Permit Number: D07-0033
Parcel: 10511061R

Address:
4500 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D07-0033
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/19/2007 FRODRIG2 ENGINEERING REVIEW Passed
10/19/2007 FRODRIG2 LANDSCAPE REVIEW Passed
10/19/2007 FRODRIG2 ZONING REVIEW Passed
10/24/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved October 24, 2007
ACTIVITY NUMBER: D07-0033
PROJECT NAME: Tucson Mall Expansion
PROJECT ADDRESS: 4500 N Oracle Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Development Plan; therefore a revised Development Plan is required for re-submittal.

The following items must be revised or added to the development plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. Awaiting the submittal of the Traffic Impact Analysis (TIA). Additional comments maybe forthcoming due to the recommendation of the TIA.


If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
10/26/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approv-Cond DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D07-0033 Tucson Mall Expansion 10/25/07

() Tentative Plat
(XXXX) Development Plan
(XXXX) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other - Elevations

CROSS REFERENCE: Annexation C9-82-48, Ordinance No. 5651

NEIGHBORHOOD PLAN: North Stone

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 11/19/07

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
(XXXX) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: D. R.Corral 791-4505 DATE: 10/24/07
Resubmittal shall not be required at this time; based on the following conditions:

In lieu of submitting elevations of the buildings now, the applicant shall add a note to the development plan stating elevations illustrating four-sided architecture and color palate shall be submitted to the Department of Urban Planning and Design for review prior to the issuance of building permits.


In lieu of submitting signage plans now, the applicant shall add a note to the development plan stating signage plans, illustrating integration with the overall landscape plan, shall be submitted to Urban Planning and Design staff for review prior to the issuance of building permits.
10/31/2007 FRODRIG2 PIMA COUNTY WASTEWATER Approved October 31, 2007


To: Tracy Brown
National Survey & Engineering

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: Tucson Mall Expansion
Dev. Plan – 2nd Submittal
D07-033


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above-mentioned comments, please contact me.
11/06/2007 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D07-0033 TUCSON MALL EXPANSION/REVISED DEVELOPMENT PLAN
DATE: 11/05/07



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.


ES
11/26/2007 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#185703 November 26, 2007

General Growth Properties Inc.
Attn: Adam Tritt
110 N Wacker Drive
Chicago, IL 60606

Dear Mr. Tritt :

SUBJECT: Tucson Mall Expansion - Resubmittal
D07-0033

Tucson Electric Power Company has reviewed and approved the development plan submitted October 23, 2007. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.

If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Should you have any technical questions, please call the area Designer Warren McElyea at (520) 918-8268.

Sincerely,


Elizabeth Miranda
Office Support Specialist
Design/Build
lm
Enclosures
cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email)
W. McElyea, Tucson Electric Power
11/26/2007 FRODRIG2 UTILITIES DUMMY CRITICAL Passed
11/27/2007 ANDY VERA ENV SVCS REVIEW Denied 1. R1, R2, R3, R4, & R9
Whether unknown user type or not must provide for minimum one double or two single enclosure types to accomodate for both refuse and recycle dumpsters for each building/business. Refer to DS 6-01.3.0 & DS 6-01.4.0.

2. Must provide adequate accessibility and maneuverability within development without backing into potential moving traffic DS 6-01.4.1.I, 6-01.4.1.A, & 6-01.3.1.
Provide a minimum required 14 ft x 40 ft clear approach to enclosure area with a maximum back-up distance no greater than 40 ft. DS 6-01.4.1.C. Service vehicle should be perpendicular to enclosure at 10 ft in front of enclosure.
Minimum turning radii is 36 ft inside rear wheel and 50 ft outside front bumper.

3. Include within DP a detailed drawing of the refuse/recycle enclosure (single and/or double type) with all apporiate requirements shown. refer to DS 6-01.4.1 & 6-01.4.2
Ensure to provide a 10 ft x 10 ft inside clear service area between the rear and side wall protectors and the front gates.
Gates must be equipped with the ability to be secured in the open and closed positions. Show within detail drawing and annotate at minimum " positive locking with (Bayonet) anchors, Qty-4, 1 in. dia. x 6 in. long galvanized pipe flush with concrete/foundation". Per Architect/engineer design.
Recommend designing gates to open a minimum of 180 degrees with anchors/cane bolts and galvanized pipe appropriately locationed to secure at 180 degree opening.

4. Show all dimensions, route path, and turning radii's.

5. Centralized compactors for service court areas will work.

Please provide corrections on resubmittal.

If you have any questions you may contact Andy Vera at (520) 791-5543 ext 1212 or e-mail: Andy.Vera@tucsonaz.gov
12/03/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

December 3, 2007

Tracy Brown, P.E.
National Survey & Engineering
16745 West Bluemound Road
Brookfield, WI 53005

Subject: D07-0033 Tucson Mall Expansion Development Plan

Dear Tracy:

Your submittal of October 19, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

2 Copies Revised Development Plan (ESD, DSD)

2 Copies Revised Landscape Plan (ESD, DSD)





PLEASE NOTE THAT THE ZONING, LANDSCAPE AND ENGINEERING REVIEWS ARE BEING DONE BY WILLDAN, THIRD PARTY.

Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (262) 781-8466
12/03/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES


January 7, 2008

Tracy Brown, P.E.
National Survey & Engineering
16745 West Bluemound Road
Brookfield, WI 53005

Subject: D07-0033 Tucson Mall Expansion Development Plan

Dear Tracy:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

PRIOR TO SUBMITTING THE MYLARS TO THE CDRC OFFICE, THE ENVIRONMENTAL SERVICES DEPARTMENT MUST REVIEW AND APPROVE THEM. THE APPROVAL MUST BE IN WRITING (E-MAIL IS OKAY).

Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (262)781-8466
12/03/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES
***REVISE***


June 26, 2008

Tracy Brown, P.E.
National Survey & Engineering
16745 West Bluemound Road
Brookfield, WI 53005

Subject: D07-0033 Tucson Mall Expansion Development Plan

Dear Tracy:

The above referenced development plan has been APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.


Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager