01/03/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Terry Stevens Lead Planner PROJECT: D07-0031 Aeris Dental Development Plan TRANSMITTAL: 01/03/08 DUE DATE: 1/10/08 COMMENTS: 1. The Zoning Review Section approves the development plan for this project. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements. If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961 C:\planning\cdrc\developmentplan\D07-0031dpa.doc |
01/07/2008 | GLYNDA ROTHWELL | UTILITIES | TUCSON ELECTRIC POWER | Approved | >>> <HNoriega@tep.com> 01/07/2008 9:11 AM >>> <<Aeris Dental Resubmittal WR#185264 D0-0031.doc>> SUBJECT: Aeris Dental D07-0031 Tucson Electric Power Company has reviewed and approved the development plan submitted October 25, 2007 It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development. |
01/07/2008 | PGEHLEN1 | UTILITIES | DUMMY CRITICAL | Passed | |
01/16/2008 | ANDY VERA | ENV SVCS | REVIEW | Approved | |
01/17/2008 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Approv-Cond | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES January 17, 2008 Andrew L. Ogas Indevco A&E, Inc. 5995 East Grant Road, #111 Tucson, Arizona 85712 Subject: D07-0031 Aeris Dental Development Plan Dear Andrew: Your submittal of December 11, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed: ALL BLACKLINES MUST BE FOLDED 2 Copies Revised Development Plan (Engineering, DSD) 2 Copies Revised Landscape Plan (Engineering, DSD) Should you have any questions, please call me at 837-4919. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 545-0092 |
01/17/2008 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Approv-Cond | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES ***REVISED*** January 29, 2008 Andrew L. Ogas Indevco A&E, Inc. 5995 East Grant Road, #111 Tucson, Arizona 85712 Subject: D07-0031 Aeris Dental Development Plan Dear Andrew: The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off. 1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). AND 1 Double Matte right-reading Océ or Photo Mylar of the Development Plan. AND 1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan. The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options. TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html. Should you have any questions, please call me at 837-4919. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 545-0092 dpapproved |
12/11/2007 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
12/14/2007 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | DATE: December 14, 2007 SUBJECT: Aeris Dental - Engineering CDRD - Development Plan Review TO: Andrew Olgas LOCATION: 10410 E Rita Ranch Road, T15S R15E Sec 25, Ward 4 REVIEWER: Bianca Ramirez, CFM ACTIVITY: Development Plan D07-0031 (Second Review) RESUBMITTAL REQUIRED: Revised Development Plan The Engineering Division has reviewed the development plan and we do not recommend approval at this time. The following comment must be addressed prior to approval: Development Plan: 1. Development plan should include a minimum one-half (1/2)-inch margin on each side. 2. Show cross section PAAL with transverse and longitudinal slopes. 3. Provide roof drainage arrows. 4. Label 5' sidewalk along Rita Ranch Road as existing. 5. The proposed turnaround location on the adjacent vacant property requires an access easement. Provide a copy of the documentation for the cross access agreement between the two properties and the easement recordation data on the plan. Indicate on the plan if the easement is public or private. 6. Depict and label 25-feet radii concrete curbs per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213) at the driveway entrance along Rita Ranch Road. The curbs should be constructed at the edge of pavement and entirely on the subject property, which must also be depicted on the site plan OR provide approval from Jose Ortiz 520-791-4259 with the City of Tucson, Transportation Department. 7. Provide geotechnical report for recommendations for building pad bench and construction slope recommendation. 8. Provide details of all surface materials. 9. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. 10. Call out all slopes and stabilization material (concrete, riprap, gabbions or vegetation). 11. Drainage patterns with percent slopes (Show patterns within the first 100 feet from the property line). 12. Provide flow arrows, grades and flow rates within and adjacent to site to show drainage scheme. 13. Call out peak discharges entering and exiting the site. 14. Provide copy of the Master Drainage Report for Rita Ranch illustrating that this site is included in area for on site retention. 15. Show details of all surface and subsurface drainage devices. 16. Revise the development plan to call out Rita Ranch Road as a Major Streets and Routes (MS&R). Provide a note stating that the site plan is in conformance with the MS&R overlay zone criteria. Provide recordation information for Rita Ranch Road. 17. Provide distance from driveways of adjacent properties. 18. See attached Solid Waste Disposal (Refuse) detail enclosed and modify detail as necessary. 19. The Grading Plan is currently in review. Any changes made to the Development Plan must be reflected on the Grading Plan. The Development Plan and Grading Plan must match. The grading plan cannot be approved prior to the approval of the development plan. 20. Contact DSD Environmental Services for Solid Waste Disposal (Refuse) detail and revise detail on sheet DP.1 as necessary. 21. Provide curb stop at end of paving located along eastern side of building. 22. Provide scupper under sidewalk along Rita Ranch Road and provide Q100 along with direction of flow. 23. Provide adequate pedestrian access to trash enclosure. Sidewalk to trash enclosure is required or adequate pedestrian access. 24. Recordation information for abandoned electric easement will be required prior to development plan approval. 25. Additional comments may be forthcoming. If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov Bianca Ramirez Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4928 office (520) 879-8010 fax |
12/14/2007 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | Comments have been addressed or may be confirmed on the MYLAR. |