Permit Number: D08-0001
Parcel: 110162190

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: REVISION - DEV PLAN

Permit Number - D08-0001
Review Name: REVISION - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
04/09/2009 JIM EGAN COT NON-DSD FIRE Approved
04/14/2009 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Costco Addition
D08-0001
Development Plan (Revision)

TRANSMITTAL DATE: April 14, 2009

DUE DATE: April 21, 2009

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section conditionally approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

2. The sidewalk area located just south of the proposed 12 x 35 loading space needs to extend west an additional four (4) feet, similar to what was shown on the last approved DP.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

I:\planning\cdrc\developmentplan\2008\D08-0001-4th.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents.
04/15/2009 LAITH ALSHAMI ENGINEERING REVIEW Approved Laith Alshami, Engineering and Floodplain Review, 04/15/2009,

TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: Costco Addition
D08-0001, T13S, R14E, SECTION 36

RECEIVED: Development Plan and Drainage Statement on April 08, 2009

The subject project has been reviewed. The revised Development Plan is acceptable and it is recommended for a approval pertaining to Engineering and Floodplain Review.
04/23/2009 ANDY VERA ENV SVCS REVIEW Approved
04/29/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approv-Cond April 28, 2009

To: Nathan Menard
Mulvanny G2 Architect

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Chandubhai C. Patel, P.E., Civil Eng. Manager
Development Review Division (Wastewater)

Subject: COSTCO WHOLESALE, Store # 407 Expansion
Deevelopment Plan – 4th Submittal, D08-001


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

Sheet DR-1.1: Show the required 35’ easement for the proposed public sewer and its recordation information.

Sheet DR-1.1: You are proposing to connect the new 8-in sewer line to an existing 36-in sewer in Grant Road. Although the sewer improvement plan is accepted by PCRWRD for this proposal, it is contingent upon getting the Flow Management Plan approved. Considering the costs of manhole construction, the flow management and traffic control, you might not implement this proposal. If that happens, this Development Plan will need a revision.

SUBJECT TO THE ABOVE, the PDEQ and the PCRWRD hereby CONDITIONALLY APPROVE the above referenced submittal of the development plan as submitted on April 07, 2009.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.
04/29/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approv-Cond May 8, 2009

To: Nathan Menard
Mulvanny G2 Architect

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Chandubhai C. Patel, P.E., Civil Eng. Manager
Development Review Division (Wastewater)

Subject: COSTCO WHOLESALE, Store # 407 Expansion
Deevelopment Plan –Revision 1 Submittal, D08-001


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The PDEQ and the PCRWRD hereby approve the REVISED Development Plan received by us on 05-08-09. This approval VOIDS the conditional approval dated 04-28-09.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.
05/01/2009 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES


May 1, 2009

Michael Pniewski
WRG Design Inc.
9977 N. 90th Street, Ste 350
Scottsdale, AZ 85258

Subject: D08-0001 Costco Addition Revised Development Plan

Dear Michael:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the online comments, please submit the following documents for sign-off.

1 Rolled blueline COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). Please include applicable sheets from any other concurrent reviews.
AND
1 Rolled blueline set of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra rolled blueline set that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the rolled bluelines to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html. BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

PRIOR TO SUBMITTAL TO THE CDRC OFFICE, THE PLANS MUST BE REVEIWED AND APPROVED BY PCWWM. THE APPROVAL MUST BE IN WRITING (EMAIL IS OKAY).

Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager