 3.7.2.3.A.1.c, DS 2-07.2.2.A.2.e

3. Areas where plants are susceptible to injury by vehicular traffic or parked vehicles must be protected by appropriate means, such as curbs, bollards, or low walls. Dimension the overhang distance, which must be a minimum of 2-1/2 feet for the required vehicle overhang area for the 5 parking spaces adjacent to the street landscape border. Note that the 2-1/2 foot vehicle overhang area may not be counted as part of the required street landscape border width. Wheelstop curbs may be required in these spaces if the proposed 10-foot street landscape border is otherwise encroached upon by parked vehicles. Also, vegetative screens may encroach up to 3 feet into the street landscape border. Revise the 30" high vegetative screen location in this area to demonstrate compliance. It may also be necessary to dimension the street landscape border widths separately on both sides of the sidewalk in order to demonstrate compliance clearly.
LUC 3.7.2.3.B, DS 3-05.2.3.C.1, DS 2-06.3.7.B.5.b

4. Place the development plan case number (D08-040) along with the DSMR and any other related case numbers in the lower right hand corner of all sheets of the development plan, landscape plan and native plant preservation plan.
DS 2-05.2.2.B.2

5. A 5-foot high screen wall is required along the south property line. Revise development plan accordingly and label the wall on the landscape plan. Indicate the wall location along the property line, its linear dimension, its height and the materials of construction.

6. Within a vehicular use area, one (1) canopy tree is required for each ten (10) motor vehicle parking spaces or fraction thereof. Revise parking lot canopy tree calculation to indicate that with 64 parking spaces proposed a total of 7 canopy trees are required. LUC 3.7.2.3.A.1
LUC Table 3.7.2-I, DS 2-07.2.2.A.3
09/17/2008 PETER MCLAUGHLIN ZONING REVIEW Denied 1. All lettering and dimensions shall be the equivalent of 12 point (0.12") or greater in size. Revise the text for the street names in the location map to meet this minimum standard. If there is not enough space for all street names at the location map scale, the names of the major streets and the streets bounding the site will suffice.
DS 2-05.2.1.C

2. Class 2 bicycle parking is to be located no more than 50 feet from the main building entrances and along the front side of the building as well as along other sides of the building that have entrances. DS 2-09.4.1

3. Once the DSMR has been approved, add the case number, date of approval and any conditions imposed to general note 3 on sheet 1.

4. Place the development plan case number (D08-040) along with the DSMR case number and any other related case numbers in the lower right hand corner of all sheets of the development plan, landscape plan and native plant preservation plan.
DS 2-05.2.2.B.2
09/17/2008 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved ADOT has NO COMMENT on this project

--------------------------------------------------------


Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
09/18/2008 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved
09/19/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
09/23/2008 FERNE RODRIGUEZ LANDFILL ENVIRONMENTAL SERVICES Passed
09/26/2008 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#203018 September 25, 2008


Greg Carlson Engineering, LLC
Attn: James McMurtrie
1521 E. Broadway Blvd.
Tucson, AZ 85719

To Mr. McMurtrie:

SUBJECT: Desert Bloom Medical Office Bl.
D08-0040


Tucson Electric Power Company has reviewed and approved the development plan submitted September 24, 2008 It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. There is an existing feeder line on the east side of the property within the (10) electric easement. The customer is responsible for the new trenching to relocate them as well as the relocation cost.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Please call the area Designer Nancy DiMaria at (520) 918-8267, should you have any questions.


Sincerely,



Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
cc: City of Tucson, (Email only)
N. DiMaria, Tucson Electric Power
09/30/2008 TIM ROWE PIMA COUNTY WASTEWATER Denied September 30, 2008

To: JAMES MCMURTRIE
GREG CARLSON ENGINEERING, LLC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: DESERT BLOOM MEDICAL OFFICE BUILDING
Dev. Plan - 1st Submittal
D08-040


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

This project will be tributary to the Roger Rd and Ina Rd Wastewater Treatment Facility via the Pantano Interceptor. Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The development plan for this project cannot be approved until a copy of this letter has been received by this office.

Sheet 1: Add a General Note that states:

THIS PROJECT WILL HAVE ______ EXISTING AND______ PROPOSED WASTEWATER FIXTURE UNIT EQUIVALENTS PER TABLE 13.20.045(E)(1) IN PIMA COUNTY CODE 13.20.045(E).

And fill in the blanks with the appropriate values.

Sheet 1: Add a General Note that states:

THE ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE PLAN, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT.

Sheet 1: Add a Permitting Note that states:

A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT.

Sheet 2: Provide documentation showing authority to connect to the private sewer line as shown on plan.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $100.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.



