Permit Number: D07-0045
Parcel: 12307229B

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D07-0045
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

January 4, 2008

Leo Katz
Leo R. Katz, Architect
2415 East 7th Street
Tucson, Arizona 85719

Subject: D07-0045 Speedway Office Development Plan

Dear Leo:

Your submittal of November 9, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

9 Copies Revised Development Plan (Landscape, DUPD, Addressing, Fire, Wastewater, Zoning, Engineering, Real Estate, DSD)

5 Copies Revised Landscape Plan (Landscape, DUPD, Zoning, Engineering, DSD)

2 Copies Revised NPPO Plan (Landscape, DSD)

2 Copies Color, dimensioned building elevations (DUPD, DSD)




Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 325-3904 (call first)
11/09/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
11/16/2007 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved ADOT has NO COMMENT on this project
D07-0045
SPEEDWAY OFFICE

--------------------------------------------------------


Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
11/19/2007 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)
FROM: Gary Ault, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: November 16, 2007


RE: Assessor’s Review and Comments Regarding DEVELOPMENT PLAN
D07-0045 SPEEDWAY OFFICE T141405

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS:
THANK YOU FOR YOUR SUBMITTAL. IF YOU HAVE ANY QUESTIONS PLEASE CALL ROSANNA WERNER AT 740-4390



ROSANNA WERNER
11/19/2007 CDRC1 OTHER AGENCIES PIMA ASSN OF GOVTS Completed >>> "Aichong Sun" <asun@pagnet.org> 11/19/2007 11:11 AM >>>
CASE: D07-0045, SPEEDWAY OFFICE: DEVELOPMENT PLAN

COMMENT: NO OBJECTIONS OR ADVERSE COMMENTS




Vehicle Trip Generation: Daily: 42 PM Peak: 6



Please call if you have questions,



Aichong Sun

Pima Association of Governments

177 N. Church Ave, #405

Tucson, AZ 85701

Tel: (520) 792-1093, Fax: (520) 620-6981

Web: www.PAGnet.org and www.RTAmobility.com
11/23/2007 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Add the CDRC case number and any related case numbers to the landscape and native plant preservation plans. DS 2-07.2.1.B

2) Street landscape borders shall be a minimum of ten (10) feet wide as measured from the street property line. Buildings and mechanical cannot be located within the street landscape border. LUC 3.7.2.4.A.1

3) Revise the landscape plan to show the locations and note the height and materials used to construct any proposed or required screen walls. DS 2-07.A.3

4) A minimum distance of two (2) feet must be maintained between a PAAL
and any wall, screen, or other obstruction. The required screen walls cannot be located at the edge of the vehicular use area. DS 3-05.2.2.B.3

5) An unpaved planting area four (4) feet in width must be provided for each canopy tree. Revise the plans to provide the four foot wide planter along the west side of the parking lot. LUC 3.7.2.3.A.1.c

6) The loading area is required to be screened from the street and adjacent parcels per LUC table 3.7.2-I. Revise the landscape and development plans to include the required 6' high wall.

7) Revise the vehicular use area calculation on sheet L-1. Within a vehicular use area, one (1) canopy tree is required for each ten (10) motor vehicle parking spaces or fraction thereof per LUC 3.7.2.3.A.

8) Revise the landscape to include a maintenance schedule per DS 2-072.2.A.4 including:

A) Pruning schedules to show that plant material will maintain
pedestrian and vehicular clearances or that the material will
establish opaque hedge screens

B) Replacement criteria, should plant material not survive.

C) Replacement or upkeep maintenance schedules for inert ground
cover materials.

D) Maintenance schedules for exterior hardscape materials.

E) Maintenance and replacement schedules for irrigation systems.

9) Provide screening for the refuse storage area per LUC Table 3.7.2-I.

10) The native plant preservation submittal is approved, however, please use the appropriate City of Tucson forms.


RESUBMITTAL OF ALL PLANS IS REQUIRED
11/23/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D07-0045 Speedway Office 11/21/07

( ) Tentative Plat
( ) Development Plan
(XXXX) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
(XXXX) Other - Site Plan

CROSS REFERENCE: C9-06-30 Palo Verde Import/Export - Speedway Blvd

NEIGHBORHOOD PLAN: Blenman Vista Neighborhood Plan/University Area Plan

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 12/11/047

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies with Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
(XXXX) Resubmittal Required:
( ) Tentative Plat
( ) Development Plan
(XXXX) Landscape Plan
(XXXX) Other - Color Elevations

REVIEWER: drcorral 791-4505 DATE: 11/21/07
1. Please list rezoning conditions under the general notes section of the site plan.

2. To help stabilize the edge of the neighborhood and to form a visually interesting edge, building facades at the rear and sides should be designed with attention to the architectural character and detail comparable to the front façade and the rooflines shall be varied. Per rezoning condition #2, please submit detailed color elevations.

3. Freestanding signs shall be incorporated into the landscape plan, and the sign materials and colors shall be consistent with the overall design scheme of the development. Per rezoning condition #8, please submit sign details and show these on the landscape plan.

4. Unsightly and noise-generating elements such as loading zones and trash collection areas are to be screened by masonry walls and landscaping to mitigate potential visual, odor, and noise impacts. Per rezoning condition #9, please provide a detail of loading and trash collection areas and illustrate these on the landscape plan.
11/27/2007 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D07-0045 SPEEDWAY OFFICE/DEVELOPMENT PLAN
DATE: November 27, 2007



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Legal Description should read: lots 15, 16 and ptn of 14, Block 38, Olsens Addition, Bk 4, Pg. 88.

Add Section, Township, Range to Location Map.

Delete 2345 E. Speedway.

Delete direction and spell-out suffix for Norton Avenue and Speedway Boulevard.

Label Project Number.



jg
11/27/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: November 27, 2007

TO: DSD_CDRC@ tucsonaz.gov

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov


SUBJECT: D07-0045 Speedway Office: Development Plan(11-9-07)


Parks and Recreation has no comments on this project.
11/29/2007 JIM EGAN COT NON-DSD FIRE Denied The building must have automatic fire sprinklers. IFC 903.

The proper occupancy group for the residential is R-2. IFC Section 202.

A horizontal separation cannot be used to separate a structure into 2 buildings.
11/30/2007 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved
12/04/2007 TIM ROWE PIMA COUNTY WASTEWATER Denied December 4, 2007

To: Leo Katz
Leo R. Katz Architect

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: Speedway Office, 2339 E. Speedway
Site plan - 1st Submittal
D07-045


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The Site Plan for this project cannot be approved until a copy of this letter has been received by this office.

All Sheets: Show the jurisdiction’s case number, D07-045, in or near the title block of each sheet. This case number should be shown larger and bolder than any associated cross-reference numbers.

The site plan submitted is significantly deficient. Refer to Pima County Development Services “Development Plan Review, Checklist Requirements” section J. WASTEWATER, for submittal requirements. The checklist is available at;

http://www.pimaxpress.com/SubDivision/Documents/DevPlanReq.pdf

Sheet 1: The address written under the location map does not match what is shown for the project in the Title Block.
Sheet 1: A legend needs to be created showing symbols for the various sewer elements: existing/proposed sewer lines, manholes, cleanouts ,etc.. Be sure to distinguish private from public elements.

Sheet 1: It is unclear by this plan how you plan to connect to the public sewer. Make sure that you show the public sewer line in both Speedway Blvd. and Norton Ave. The line should include the IMS#’s for the manholes with rim and invert elevations and the construction plan # and pipe size for the public sewer.

If you are proposing a new connection it should be labeled as private BCS and should include the pipe size/length and slope. Any existing connections should also be shown and marked as private/existing with pipe size.

Sheet 1: Ownership of property information should be shown on plan

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the . The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above-mentioned comments, please contact me.
12/10/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
12/11/2007 ANDY VERA ENV SVCS REVIEW Approved Adequate street frontage service access for curbside APC refuse and recycle collection from Norton Ave.

