Permit Number: D07-0028
Parcel: 141220130

Address:
9047 S RITA RD

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D07-0028
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2007 JIM EGAN COT NON-DSD FIRE Denied D07-0028, EEC Drawings, 19 Sheets

Fire protection items on all sheets should be coordinated with the R.A.S.K. drawings.

Sheet 10
The hydrant that is on City water is missing from this area. The hydrant is shown on the R.A.S.K. drawings to allow the fire department to pump directly into the building system from Tucson Water.

The hydrant needs to be on the Tucson Water side of the building not on the fire loop side. You could leave a Stortz connection on this hydrant to differentiate it from the other hydrants. Also see R.A.S.K. FP-3 for connection location.
09/24/2007 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond 1) Add the WASH Case # and date of approval on the Development plan. DS 2-05.2.2.B.10

2) A resubmittal is required if the development plans are revised in a manner that conflicts with the landscape plans.
09/24/2007 JIM EGAN COT NON-DSD FIRE Denied >>> FireDSC FireDSC 10/25/2007 10:27 AM >>>
Fire has approved D07-0028, Target Fulfillment Center.
09/25/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved D07-0028, EEC Drawings, 19 Sheets

Fire protection items on all sheets should be coordinated with the R.A.S.K. drawings.

Sheet 10
The hydrant that is on City water is missing from this area. The hydrant is shown on the R.A.S.K. drawings to allow the fire department to pump directly into the building system from Tucson Water. The hydrant is stiil shown on the fire line after it goes through your system, it should be on the supply side to pump from City Water to you system. You could leave a Stortz connection on this hydrant to differentiate it from the other hydrants. Also see R.A.S.K. FP-3 for connection location.
09/27/2007 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Target Fulfillment Center West
D07-0028
Development Plan (3rd Review)

TRANSMITTAL DATE: September 27, 2007

DUE DATE: October 05, 2007

COMMENTS:

1. The Zoning Review Section conditionally approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

2. On sheets 10 & 11 change all references to "TRAILER PARKING/STORAGE AREA" to "TRAILER STAGING AREA".


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\cdrc\developmentplan\D07-0028dp-3Rd.doc
09/27/2007 FRODRIG2 PIMA COUNTY WASTEWATER Approved September 26, 2007

To: Ken Perry
EEC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: Target Fulfillment Center West
Dev. Plan – 3rd Submittal
D07-028


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above-mentioned comments, please contact me.
09/28/2007 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D07-0028 TARGET FULFILLMENT CENTER WEST/REVISED DEVELOPMENT PLAN
DATE: September 28, 2007




The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


APPROVED WITH THE FOLLOWING CONDITION:

SPELL OUT “ROAD” FOR RITA ROAD ON ALL APPLICABLE SHEETS OF MYLAR.



NOTE:

Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.





jg
10/03/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/10/2007 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved
10/11/2007 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#184029 October 10, 2007




Dear Mr. Perry:

SUBJECT: Target Fulfillment Center West - 2nd Resubmittal
D07-0028


Tucson Electric Power Company has reviewed and approved the development plan submitted September 27, 2007 It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. All relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Please call the area Designer Steve Garcia at (520) 917-8739, should you have any questions.


Sincerely,



Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
cc:S. Garcia, Tucson Electric Power
P. Gehlen, City of Tucson (Email)
10/12/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES


October 12, 2007

Ken Perry
Engineering & Environmental Consultants, Inc.
4625 East Fort Lowell Road
Tucson, Arizona 85712

Subject: D07-0028 Target Fulfillment Center West Development Plan

Dear Ken:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per on-line comments, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

Should you have any questions, please call me at 837-4919.


Sincerely,



Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 321-0333
dpapproved