Permit Number: D08-0030
Parcel: 13727991E

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D08-0030
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
11/05/2008 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Holiday Inn Express - Valencia Road and Commerce Court
D08-0030
Development Plan (3rd Review)

TRANSMITTAL DATE: November 5, 2008

DUE DATE: December 1, 2008

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

2. The proposed landscape planters shown along the north side of the pedestrian circulation, between buildings 1 & 3, do not appear to provided sufficient space for a tree, see landscape comments.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\cdrc\developmentplan\D08-0030dp-3rd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat/development plan and additional requested documents.
11/13/2008 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approved November 12, 2008


To: Anthony Tsang
A.C. Tsang Engineering

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Chandubhai C. Patel, P.E., Civil Eng. Manager
Development Review Division ( Wastewater)

Subject: Holiday Inn Express Hotel
Dev. Plan – 3rd Submittal
D08-030


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The PDEQ and the PCRWRD approve the above referenced submittal of the Development Plan as received by us on October 28, 2008.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above comments, please do not hesitate to contact me.
11/19/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Approv-Cond By the way some of the landscape planters within the vehicle use area are dimensioned (from the outside of the planter areas) it is unclear that the minimum width and minimum square footage requirements are met. An unpaved area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree. Provide a detail which dimensions the minimum inside (unpaved) width and length of the smaller types of planter areas and add the square footage (min. 34 square feet) of the planter areas to the details.
LUC 3.7.2.3.A.1.c, DS 2-07.2.2.A.2.e
11/26/2008 ANDY VERA ENV SVCS REVIEW Approved
11/28/2008 ELIZABETH EBERBACH ENGINEERING REVIEW Denied DATE: November 28, 2008
TO: Patricia Gehlen; CDRC Manager
FOR: A. C. Tsang Engineering
PROJECT: Commerce Court Holiday Inn Express 3rd submittal
SUBJECT: Development Plan Engineering Review
LOCATION: 6401 S Midvale Park Rd, Ward 1
FEMA PANEL: 2238K X-unshaded
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: D08-0030

SUMMARY: The Holiday Inn Express revised Development Plan was reviewed by Engineering. The package included the revised Development Plan for the Holiday Inn Express, the revised drainage report, a geotechnical report, landscape plans, and response letters. Development Services Department Engineering Division does not recommend approval of the Development Plan at this time. The drainage report was reviewed for Development Plan purposes only.

DEVELOPMENT PLAN COMMENTS:
1) DS Sec.10-02.14.2.6: For clarification on detail section C-C, a stockpile area is indicated per the geotechnical report along the north side of the project. Include the stockpile height on the plans and revise topography accordingly, and show height of stockpile on detail section B.
2) DS Sec.2-05.2.4.H: Address the following drainage comments on the Development Plan:
a) Revise design of channel detail section C-C to reflect change of grades at stockpile.
b) DS Sec.2-03.2.4.L.7: Clarify by providing sections and details to address conveyance and erosion protection for flows exiting at concentration point northeast of the proposed building pad that cross the water easement.
c) DS Sec.2-05.3.2.A: A provision for water harvest area was provided along front of Hotel. Ponding is not accepted so close to buildings without meeting geotechnical engineering setback recommendations. Provide geotechnical recommendation for setback for proposed water harvesting area at the south side of proposed hotel.
d) Provide drainage report calculation for north channel.
3) DS Sec.2-05.2.4.H.4, DS Sec.2-05.3.1.H: Provide more general spot elevations on sheet 1 for clarification of grading concept that follows proposed drainage scheme. All drainage improvement areas should have conceptual grading spot elevations to meet minimum standards.
4) DS Sec.3-01.5.1.A.1: Assure sight visibility triangles are accurately depicted on Landscape plans and match development plan, and that the SVT along Commerce Court for south adjacent parcel is depicted, and Landscape Plans are revised. Trees may be located within existing and future sight visibility triangles only if clear of leaves and branches to a height of at least six feet above grade upon installation.
5) DS Sec.11-.01.9.2, DS Sec.10-02.2.3.1.5.G, DS Sec.2-05.2.4.H.5, DS Sec.2-05.2.4.P: Provide minimum setback at south and east property lines adjacent to Parcel 137-27-989A to reflect sufficient area for proposed building foundation construction and required grading setback. Otherwise provide construction access easement for offsite construction activity. Since a building is proposed downstream of the adjacent Parcel 137-27-989A, provide written permission from the appropriate property owner(s) of Parcel 137-27-989A for the proposed offsite improvements. City of Tucson can not approve off-site improvements that are proposed without authorization from the offsite parcel. Provide construction easements, authorization letters, and cross access easement documentation for Parcels 137-27-9870 and 137-27-989A; submit documentation (include parking agreement with a copy of the lease agreement with Parcel 137-27-989A) for the offsite improvement.

Resubmittal is required. Submit the revised Development Plan addressing all of the comments. Include the revised drainage report, the revised Development Plan, soils report, other documentation, and response letter thoroughly explaining each comment. If you have questions or would like to set up a meeting, call me at 837-4934.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services Department
12/04/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

December 4, 2008

Antony C. Tsang
A.C. Tsang Engineering Group Inc.
4626 East Fort Lowell Road, Suite S
Tucson, Arizona 85712

Subject: D08-0030 Holiday Inn Express Development Plan

Dear Tony:

Your submittal of October 30, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Development Plan (Landscape, Zoning, Engineering, DSD)

4 Copies Revised Landscape Plan (Landscape, Zoning, Engineering, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)

2 Copies Soils Report (Engineering, DSD)


Should you have any questions, please call me at 837-4919.



Sincerely,


Patricia Gehlen
CDRC Manager


All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 325-0979