Prior approval letter furnished by John Clark acceptable.
12/11/2007 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: D07-0045, Speedway Office, 2339 E. Speedway
Rezoning from R-1 to allow office and residential apartment
Development plan, 1st review

TRANSMITTAL DATE: December 11, 2007

DUE DATE: December 11, 2007

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is November 8, 2008.

2. This project was reviewed for compliance with the Land Use Code (LUC), Development Standard (DS), American National Standard Institute (ANSI), and International Building Code 2006 (IBC). The content of this plan was reviewed for compliance with DS 2-05.

3. Per DS 2-05.2.1.C, please increase the type size on: utility lines, the roof slopes, and dimensions on gates at the north side - to 12 point for microfilming.

4. Per DS 2-05.2.1.D, regarding location map:
A) please revise to meet a scale of 3' = 1 mile
B) Please add the Township, Range and Section number of the site - and adjacent sections

5. Per DS 2-05.2.1.K, please provide a title block in the lower right hand corner of each sheet of the project. In the title block, please include the Development Plan number D07-0045, rezoning case number C9-06-30, the title of the project, and indicate the project is the development of both offices and an apartment.

6. Per DS 2-05.2.1.K, please list the rezoning conditions of C9-06-30.

7. Per DS 2-05.2.2.A.1, list the names, addresses and phone numbers of the primary property owner of the site and developer of the project.

8. Per DS 2-05.2.2.A.2, please provide the address of your office Leo - how about in between the phone number and "Architect" - thanks!

9. Per DS 2-05.2.2.B.1, thank you for the zoning note. Can you please revise to state "existing zoning is R-1, proposed zoning is O-2 per rezoning case C9-06-30".

10. Per DS 2-05.2.2.B.10, please provide the following note: "The project is designed to meet the Major Streets and Routes Overlay Zone, LUC 2.8.3."

11. Per DS 2-05.2.2.B.11, thank you for the square footage note for the combined lots. Please indicate the size of the site in acreage as well, thank you.

12. Per DS 2-05.2.3.B, please ensure any/all easements are graphically indicated on the plan, including their recordation and use. Thank you.

13. Per DS 2-05.2.3.C, please dimension the rights of way of Norton and Speedway, showing the centerlines, future curb (if Speedway is already at maximum width -which is 120'- please label curb as Future/Existing curb and call out total right of way of Speedway as maximized. Thank you.

14. Per DS 2-05.2.3.D.4, please indicate the site is currently vacant - prior structures were demolished under permit T06BU00061.

15. Per DS 2-05.2.4.B, please revise the zoning classification to the adjacent property to the west to be an "O-1" zoning classification.

16. Per DS 2-05.2.4.C, please advise if the project will be phased and include any separate phasing calculations if applicable.

17. Per DS 2-05.2.4.D.3, please just add a dimension to the entry to the site for inspections and record purposes.

18. Per DS 2-05.2.4.I, regarding building setbacks:
A) please revise the note for the required minimum building setback at the east to read "the greater of 21' or the height of the exterior building wall from the travel lane of Norton Avenue."
B) Please revise the note for the required minimum building setback at the north to read "the greater of 10' or ¾ of the height of the exterior building wall from the property line"
C) Please revise the setback note for the south property line to read "the greater of 21' or the height of the exterior building wall from the back of the future curb of Speedway"
D) For verification that sufficient building setbacks have been proposed, please provide the wall heights of the buildings, measured from grade to the top of the walls.


19. Per DS 2-05.2.4.K, please revise the width of the pedestrian gates proposed throughout the site to be 4' wide, per DS 2-08. All pedestrian routes must be 4' wide.

In addition, please delineate the sidewalk or concrete location along the north side of the site - and over by the loading zone as well.

20. Per DS 2-05.2.4.N, I see the square footage notations provided for the development, thank you. For permitting and records purposes, please provide a dimension to the footprint of the structures, both 1st and 2nd floors. In addition, please provide the overall heights of each portion of the building - from grade to top of the roof pitch and from grade to the midpoint of the pitch as well.

