Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2007 FRODRIG2 START PLANS SUBMITTED Completed
07/02/2007 JIM EGAN COT NON-DSD FIRE Approved
07/03/2007 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: August 21, 2007
CDRC/Zoning Manager

SUBJECT: Lot 25, 8272 S. Camino De Cafe
Development Plan D07-0027 (First Review)
T15S, R15E, Section 27

RESUBMITTAL REQUIRED: Development Plan and Drainage Report.

The Development Plan (DP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207. Dimension all truncated domes as a min. 2' wide.
3. Incorporate water harvesting into the DR by showing where the water harvesting areas will be with depressed curbs and/or scuppers.
4. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. Show exist. SVT at the corner of Cam. De Café and Cam. Abril. Also Cam. De Café is not on the the Major Streets and Routes (MS&R) Plan.
5. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
6. Fully-dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14. Show how the refuse vehicle services the refuse enclosure.
7. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16. Show how the stormwater enters the water harvesting areas.
8. Add a depressed landscaped maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DP.
9. Show all fences, walls, or vegetation for screening and sight visibility by type, material, height, location and spacing per D.S. 2-02.2.1.27.
10. Show the Development plan number (D07-0027) on all sheets per D.S. 2-02.2.1.29.
11. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. Provide documentation from Permits and Codes for the use of driveway aprons instead of curb returns and for the number and placement of the driveways.
12. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. This review was performed for Development purposes only. Final review and acceptance will be at the grading plan stage.
3. Stormwater cannot directly discharge into the public right-of-way, the stormwater must drain into water harvesting areas prior to discharging into the public right-of-way.
4. Incorporate water harvesting into the DR by showing where the water harvesting areas will be with depressed curbs and/or scuppers.
5. Show where sidewalk scuppers will be used and call out COT detail number.

If you have any questions, I can be reached at 873-4932 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 873-4932 office
(520) 879-8010 fax
C:/8272 S. Camino De Cafe CDRC
07/03/2007 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
D07-0027
STANLEY ENGINEERING & DRAINAGE, INC
LOT 25 BROWN/RITA RANCH

--------------------------------------------------------


Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
07/12/2007 TIM ROWE PIMA COUNTY WASTEWATER Denied July 12, 2007


To: Jeff Stanley
Stanley Engineering

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: Lot 25 Brown/Rita Ranch
Dev. Plan - 1st Submittal
D07-027


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The development plan for this project cannot be approved until a copy of this letter has been received by this office.

All Sheets: Show the jurisdiction’s case number, D07-027, in or near the title block of each sheet. This case number should be shown larger and bolder than any associated cross-reference numbers.

Sheet 1: Add a Permitting Note that states:

A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT.




Sheet 2: The distinction between existing and proposed sewer line is not adequate. The line types are too similar.

Sheet 2: The size of pipe for the existing public sewer line should be shown on plan.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $100.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above-mentioned comments, please contact me.
07/17/2007 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D07-0027 LOT 25 BROWN/RITA RANCH/DEVELOPMENT PLAN
DATE: 7/16/07



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


1.) Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.


ES
07/20/2007 JOE LINVILLE LANDSCAPE REVIEW Denied Provide screening for the loading area(s) per LUC Table 3.7.2-I

Add the DP case number to the landscape and NPPO plans.
07/20/2007 CDRC1 OTHER AGENCIES PIMA ASSN OF GOVTS Approved CASE: D07-0027, LOT 25 BROWN/RITA RANCH, DEVEL PLAN

COMMENT: NO OBJECTIONS OR ADVERSE COMMENTS




Vehicle Trip Generation: Daily: 50 PM Peak:
7



Please call if you have questions



Tom Cooney, Travel Forecasting Manager

Pima Association of Governments

177 N. Church Ave, #405

Tucson, AZ 85701

Tel: (520) 792-1093, Fax: (520) 620-6981

Web: www.PAGnet.org and www.RTAmobility.com
07/24/2007 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR# 184035 July 23, 2007



Stanley Engineering & Drainage, Inc.
Attn: Jeff Stanley
P.O. Box 1888
Tucson, Arizona 85702

Dear Jeff Stanley:

SUBJECT: LOT 25 BROWN/ RITA RANCH
D07-0027

Tucson Electric Power Company (TEP) has reviewed the plan submitted July 2, 2007. TEP is unable to approve the plan at this time. There are existing electrical facilities within the boundaries of this project. In order for TEP to approve the plan the facilities and easements must be depicted on the plans.

Enclosed is a copy of a TEP facility map showing the approximate location of the existing facilities. All costs associated with the relocation of the facilities in conflict will be billable to the developer.

Please resubmit two revised bluelines to City of Tucson or TEP's review. You may contact the area Designer, Steve Garcia at 917-8739 should you have any technical questions.

Sincerely,



Henrietta Noriega
Office Specialist

hn
Enclosure
cc: P. Gehlen and F. Rodriguez, City of Tucson (by e-mail)
S. Garcia, Tucson Electric Power
07/24/2007 CDRC1 COT NON-DSD REAL ESTATE Approved >>> Jim Stoyanoff 07/24/2007 9:17 AM >>>
No comment
07/25/2007 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: D07-0027
Lot 25 Brown/Rita Ranch
Development Plan

TRANSMITTAL: 07/25/07

DUE DATE: 07/24/07

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is 07/23/08.

