Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D08-0006
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2008 FRODRIG2 START PLANS SUBMITTED Completed
04/04/2008 CDRC1 PIMA COUNTY WASTEWATER Denied April 4, 2008

To: Steve Corrales
Steve Corrales Engineering

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: Academy of Math and Science
Dev. Plan - 2nd Submittal
D08-006


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Sheet 2: For the proposed private sewer include the following: length and slope of pipe.2nd request.

Sheet 2: The existing public sewer line south of the proposed public manhole is not shown on plan. This manhole needs to be labeled as public and should be numbered as MH#1. The other manholes proposed on site should be labeled as private and numbered one and two respectively.

Sheet 2:MH #5870-01 is mislabeled. It should be called out as 5867-02.

Sheet 2: Cleanout 5870*01 is not shown on plan in Lerdo Rd.

Sheet 2: Cleanout 5852*01 and MH 5852-01 are not shown on this plan just west of the project. The corresponding easement for this public sewer line is also not shown. The sewer line should match what is shown in the Legend on Sheet 1for an existing public sewer line.

Sheet 1: In the Legend on Sheet 1 there is no symbol shown for public sanitary sewer manhole.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $78.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.



If you have any questions regarding the above-mentioned comments, please contact me.
04/04/2008 CDRC1 PIMA COUNTY WASTEWATER Denied The mylar is approved.


Respectfully,

Tom Porter Sr. CEA
Pima County DSD
Wastewater Review
04/10/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Approved
04/23/2008 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Denied 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#194090 April 22, 2008


Krebs Carhuff Architect
Attn: Phil Carhuff
3149 E Prince Rd #151
Tucson, Arizona 85716

Dear Phil Carhuff:

SUBJECT: Academy of Math and Science- Resubmittal
D08-0006

Tucson Electric Power Company (TEP) has reviewed the plan submitted April 11, 2008. TEP is unable to approve the plan at this time. There are existing electrical facilities within the boundaries of this project.
**Identify all existing TEP facilities within the mapped area of the development (both on site and off site) including but not limited to overhead and underground electric lines, utility poles, and pad mounted equipment. Specifically the TEP facilities are not mapped correctly on the development plan, check pole locations, overhead & underground conductor routes and identify all TEP facilities on the plan.

Enclosed is a copy of a TEP facility map showing the approximate location of the existing facilities. All costs associated with the relocation of the facilities in conflict will be billable to the developer.

Please resubmit two revised bluelines to City of Tucson for TEP’s review. You may contact the area Designer, Steve Garcia at 917-8739 should you have any questions.

Sincerely,



Henrietta Noriega
Office Specialist

lm
Enclosure
cc: City of Tucson, Email
S. Garcia, Tucson Electric Power
04/23/2008 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Denied 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#194090 May 7, 2008


Krebs Carhuff Architect
Attn: Phil Carhuff
3149 E. Prince Rd. #151
Tucson, AZ 85716

Dear Mr.Carhuff: :

SUBJECT: Academy of Math and Science – Resubmittal
D08-0006


Tucson Electric Power Company has reviewed and approved the development plan submitted April 11, 2008. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.

The customer is responsible for the new trenching to relocate them as well as the relocation cost.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Please call the area Designer Steve Garcia at (520) 917-8739, should you have any questions.


Sincerely,



Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
cc: City of Tucson, (Email only)
S. Garcia, Tucson Electric Power
04/24/2008 PAUL MACHADO ENGINEERING REVIEW Approved
04/25/2008 ANDY VERA ENV SVCS REVIEW Approved
04/28/2008 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department, Plans Coordination Office

FROM: Heather Thrall, Senior Planner

PROJECT: Academy of Math & Science, 435 W. Valencia Road
New Secondary School
Development Plan, 2ndReview

TRANSMITTAL DATE: April 28, 2008

DUE DATE: April 28, 2008

COMMENTS:

1. Per DS 2-05.2.2.A.1, (last review) list name, address & phone of developer.

2. (last review) the plan shows a "new property line" at the north side of the site. Present documentation that the lot split/reconfiguration of lot lines has been done with city DSD staff review and approval. (Staff reviewed the plan with the idea that the "new lot line" position shown on the last plan will be the actual lot line in final outcome and that the calculations provided reflect that)

3. Per DS 2-05.2.4.N, Regarding building height: (last review)
A) note on drawing what the type of roof is - pitched or flat with parapet?
B) provide note "building height is measured from finished design grade to (specify flat roof with parapet or to ridge and midpoint of pitch) "
C) you have 3 different building heights noted - in building footprint on drawing, in setback and height notes - clarify what is maximum building height proposed.

4. Per DS 2-05.2.4.Q, and 2-09.4.1, ALL class 2 bike parking must be provided within 50' of the main entry to the building. Shift bike parking racks closer to entry.

5. Per DS 2-05.2.4.U, in a separate heading, LIST applicable conditions of rezoning C9-72-57 on sheet 1. Staff understands the following are applicable: A, C, D4, E, F. (I acknowledge that you have provided a list of how the conditions will be met, thank you)

6. Please note further review comments may be forthcoming, depending upon responses provided. I may be reached at Heather.Thrall@tucsonaz.gov or at 837-4951.


C:\planning\cdrc\developmentplan\D08-0006 Math & Science 2.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional lot line reconfiguration documentation.
04/28/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES


April 28, 2008

Phil Carhuff
Krebs Carhuff Architect
3149 East Prince Road, #151
Tucson, Arizona 85706

Subject: D08-0006 Academy of Math and Science Development Plan

Dear Phil:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

PRIOR TO SUBMITTING THE MYLARS TO THE CDRC OFFICE, THEY MUST BE REVIEWED AND APPROVED BY TEP AND WASTEWATER. THE APPROVAL MUST BE IN WRITING (E-MAIL IS OKAY).

Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager