Permit Number: D08-0003
Parcel: 141110300

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D08-0003
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2010 TERRY STEVENS ZONING REVIEW Approved
01/06/2010 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Approved COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

January 14, 2010

John A. Evans
John A. Evans and Associates, Inc.
5450 N. Sabino Highlands Place
Tucson, Arizona 85749

Subject: D08-0003 Old Vail Road Industrial Center Development Plan

Dear John:

Your submittal of January 24, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 2 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

2 Copies Revised Development Plan (Landscape, PDSD)

2 Copies Revised Landscape Plan (Landscape, PDSD)

Should you have any questions, please call me at 837-4919.


Sincerely,





John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (520) 749-1521
01/06/2010 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Approved COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES
*** REVISED ***

January 20, 2010

John A. Evans
John A. Evans and Associates, Inc.
5450 N. Sabino Highlands Place
Tucson, Arizona 85749

Subject: D08-0003 Old Vail Road Industrial Center Development Plan

Dear John:

The above referenced development plan has been APPROVED by the Community Design Review Committee. Please submit the following documents for sign-off.

1 Rolled blue line COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). Please include applicable sheets from any other concurrent reviews.

1 Rolled blue line set of the Development Plan.

1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra rolled blue line set that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. The printing company will deliver the original rolled blue line to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html.
BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

Should you have any questions, please call me at 837-4919.



Sincerely,





John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (520) 749-1521
12/04/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
12/11/2009 LAITH ALSHAMI ENGINEERING REVIEW Approved Laith Alshami, Engineering and Floodplain Review, 12/10/2009,

TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: Old Vail Rd Industrial Center
D08-0003, T15S, R15E, SECTION 21

RECEIVED: Development Plan and Drainage Report on December 07, 2009

The subject submittal has been reviewed. The approval conditions for the Development Plan have been satisfactorily addressed. The Development Plan is hereby recommended for approval pertaining to Engineering and Floodplain Review. The Drainage Report and Landscape Plan are also acceptable and hereby approved.
12/31/2009 JOE LINVILLE LANDSCAPE REVIEW Approved 1) Basin slopes are required to have slopes no steeper than 4:1 where depths are three feet or greater. Slopes for basins less than three feet are to be no steeper than 3:1 for unprotected slopes and 2:1 for protected. DS 10-01.4 (P.78 of SDRM)

LUC 3.7.4.3 provides the landscape requirements for basins. The section infers a natural configuration of the basin and directs us to DS 10-01.0 for the specific design criteria.
Importantly, it also establishes basins as multi-use areas providing both an area designed to meet detention/retention requirements and an area for visually appealing landscape areas. (see p. 1 of the SDRM Objectives and Goals)

DS 10-01.4. The different types multi-use areas and the concepts for each are discussed in the SDRM manual.
They include Project Amenity, Active Recreation, Passive Recreation, Urban Open Space, Native Plant Communities, Water Harvesting, Wildlife Habitat

The LUC requirement mandates that the basin serve as a landscaped space, which places it in the category of a project amenity, among others.

The plans require revision to comply with Development Standards. However, a Development Standard Modification Request could be supported.

We did notice that the plant selected for use in the basin would be completely submerged at times when the basin is full and suggest that the trees may fare better on sides slopes for a basin that deep.

Resubmittal of all Plans is required.