21. Per DS 2-05.2.4.O, please revise the loading zone notes to show the loading zone required at a minimum size of 10x18, per LUC 3.4.5.6. Remove the wheel stop from the loading zone to ensure it is the appropriate length.

22. Per DS 2-05.2.4.P, regarding parking:
A) please revise the minimum fine for illegally parking in a handicapped space as $518.00
B) please revise the location of all wheel stops to be fully contained within 2'6" of the top of the parking space.

23. Per DS 2-05.2.4.Q, regarding bike parking:
A) provide two class 2 spaces
B) please revise the bike parking calculation to show that bike parking is provided at 8% of the total number of vehicle spaces of the commercial use. ( 8% of 19 = 2)
C) revise the style of the class 2 bike parking to meet the amended DS 2-09 section.
D) Please call out the surfacing of the bike parking area - gravel?

24. Per DS 2-05.2.4.T, please see Engineering and Environmental Services about trash enclosure requirements.

25. Per DS 2-05.2.4.U, please provide a SEPARATE response letter declaring how the property will be developed to meet rezoning conditions.

26. Per DS 2-05.2.4.V, declare location of postal service please.

27. Per DS 2-05.2.4.W, please declare any new free-standing signage.

28. Please change the title to read the project is a development plan, rather than a site plan.

29. Please List the maximum allowed lot coverage as 70% and break down the square footage of the building footprint and the square footage of the vehicle use area.

30. Please revise the Floor Area Ratio calculation to express the FAR in decimal format. I acknowledge that there is no issue with the FAR. Thank you.

31. Please provide a note that the project is subject to the following LUC Sections 2.4.2.6.A.B, 3.5.13.1.B, 3.5.13.2, 3.5.13.3, 3.5.13.4 - and list out these code sections. Of particular concern - please indicate how the project will meet 3.5.13.4, requiring NO OPENINGS ON THE NORTH SIDE OF THE OFFICE. Please provide this note on the plan, and provide an elevation.

32. Please note that further comments may be forthcoming, depending upon the responses provided. I may be reached at Heather.Thrall@tucsonaz.gov or at 520-837-4951 if you have any questions on this review, or wish to meet.

If you have any questions about this transmittal, please call (520) 791-5608.


C:\planning\cdrc\developmentplan\D07-0045 Speedway Office.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, and additional requested documents.
12/12/2007 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: December 12, 2007
SUBJECT: The Roadside Steakhouse - Engineering CDRD - Development Plan Review
TO: Anthony C Tsang
LOCATION: 7648 S Wilmont, T15S R15E Sec 27, Ward 4
REVIEWER: Bianca Ramirez, CFM
ACTIVITY: Development Plan D07-0044 (First Review)


RESUBMITTAL REQUIRED: Revised Development Plan

The Engineering Division has reviewed the development plan and we do not recommend approval at this time. The following comment must be addressed prior to approval:
.