If you have any questions regarding the above-mentioned comments, please contact me.
10/01/2008 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: October 01, 2008

TO: DSD_CDRC@ tucsonaz.gov

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov


SUBJECT: D08-0040 Desert Bloom Medical Office Bl: Development Plan Review(9-11-08)



Staff has no comments.
10/01/2008 FERNE RODRIGUEZ OTHER AGENCIES PIMA ASSN OF GOVTS Approved CASE: D08-0040 DESERT BLOOM MEDICAL OFFICE BL: DEVELOPMENT PLAN

COMMENT: NO OBJECTIONS OR ADVERSE COMMENTS





Vehicle Trip Generation: Daily: 405 PM Peak: 42











Please call if you have questions or need additional information.





-------------------------------------------

KoSok Chae, Ph.D.



177 N. Church Ave., Suite 405

Tucson, AZ 85701



520-792-1093 x487 [tel]

520-620-6981 [fax]

www.PAGnet.org
10/06/2008 ANDY VERA ENV SVCS REVIEW Approv-Cond DP demonstrates adequate access and maneuverability within development for collection vehicle...enclosure detail okay.

1. This type facility will generate both refuse and recycle type waste. Recommend providing two single enclosures placed side by side directly at the southend of PAAL and retain existing enclosure area as a turnaround. This will allow to accomodate for both refuse and recycle waste.

If you have any questions you may contact Andy Vera at (520) 791-5543 ext 1212 or e-mail: Andy.Vera@tucsonaz.gov
10/08/2008 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: October 2, 2008
CDRC/Zoning Manager

SUBJECT: Desert Bloom Medical Office, 6452 E. Carondelet Drive
Development Plan D08-0040 (First Review)
T15S, R14E, Section 07

RESUBMITTAL REQUIRED: Development Plan and Drainage Report.

The Development Plan (DP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
3. The refuse enclosure cannot be placed in the floodway per Chap. 26-5.2.13 and D.S. 6-01.4.1F. Perhaps another location can be found for the enclosure.
4. A flood plain use permit is required.
5. Please provide property description per D.S. 2-02.2.1.3.
6. Please label lot dimensions and bearings per D.S. 2-02.2.1.5
7. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12. Provide a painted 4' wide sidewalk to the refuse enclosure.
8. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15.
9. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
10. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the TP/DP.
11. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
12. Show Development plan number (D08-0040) on all sheets per D.S. 2-02.2.1.29.
13. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. Please address.
14. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
15. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
16. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
17. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
18. "A grading permit and Stormwater Pollution Prevention Plans (SWPPP's) will be required for this project. Submit 2
19. sets of grading and SWPPP's with text, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans".

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. This review was performed and accepted for Development Plan purposes only.
3. The refuse enclosure cannot be placed in the floodway per Chap. 26-5.2.13 and D.S. 6-01.4.1F. Perhaps another location can be found for the enclosure.
4. Show the project address or administration address on the cover sheet of the DR.
5. If applicable, add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DR.


If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/6452 E. Carondelet Dr._CDRC
10/10/2008 FERNE RODRIGUEZ PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: D08-0040 DESERT BLOOM MEDICAL OFFICE BUILDING/DEVELOPMENT PLAN
DATE: 10/09/08



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Label project number on all sheets.
Delete parcel number for surrounding properties on all sheets.
Delete “Dr” from Shepherd Hills on location map.
Delete “Ave” from Corinth on location map.
Delete “St” from Printer Udell on location map.
Delete “St” from Marta Hillgrove on location map.
Delete “Ave” from Natachee on location map.
Delete western most “1st St” from location map.
Delete “Caribe Cir” from location map.
Correct Rosewood Ave to Rosewood St. on location map.




es
10/10/2008 FERNE RODRIGUEZ COT NON-DSD REAL ESTATE Approved No comment
10/10/2008 ED ABRIGO PIMA COUNTY ASSESSOR Passed
10/15/2008 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
10/20/2008 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: D08-0040
CASE NAME: Desert Bloom Medical Office Building
DATE SENT:

Items reviewed: Development Plan and Landscape Plan

Cross Reference Cases: N/A - not a rezoning
Area or Neighborhood Plan: Sewell-Hudlow Neighborhood Plan
Gateway/Scenic Route: N/A
Due Date: October 9, 2008

Comments:

There are no annexation or rezoning conditions. Staff has no comments, and the plan is approved. No resubmittal is required.

Joanne Hershenhorn, 791-4505
9/24/08
10/23/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

October 23, 2008

James McMurtrie
Greg Carlson Engineering, LLC
1521 East Broadway Blvd
Tucson, Arizona 85719

Subject: D08-0040 Desert Bloom Medical Office Development Plan

Dear James:

Your submittal of September 11, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 7 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

7 Copies Revised Development Plan (Zoning, Landscape, Wastewater, ESD, Engineering, Addressing, DSD)

4 Copies Revised Landscape Plan (Zoning, Landscape, Engineering, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)




Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 624-4197
dp-resubmittal