Permit Number: D08-0007
Parcel: 13623007K

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D08-0007
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/19/2008 JIM EGAN COT NON-DSD FIRE Denied Building 2 appears to exceed maximum allowable distances from fire hydrant(s). Refer to C.O.T amendments to 2006 IFC, section 508 for requirements. Install additional hydrant or install fire sprinklers.
06/26/2008 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D08-0007 EL RIO HEALTH CENTER SE CLINIC/REVISED DEVELOPMENT PLAN
DATE: 6/25//08



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
07/01/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied The landscape plan and native plant preservation plan cannot be reviewed because many of the layers appear to be "turned off" and are not shown on the plan drawing or in the legend. Landscape Plan must include parking layout, planter islands, landscape border information, etc. Revise plan to be complete. Previous review comments apply.
07/01/2008 CDRC1 PIMA COUNTY WASTEWATER Denied June 30, 2008

To: Grant Gete
CDG Architects

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: El Rio Health Center Southeast Clinic
Dev. Plan -2nd Submittal
D08-007


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

1. We will send to your office via e-mail, a .pdf file containing a Sewer Service Agreement for the proposed number of wastewater fixture unit equivalents. Three originals will need to be printed out from this file for notarized signatures by the Owner of Record. The three signed originals of the Agreement must be returned to this office in order to satisfy the necessary requirements needed to approve the Mylars of thedevelopment plan .

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

The next submittal of this project will be the third (3rd) submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above-mentioned comments, please contact me.
07/09/2008 JOSE ORTIZ COT NON-DSD TRAFFIC Denied July 9, 2008
ACTIVITY NUMBER: D08-0007
PROJECT NAME: El Rio Health Center SE Clinic
PROJECT ADDRESS: 6950 E Golf Links Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Development Plan; therefore a revised Development Plan is required for re-submittal.

The following items must be revised or added to the development plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. Based on City standards the taper shown on the plans is a little short. We need to see a taper of 100' which may impact your right of way dedications so we need to verify what right of way dedication is necessary prior to final approval by TDOT-Traffic.


If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
07/15/2008 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department, Plans Coordination Office

FROM: Heather Thrall, Senior Planner

PROJECT: D08-007, El Rio Health Center Southeast Clinic, 6950 E. Golf Links
2nd Review, Development Plan, rezoning case C9-05-21

TRANSMITTAL DATE: July 15, 2008

DUE DATE: July 17, 2008

COMMENTS:

1. (last/current review) The submittal differs from the Preliminary Development Plan (PDP) approved August 15, 2005. The use and building sizes changed, which may require Mayor & Council to revisit the rezoning case and conditions for C9-05-21. Send a letter to the Director of the Department of Urban Planning and Design (DUPD), asking if this project is a major change to the PDP and requires Mayor & Council attention. For staff to accept the resubmittal in for review, a letter of advisement from the DUPD Director is required. Zoning reviewed the plan in the event DUPD accepts the proposal. Should rezoning conditions change, note them on the resubmittal.
Your response to the above stated a letter would be provided from DUPD. Please include with resubmittal.

2. Legend has symbols missing next to descriptions and zoning line is missing on sht 2.

3. Per DS 2-05.2.4.P, please note total parking provided overall for the site.

4. Per DS 2-05.2.4.Q, regarding bicycle parking:
A) Per DS 2-09.4.1, class 2 bike parking required within 50' of building entry. Clarify if multiple tenants - disperse bike racks to serve multiple tenants.
B) Per DS 2-09.4.2, class 1 bike parking should be reasonably located for employee access. Clarify if there are multiple tenants - dispersing bike parking for multiple tenants.

5. Per DS 2-05.2.4.W, sight visibility triangles at Golf Links entry are not on sheet 2. Add and ensure sign outside SVT, thank you.

6. Please note further review comments may be forthcoming, depending upon responses provided. I may be reached at Heather.Thrall@tucsonaz.gov or at 837-4951.

C:\planning\cdrc\developmentplan\D08-007 el rio 2.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, and additional requested documents.
07/18/2008 FRODRIG2 COT NON-DSD REAL ESTATE Denied Per the comments submitted June 12, 2008 by Grant Getz with the development plan D08-0007, the development plan can not be approved with out the right of way dedications and linear park having taken place, as such the dedications will need to be completed prior to approval of the development plan. Please submit the legal descriptions for the rights of way and linear park to the Real Estate Division for processing of the Deed and Easement.



