Permit Number: D08-0007
Parcel: 13623007K

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D08-0007
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2008 JIM EGAN COT NON-DSD FIRE Approved
09/22/2008 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
09/26/2008 CDRC1 PIMA COUNTY WASTEWATER Approved September 26, 2008

To: Grant Gete
CDG Architects

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Chandubhai C Patel, P.E., Civil Eng. Manager
Development Review Division ( Wasterwater)

Subject: El Rio Health Center Southeast Clinic
Dev. Plan -3rd Submittal
D08-007


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The PDEQ the PCRWRD hereby approve the above referenced submittal of the development plan as received by us on September 16, 2008.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above comments, please do not hesitate to contact me.
09/29/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Approved
10/14/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/14/2008 ANDY VERA ENV SVCS REVIEW Approved
10/14/2008 PAUL MACHADO ENGINEERING REVIEW Approv-Cond To: Patricia Gehlen DATE: October 9, 2008
CDRC/Zoning Manager

SUBJECT: El Rio Health Ctr., 6950 E. Golf Links Rd.
Development Plan D08-0007 (Third Review)
T14S, R15E, Section 30

RESUBMITTAL REQUIRED: None.

Development Plan:

1. Conditional approval by engineering providing the following comments have been addressed.
2. (last/current review) The submittal differs from the Preliminary Development Plan (PDP) approved August 15, 2005. The use and building sizes changed, which may require Mayor & Council to revisit the rezoning case and conditions for C9-05-21. Send a letter to the Director of the Department of Urban Planning and Design (DUPD), asking if this project is a major change to the PDP and requires Mayor & Council attention. For staff to accept the resubmittal in for review, a letter of advisement from the DUPD Director is required. Zoning reviewed the plan in the event DUPD accepts the proposal. Should rezoning conditions change, note them on the resubmittal.
Your response to the above stated a letter would be provided from DUPD.

Drainage Report:
1. The DR has been accepted for DP review only.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/6950 E. Golf Links Rd. CDRC_3
10/15/2008 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: D08-007
El Rio Health Center Southeast Clinic, 6950 E. Golf Links
3rd Review, Development Plan,
rezoning case C9-05-21

TRANSMITTAL DATE: October 14, 2008

DUE DATE: October 15, 2008

COMMENTS:

1. Per the DUPD director the change of PDP is considered minor and no additional conditions have been added to the rezoning conditions authorized by the Mayor and Council. However this plan was previously reviewed based on the new use of Medical Service Outpatient. I have requested that Ronald Brown Commercial plans reviewer and HC/ADA expert been given an opportunity to review the plan based on the change of use. Please address Ron's comments in the same manner as all comments from all review agencies are addressed.

Previous Comment: (last/current review) The submittal differs from the Preliminary Development Plan (PDP) approved August 15, 2005. The use and building sizes changed, which may require Mayor & Council to revisit the rezoning case and conditions for C9-05-21. Send a letter to the Director of the Department of Urban Planning and Design (DUPD), asking if this project is a major change to the PDP and requires Mayor & Council attention. For staff to accept the resubmittal in for review, a letter of advisement from the DUPD Director is required. Zoning reviewed the plan in the event DUPD accepts the proposal. Should rezoning conditions change, note them on the resubmittal.
Your response to the above stated a letter would be provided from DUPD. Please include with resubmittal.

2. I have seen Ron Brown's comments relative to Accessibility and would encourage you to take the opportunity to discuss the comments he has placed in permits plus before re-submitting any plans through the CDRC process. Several comments have been made and can be of major concern and must be addressed by revising the plan.

3. Zoning conditionally approves the development plan barring any changes necessary due to other review agency comments that affect zoning requirements.
10/15/2008 FERNE RODRIGUEZ COT NON-DSD REAL ESTATE Denied Please provide title reports for the three new parcels. Also, new legal descriptions and sketch for the right of way dedication based on the new property lines.

Sincerely,

Jim Stoyanoff
Property Agent
Real Estate Division
City of Tucson
201 N. Stone Ave. 6th Fl.
Tucson, Arizona 85701
(O) 520.837.6719
(F) 520.791.5641
Jim.Stoyanoff@tucsonaz.gov
10/15/2008 RBROWN1 ADA REVIEW Denied 15 OCTOBER 2008
D08-0007/EL RIO HEALTH CENTER - SOUTHWEST CLINIC
REVIEWED BY RON BROWN

ACCESSIBLE REVIEW
2006 IBC/ICC 117.1

DENIED: SEE COMMENTS BELOW

I. SHEET 1 of 4
A. NOTE 10: CHANGE GOVERNING ACCESSIBILITY CODE TO 2006 IBC, CHAPTER 11 AND ICC, ANSI 117.1 FOR PRIVATE PROPERTY. ADD THE FOLLOWING: "GOVERNING ACCESSIBILITY CODE FOR PUBLIC RIGHT OF WAY IS COT DOT".
B. ALL ACCESSIBLE SIGNAGE TO BE AS PER "PARK WISE" REQUIREMENTS.
II. SHEET 2 of 4:
A. SHOW RAMPS, SIGNAGE AND LOCATE "VAN ACCESSIBLE" SPACES FOR ALL ACCESSIBLE PARKING. PROVIDE A SURFACE MOUNTED CURB AT ALL ACCESSIBLE ROUTE AREAS THAT ARE FLUSH WITH THE VEHICLE AREAS EXCEPT AT PARKING AISLE ACCESS. REFERENCE ZONING REQUIREMENTS FOR ACCESSIBLE ROUTE .
B. THE NORTHERLY RAMPS FOR BOTH MARKED CROSSINGS DO NOT WORK, REDESIGN. PROVIDE A LARGE SCALE DETAIL SHOWING ALL DIMENSIONS, SLOPES, DETECTABLE WARNINGS AND ETC TO COMPLY WITH ANSI 117.1, SECTION 406.
C. THE MOST EASTERLY MARKED CROSSING DOES NOT WORK. STRAIGHTEN OUT CROSSING AND PROVIDE NEW RAMP SYSTEM AS PER ANSI SECTION 405.
D. PROVIDE A NEW REFERENCE FOR ALL INTERIOR SITE CURB AND SIDEWALK RAMPS ON PRIVATE PROPERTY TO REFERENCE COMPLIANCE WITH ANSI SECTION 405 AND/OR 406 AND NOT DOT 207.
III. SHEET 3 of 4:
A. DETAIL "A": SHOW 5' WIDE ACCESSIBLE ROUTE AND SIDEWALK RAMPS. PROVIDE A SURFACE MOUNTED CURB AT ALL ACCESSIBLE ROUTE AREAS THAT ARE FLUSH WITH THE VEHICLE AREAS EXCEPT AT PARKING AISLE ACCESS. REFERENCE ZONING REQUIREMENTS FOR ACCESSIBLE ROUTE.

I SUGGEST A MEETING TO REVIEW MY COMMENTS PRIOR TO SUBMITTAL OF FINAL MYLARS.

END OF REVIEW
10/15/2008 GLENN HICKS COT NON-DSD PARKS & RECREATION Approv-Cond DATE: October 10, 2008

TO: DSD_CDRC@ tucsonaz.gov

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov

CC: Patricia Gehlen

SUBJECT: D08-0007 El Rio Health Center SE Clinic: Resubmittal(9-17-08)



Conditionally approved, provided trail easement note meeting Parks and Recreation and Real Estate approval is shown on the final plat.
10/15/2008 GLENN HICKS COT NON-DSD PARKS & RECREATION Approv-Cond PARKS AND RECREATION DEPARTMENT COMMENTS

City of Tucson CDRC – Community Design Review Committee

CASE NAME & NUMBER: D08-0007, El Rio Health Center SE Clinic: DP
Submittal #: 3

COMMENTS SENT: 11/19/08 (based on a walk-through review)


Items reviewed: Development Plan and trail easement language

Related: rezoning - C9-05-21
CDRC – WASH Ordinance review
land use plan(s) – South Pantano Area Plan

Parks and Recreation Department Staff has reviewed this proposal and offers the following comments:


Plans are APPROVED – No additional submittal is required.


REVIEWER: Joanne Hershenhorn DATE: 11/18/08
























S:\PARKS_AND_RECREATION_DEPT\REVIEW_COMMENTS\CDRC_Cases\2008_ReviewsD08-0007b_El_Rio_Health_Center_SE.doc
10/31/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES


October 31, 2008

Grant Gete
CDG Architects
2102 North Country Club Road, #9
Tucson, Arizona 85719

Subject: D08-0007 El Rio Health Center Development Plan

Dear Grant:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on line comments, please submit the following documents for sign-off.

1 Rolled blueline COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). Please include applicable sheets from any other concurrent reviews.
AND
1 Rolled blueline set of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra rolled blueline set that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the rolled blueline to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

PRIOR TO SUBMITTING THE FINAL PLANS TO THE CDRC OFFICE, THEY MUST BE REVIEWED AND APPROVED BY PARKS AND RECREATION. THE APPROVAL MUST BE IN WRITING (E-MAIL IS OKAY).

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html. BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 798-3341