1. Project location map should cover approximately one (1) square mile, be drawn at a minimum scale of 3" = 1 mile. Provide scale 3" = 1 mile along with section, township and range. Include section corners within location map.
2. Per aerial photo, there appears to be an existing building. Demo permit required for demolition of existing building. Show the existing structure on the development plan and indicate whether it is to remain or be removed.
3. Provide title block - the following title block information is to be provided in the lower right corner of the sheet:
a. The proposed name of the project or, if there is no name, the proposed tenant's name or the property address.
b. A brief legal description
c. Label the plan as development plan.
4. Provide contour interval on development plan. The north arrow, scale and contour interval should be placed together on each sheet, preferably in the upper right hand corner of the sheet.
5. Verify that all-rezoning, annexations, or subdivision case numbers are listed in the lower right corner next to the title block.
6. List the name of the property owner and the developer along with address, contact name and telephone number. Add address for Leo R. Katz, Architect to the development plan.
7. List the gross area of the site by square footage and acreage.
8. Provide the following drainage notes;
a. "The developer, any successors and assigns, will hold the City of Tucson, its officers, employees, and agents harmless from any and all claims for damages related to the use of this development as shown hereon, now and in the future, by reason of flooding, flowage, erosion, or damage caused by water, whether surface flood or rainfall."
b. "Drainage will remain in its natural state and will not be altered, disturbed, or obstructed other than as shown on this development plan."
9. Provide the following Street and Road notes:
a. "No structure or vegetation shall be located or maintained so as to interfere with the sight visibility triangles in accordance with Development Standard 3-01.0.0."
10. Provide the following utility note:
a. "Any relocation or modification of existing utilities and/or public improvements necessitated by the proposed development will be at no expense to the public."
11. Provide bearing information for all site boundary lines, include nearing in degrees, minutes and seconds, with basis for bearing noted.
12. Verify that the following information regarding existing utilities are provided: the location and size of water lines, fire hydrants, sanitary sewers, including pipe diameter and the interval and rim elevations of all manholes and cleanouts; the Pima County Wastewater Management Department (PCWMD) reference number; locations of gas lines, electric and telephone lines, poles and communication cables, on ground junction boxes, and street lights. If water mains area not located on or adjacent to the tract, indicate the direction, distance to, and sizes of those nearest to the property.
13. Verify that structures, fences, walls, etc. are shown in a different line weight than the proposed improvements. Add label to be removed or remain.
14. Indicate if existing streets are public or private; provide street width; curb; sidewalks and utility locations; all fully labeled and dimensioned. Provide any appropriate recordation information.
15. Show all right of way dedications on or abutting the site and label. If street dedication is not required or proposed and the project site is adjacent to a Major Streets or Route, draw the Major Streets right of way lines for those streets. (Add the MS&R future sidewalk, right of way lines, etc.)
16. Provide percent slopes for drainage and sidewalks on development plan.
17. Clarify the purpose of the 3' dimension for sidewalk located south of building.
18. At any point where a ten (10) year flood discharge starts to cross a sidewalk or a pedestrian access, the sidewalk/access shall be designed and constructed to convey the ten (10) year flood flows under the sidewalk/access. Provide drainage arrows and locations of all concentration points. Specifically show roof down spout locations proposed buildings at pedestrian circulation areas. A detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage at all pedestrian sidewalk is required, refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk.
19. All sidewalks must comply with accessibility requirements for the physically disabled. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
20. Call out dimensions for the existing sidewalk notes. One located in south-southeast corner of plan and the other in the east- southeast corner of plan.
21. Verify that leader for note new 5'wide sidewalk in northeast corner of plan is pointing to correct area being called out.
22. Label the height and dimension of each building.
23. Draw locations and indicate types of off-site runoff acceptance points and /or onsite runoff discharge points.
24. If there are any proposed signs, indicate the type of proposed sign (wall, free-standing, pedestal) to assure there are not conflicts with other requirements and the minimal locational requirements can be met.
25. Label future sight visibility triangles. If the Speedway is already built out to the existing dimension provided for the MS&R then label sight visibility triangle as existing and future sight visibility triangle.
26. Label MS&R with existing and future right of way dimensions. If the Speedway is already built out to the existing dimension. Label and existing and future right of way.
27. Additional comments may be forthcoming.




Bianca C. Ramirez, CFM
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
12/18/2007 FRODRIG2 COT NON-DSD REAL ESTATE Denied >>> Jim Stoyanoff 12/14/2007 2:12 PM >>>
Please show re-zoning conditions on the plans.
12/27/2007 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#190721 December 27, 2007

Leo R Karr Architect
Attn: Leo
2410 E 7th Street
Tucson, Arizona 85719

Dear Mr. Karr :

SUBJECT: Speedway Office
D07-0045

Tucson Electric Power Company has reviewed and approved the development plan submitted November 19, 2007. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.

If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Should you have any technical questions, please call the area Designer Mike Kaiser at (520) 918-8244.

Sincerely,


Elizabeth Miranda
Office Support Specialist
Design/Build
lm
Enclosures
cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email)
M. Kaiser, Tucson Electric Power