2. DS 2-05.2.1.D Provide on the location map the street names for Camino De Café and Camino Abril.

3. DS 2-05.2.2.B.3 Remove from the building footprint the "Proposed Warehouse" as this does not meet any of the listed proposed uses.

4. DS 2-05.2.3.B The trash enclosure appears to be inside of the indicated 15' public electric easement. Provide documentation from TEP allowing the structure to be built over the easement or relocate the trash enclosure.

5. DS 2-05.2.2.B.2 This project has been assigned the case number D07-0027. List the case number in the lower right corner next to the title block of all plan sheets including the Landscape and NPPO sheets.

6. DS2-05.2.4.D.3 At the northwest corner of the building the handicap ramp and sidewalk is required to have a radius of a minimum 5' or 18' if the PAAL is designated as fire lanes or are used as access lanes for refuse collection or loading zones. See DS 3-05.2.1.C.3.a & .b. See engineering comments.

The backup spur located near the southwest corner of the building is required to have 3' minimum distance provided between the backup spur and any obstruction over 6" in height. See DS 3-05.2.2.D

7. DS 2-05.2.4.K A continuous pedestrian circulation path is required to connect all public access areas of the development and the pedestrian circulation path located in any adjacent streets. See DS 2-08.3.1. If pedestrian circulation is going to be through the building clearly indicate such. Clearly indicate the location of all entrances to the building.

Provide a detail of each type of handicap ramp including dimensioned widths and lengths, slopes, aprons, depths and widths of truncated domes. (minimum depth of 24" for truncated domes)

On detail A sheet 3 by the location of the truncated domes it appears the sidewalk is flush with the access aisle. The note on the detail indicates a ramp per COT standards. Clarify.

8. DS 2-05.2.4.O Indicate the vehicle maneuverability for the loading zone. See engineering comments.

9. DS 2-05.2.4.P Indicate on detail A of sheet 3 , the handicap parking space, the maximum slope of the parking space and access aisle as being 1:48 as per ANSI 117.1-2003 Sec. 502.5.

10. DS 2-05.2.4.P Please provide on the plan view detail and on the site plan for the proposed class 2 bicycle parking spaces a five (5) foot wide access aisle measured from the front or rear of the seventy-two (72) inch long parking space will be provided beside each row. Lighting will be provided such that all facilities are thoroughly illuminated and visible from adjacent sidewalks, parking lots, or buildings, during working hours.
DS 2-09.5.1, DS2-09.5.2, DS 2-09.5.4, & DS 2-09.6.2

Bicycle parking provided on the DP does not meet the requirements of revised DS (Development Standard) 2-09. Per DS 2-09.4.1 Class 2 bicycle parking facilities will be located no more than fifty (50) feet from the main building entrance(s) and will be along the front side of the building as well as along other sides of the building that has an entrance. Bicycle access through the development will be separate from the pedestrian ways. Vehicular access may be used as bicycle access.

11. DS 2-05.2.4.W If applicable, indicate the locations and types of proposed signs (wall, freestanding, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Also indicate if there are existing billboards on site. Billboards will be required to meet all LUC requirements as stated in LUC Sec. 3.5.4.26. If none exists please state so.

12. In note #21 revise to the correct AEZ criteria. This project is not in a AHD-2 but is in the ADC-2 portion of the AEZ overlay.

13. Depending on changes to the plan and responses to the above comments further comments may be forth coming.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\developmentplan\D07-0027dp.doc
07/25/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approv-Cond Align Driveway along Camino Abril with proposed PAAL.
07/30/2007 ANDY VERA ENV SVCS REVIEW Denied 1. DP sheet 2.
Not adequate access/turning radius from Camino Abril onto Camino de Cafe into subject development. Vertical curbed landscape buffer in conflict w/ service vehicle acces.
DS 6-01.3.1.A

2. DP Sheet 3, Masonry refuse enclosure.
Recommend enclosure be designed so that gates are secured to the face of CMU wall or post and allow for a minimum opening of 180 degrees where possible. Anchors must be placed to allow gates to be open at its widest point or 180 degrees.

Please correct on resubmittal.
07/30/2007 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
07/30/2007 ED ABRIGO PIMA COUNTY ASSESSOR Passed
07/31/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D07-0027 Lot 25 Brown/Rita Ranch 07/31/07

( ) Tentative Plat
(XXXX) Development Plan
(XXXX) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: S99-049

NEIGHBORHOOD PLAN: Esmond Station Area Plan

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: 07/24/07

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
(X) Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies with Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:

(-) Resubmittal Required:
(-) Tentative Plat
(-) Development Plan
(-) Landscape Plan


REVIEWER: drcorral 791-4505 DATE: 07/19/07
08/01/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: July 31, 2007

TO: DSD_CDRC@ tucsonaz.gov

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov


SUBJECT: D07-0027 Lot 25 Brown/Rita Ranch: Development Plan Review(6-26-07)

Staff has no comments.
08/21/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

August 21, 2007

Jeff Stanley
Stanley Engineering & Drainage, Inc.
P.O. Box 1888
Tucson, Arizona 85702

Subject: D07-0027 Lot 25 Brown/Rita Ranch Development Plan

Dear Jeff:

Your submittal of June 26, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

8 Copies Revised Development Plan (Engineering, Wastewater, Landscape, TEP, Zoning, Traffic, ESD, DSD)

4 Copies Revised Landscape Plan (Engineering, Landscape, Zoning, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)


Should you have any questions, please call me at 837-4919


Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 792-0318
dp-resubmittal