Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - CDRC - DEV PLAN
Permit Number - D07-0034
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2008 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 02/05/2008 | FRODRIG2 | PIMA COUNTY | WASTEWATER | Approved | February 1, 2008 To: Chuck Schuiteman GD&A Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department ___________________________ From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County Departments of Wastewater Management and Environment Quality Subject: Country Club Industrial Park Dev. Plan – 3rd Submittal D07-034 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted. Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality. Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution. If you have any questions regarding the above-mentioned comments, please contact me. |
| 02/26/2008 | TERRY STEVENS | ZONING | REVIEW | Approv-Cond | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Terry Stevens Lead Planner PROJECT: D07-0034 Country Club Industrial Park Development Plan TRANSMITTAL: 02/26/08 DUE DATE: 12/07/07 COMMENTS: 1. The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements. 2. Provide on page 2 of 4, in keynote number 22, the recording information (docket and page) for the abandonment of the easement. If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961 TLS C:\planning\cdrc\developmentplan\D07-0034-2dp.doc |
| 02/28/2008 | FRODRIG2 | COT NON-DSD | REAL ESTATE | Approved | no comment |
| 03/18/2008 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Approv-Cond | TO: Patricia Gehlen; CDRC Manager SUBJECT: County Club Industrial Development Plan 3rd Resubmittal Engineering Review REVIEWER: Elizabeth Eberbach LOCATION: Lots 3 and 4 of County Club Industrial ACTIVITY NUMBER: D07-0034 SUMMARY: The revised Development Plan package, including a revised Drainage Statement, revised Landscape documents, and response letter, was received by Development Services Department Engineering. Development Services Department Engineering has reviewed the received items and recommends conditional approval of the Development Plan. A grading permit is required prior to disturbance of the site. The Drainage Statement was reviewed for development plan purposes only. DEVELOPMENT PLAN COMMENTS: 1) City of Tucson Development Standards (DS) Sections 2-05.2.3.I.2, 2-05.2.4.H.1: Per the labeled water surface contour intervals, the floodplain line extends into the proposed parking area on the southwest side of the building 3. Revise the floodplain limits and correct proposed spot elevations to provide positive drainage from the building through the parking area and coincide with the surface drainage arrows shown on planview. 2) DS Sec.2-05.2.3.C: The following information regarding existing public right-of-way for Country Club shall be provided: type and dimensioned width of paving, curbs, curb cuts, and sidewalks, preferably in a cross section for clarity. This information must be shown on the Development Plan. Specifically clarify, depict, and label existing, extents of existing curb, type of curb, and radii of existing curb. The response letter stated that the required information had been provided per this standard yet these items are still not addressed. Please assure that the information is provided on the development plan as this document acts as a basis from which improvements plans including PIA's and grading plans are derived and compared. 3) The following comments must be addressed at grading plan review stage: a) DS Sec.2-05.2.4.D.1: The existing 40-ft (industrial) ribbon curb at Country Club is acceptable for floodplain purposes; any vertical curb may obstruct jurisdictional stormwater runoff from the east that is to be directed to the basin; proposed design for the PIA shall not be in conflict with drainage recommendations of revised drainage report. b) DS Sec.2-05.2.4.D.1, general note 23: Discuss in Drainage Statement for grading plan submittal how any proposed curb will not obstruct jurisdictional stormwater runoff from Country Club from the east that is to be directed to the basin. c) DS Sec.2-05.2.3.E, 2-05.2.1.H: It will be necessary to provide a local benchmark for basis of elevation for this project at grading plan review stage. For the grading plan, provide a local benchmark on planview and the datum for the vertical data. Corrections must be made so that the final copy of the Development Plan addresses comments 1 and 2. If you have questions or would like to set up a meeting, call me at 837-4934. Elizabeth Eberbach, PE Civil Engineer Engineering Division Development Services Department |
| 03/20/2008 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Approv-Cond | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES March 20, 2008 Chuck Schuiteman, AIA Gromatzky Dupree & Associates, Southwest, LLC 250 South Craycroft Road, Suite 200 Tucson, Arizona 85711 Subject: D07-0034 Country Club Industrial Park Development Plan Dear Chuck: The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per on-line comments, please submit the following documents for sign-off. 1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). AND 1 Double Matte right-reading Océ or Photo Mylar of the Development Plan. AND 1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan. The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options. TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html. Should you have any questions, please call me at 837-4919. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 881-4390 dpapproved |