Sincerely,

Jim Stoyanoff
Property Agent
Real Estate Division
City of Tucson
201 N. Stone Ave. 6th Fl.
Tucson, Arizona 85701
(O) 520.837.6719
(F) 520.791.5641
Jim.Stoyanoff@tucsonaz.gov
07/18/2008 ANDY VERA ENV SVCS REVIEW Denied 1. Current positioning of enclosures is such that the flow for solid waste collection vehicle is impeded. DS 6-01.4.1.H.
Previous submittal had enclosure south of building 3 facing directly south and therefore worked.

2. Provide a generate note stating " One single property owner/mangement will be responsible for the management and maintenance of the solid waste collection services and storage areas to whole development."

3. Enclosure detail works.

Please provide corrections on resubmittal.

If you have any questions you may contact Andy Vera at (520) 791-5543 ext 1212 or e-mail: Andy.Vera@tucsonaz.gov
07/23/2008 PAUL MACHADO ENGINEERING REVIEW Approv-Cond To: Patricia Gehlen DATE: July 23, 2008
CDRC/Zoning Manager

SUBJECT: El Rio Health Ctr., 6950 E. Golf Links Rd.
Development Plan D08-0007 (Second Review)
T14S, R15E, Section 30

RESUBMITTAL REQUIRED: None.

Development Plan:

1. Conditional approval by engineering providing the following comments have been addressed.
2. Obtain documentation from Transportation that the proposed improvements on Langley Ave. are shown per the meeting between the Transportation dept, Development Services dept. and cdg architects.
3. Obtain and provide documentation for approval to connect the proposed 12" bleeder pipe from the ret. basin into the existing catch basin in Golf Links Road with COT-DOT/Permits & Codes located @ 201 N. Stone Ave. on the 4th floor.
4. Obtain and provide documentation for compliance for the following general notes: 7, 8, 13, and 26. Documentation was not found in the submittal.
5. Show all existing conditions on the plan. Perhaps the layer for the existing culture was turned off. Show on the mylar.

Drainage Report:
1. The DR has been accepted for DP review only.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/6950 E. Golf Links Rd. CDRC_2
08/01/2008 GLENN HICKS COT NON-DSD PARKS & RECREATION Denied PARKS AND RECREATION DEPARTMENT COMMENTS

City of Tucson CDRC – Community Design Review Committee

CASE NAME & NUMBER: D08-0007, El Rio Health Center SE Clinic: DP
Submittal #: 2

COMMENTS DUE: 7/17/08 COMMENTS SENT: 7/28/08


Items reviewed: Development Plan and Landscape Plan

Related: rezoning - C9-05-21
CDRC – WASH Ordinance review
land use plan(s) – South Pantano Area Plan

Parks and Recreation Department Staff has reviewed this proposal and offers the following comments:


NOT APPROVED – Please address the following, and resubmit the development plan:

A drainageway maintenance, and public, non-motorized, recreational trail easement must be granted to the City of Tucson over the 20-foot trail corridor. Please have the easement recorded. Identify the 20-foot easement and purposes, and show the recording information on the development plan.

As per our telephone conversation on 7/28/08, General Note 38 may be removed (as well as the last sentence under rezoning condition #5).

Feel free to call me at 837-6965 if you have any questions or want to discuss the comments above.




REVIEWER: Joanne Hershenhorn DATE: 7/28/08










S:\PARKS_AND_RECREATION_DEPT\REVIEW_COMMENTS\CDRC_Cases\2008_ReviewsD08-0007a_El_Rio_Health_Center_SE.doc
08/04/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

August 4, 2008

Grant Gete
CDG Architects
2102 North Country Club Road, #9
Tucson, Arizona 85719

Subject: D08-0007 El Rio Health Center Southeast Clinic Development Plan

Dear Grant:

Your submittal of June 18, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

10 Copies Revised Development Plan (Fire, Wastewater, Landscape, Real Estate, ESD, Traffic, Parks & Recreation, Engineering, Zoning, DSD)

5 Copies Revised Landscape Plan (Landscape, Parks and Recreation, Engineering, Zoning,DSD)

2 Copies Letter from Rezoning (Zoning, DSD)

2 Copies NPPO Plans (NPPO, DSD)




Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 798-3341