Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - CDRC - DEV PLAN
Permit Number - D08-0028
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2008 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 08/26/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
| 09/03/2008 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 09/09/2008 | CDRC1 | PIMA COUNTY | WASTEWATER | Denied | September 9, 2008 To: RICHARD LOZANO PSOMAS Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department ___________________________ From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County Departments of Wastewater Management and Environment Quality Subject: ALBERTSONS EL RIO LOT 4 / TUCSON FEDERAL CREDIT UNION Dev. Plan - 2nd Submittal D08-028 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. 1. Sheet 1:Add General Note to read as follows: THIS PROJECT WILL HAVE ______ EXISTING AND______ PROPOSED WASTEWATER FIXTURE UNIT EQUIVALENTS PER TABLE 13.20.045(E)(1) IN PIMA COUNTY CODE 13.20.045(E). And fill in the blanks with the appropriate values. This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents. Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet. The next submittal of this project will be the third(3rd) submittal. A check for the review fee of this submittal in the amount of $39.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter. If the number of sheets changes, please adjust the review fee accordingly. If you have any questions regarding the above-mentioned comments, please contact me. |
| 09/09/2008 | CDRC1 | PIMA COUNTY | WASTEWATER | Denied | October 28, 2008 To: RICHARD LOZANO PSOMAS Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department ___________________________ From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County Departments of Wastewater Management and Environment Quality Subject: ALBERTSONS EL RIO LOT 4 / TUCSON FEDERAL CREDIT UNION Dev. Plan - 3rd Submittal D08-028 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted. Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality. Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution. If you have any questions regarding the above-mentioned comments, please contact me. |
| 09/09/2008 | CDRC1 | PIMA COUNTY | WASTEWATER | Denied | I have reviewed the Mylars for this project, and found them approvable from Wastewater viewpoint. C.C. Patel, P.E. Pima County DSD |
| 09/17/2008 | CDRC1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Approved | CASE: D08-0028, ALBERTSONS @ EL RIO LOT4: RESUBMITTAL - CDRC-DEV PLAN COMMENT: NO OBJECTIONS OR ADVERSE COMMENTS Vehicle Trip Generation: Daily: 1,234 PM Peak: 153 Please call if you have questions or need additional information. ------------------------------------------- KoSok Chae, Ph.D. 177 N. Church Ave., Suite 405 Tucson, AZ 85701 520-792-1093 x487 [tel] 520-620-6981 [fax] www.PAGnet.org |
| 09/19/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | September 19, 2008 D08-0028 Albertsons at El Rio Plaza Lot 4 Development Plan Second Review Resubmittal Required: None The Engineering Division does recommends approval of this development plan. If you have any questions or wish to set up a meeting I can be contacted at loren.makus@tucsonaz.gov. Loren Makus, EIT Senior Engineering Associate |
| 09/23/2008 | HEATHER THRALL | ZONING | REVIEW | Approv-Cond | CDRC TRANSMITTAL TO: Development Services Department, Plans Coordination Office FROM: Heather Thrall, Senior Planner PROJECT: D08-0028, Tucson Federal Credit Union at Albertson's Shopping Center 1740 W. Speedway Boulevard 2nd Review, Development Plan TRANSMITTAL DATE: September 23, 2008 DUE DATE: September 23, 2008 COMMENTS: CONDITIONAL APPROVAL 1. The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements. 2. Per DS 2-05.2.3.B. regarding easements: A) I acknowledge your pending abandonment of 1' NVAE at south lot line. Please note recordation docket and page. 3. Per DS 2-05.2.4.K, regarding pedestrian circulation: A) per last review: provide sidewalk/crosswalk connection from proposed sidewalk to existing sidewalk on north part of lot 4, to tie into pedestrian route to Albertson's store. It is not clear on page 3 how the pedestrian route from the bank will tie into the existing sidewalk route to Albertsons - at east side of lot. B) per last review: provide marked pedestrian route to the dumpster, 2-08.3.1. Within all development, a continuous pedestrian circulation path is required. This path must connect all public access areas of the development and the pedestrian circulation path located in any adjacent streets. The areas within the development which must be connected include, but are not limited to, all buildings, all bicycle and vehicle parking areas, all recreation areas, all dumpster areas. 3. Please note that depending upon responses, further review comments may be forthcoming. Should you have any questions on this review, I may be reached via email at Heather.Thrall@tucsonaz.gov or at 837-4951. C:\planning\cdrc\dp\D08-0028 tucson federal credit union near Albertsons 2.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan. |
| 09/24/2008 | ANDY VERA | ENV SVCS | REVIEW | Approved | |
| 09/25/2008 | GLENN HICKS | COT NON-DSD | PARKS & RECREATION | Approved | DATE: September 24, 2008 TO: DSD_CDRC@ tucsonaz.gov FROM: Glenn Hicks Parks and Recreation 791-4873 ext. 215 Glenn.Hicks@tucsonaz.gov SUBJECT: D08-0028 Albertsons at El Rio Lot 4(8-26-08) Approved. |
| 09/26/2008 | CDRC1 | UTILITIES | TUCSON ELECTRIC POWER | Approved | 4350 E. Irvington Road, Tucson, AZ 85714 Post Office Box 711, Tucson, AZ 85702 WR#197770 September 25, 2008 Psomas Attn: Pattie Davis 4626 E. Ft. Lowell Rd # 5 Tucson, AZ 85712 To Ms Davis: SUBJECT: Albertsons @ El Rio Lot 4 – Resubmittal D08-0028 Tucson Electric Power Company has reviewed and approved the development plan submitted September 11, 2008 It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development. Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. The customer is responsible for the new trenching to relocate them as well as the relocation cost. In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to: Tucson Electric Power Company Attn: Ms. Mary Boice New Business Project Manager P. O. Box 711 (DB-101) Tucson, AZ 85702 520-917-8732 Please call the area Designer Mike Kaiser at (520) 918-8244, should you have any questions. Sincerely, Henrietta Noriega Office Specialist Design/Build hn Enclosures cc: City of Tucson, (Email only) M. Kaiser, Tucson Electric Power |
| 09/29/2008 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Approv-Cond | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES September 29, 2008 Pattie Davis Psomas 800 East Wetmore Road, Suite 110 Tucson, Arizona 85719 Subject: D08-0028 Albertsons @ El Rio Lot 4 Development Plan Dear Pattie: The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off. 1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). AND 1 Double Matte right-reading Océ or Photo Mylar of the Development Plan. AND 1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan. The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options. PRIOR TO SUBMITTIAL TO THE CDRC OFFICE, THE MYLARS MUST BE REVIEWED AND APPROVD BY PIMA COUNTY WASTEWATER AND ADDRESSING. THE APPROVAL MUST BE IN WRITING (E-MAIL IS OKAY). TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html. Should you have any questions, please call me at 837-4919. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 292-1290 |
| 11/21/2008 | KAY MARKS | PIMA COUNTY | ADDRESSING | Approv-Cond | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 JENNIFER STEPHENS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL SUBJECT: D08-0028 ALBERTSONS AT EL RIO LOT 4/REVISED DEVELOPMENT PLAN DATE: 9/24/08 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval: 1.) Delete resubdivision information from title block on all sheets. 2.) Delete owner and docket/page information for surrounding parcels on all corresponding sheets. |
| 11/21/2008 | KAY MARKS | PIMA COUNTY | ADDRESSING | Approv-Cond | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 JENNIFER STEPHENS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL SUBJECT: D08-0028 ALBERTSON'S AT EL RIO LOT 4/REVISED DEVELOPMENT PLAN DATE: 11/19/08 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project. 1.) Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses. 2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection. |