Review Details: RESUBMITTAL - CDRC - DEV PLAN
Permit Number - D07-0026
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2007 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 10/22/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | DATE: December 4, 2007 To: Patricia Gehlen CDRC/Zoning Manager FROM: Loren Makus, EIT Engineering Division SUBJECT: Elliot Electronics Supply Development Plan D07-0026 (Second Review) T13S, R14E, Section 27 RESUBMITTAL REQUIRED: None The development plan has been reviewed by the Engineering Division and we recommend approval at this time. If you have any questions, I can be reached at 520..837.4927 or loren.makus@tucsonaz.gov. Loren Makus, EIT Senior Engineering Associate |
| 10/22/2007 | KAY MARKS | PIMA COUNTY | ADDRESSING | Approved | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 KAY MARKS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: KAY MARKS, ADDRESSING OFFICIAL SUBJECT: D07-0026 THE MINI TIME MACHINE/REVISED DEVELOPMENT PLAN DATE: 10/22/07 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project. Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses. 2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection. ES |
| 10/23/2007 | STEVE SHIELDS | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Lead Planner PROJECT: The Mini Time Machine Museum of Miniatures D07-0026 Development Plan (2nd Review) TRANSMITTAL DATE: October 23, 2007 DUE DATE: November 16, 2007 COMMENTS: Please resubmit revised drawings along a separate response letter for zoning, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is June 25, 2008. 2. The lot split must be completed prior to approval of the development plan. D.S. 2-05.2.4.A.It appears that some type of lot split is proposed. Provide City of Tucson approved documentation for the lot split. It appears that this project is comprised of two (2) different parcels. There are two (2) options in regards to utilizing the two (2) parcels as one site. Prior to approval of the site plan provide; 1) A Pima County Tax Parcel Combo and a recorded covenant regarding development and use of real property, or 2) Provide a site plan for each parcel that shows how the parcels can stand alone and meet the requirements of the LUC if sold separately along with a recorded covenant regarding development and use of real property. 3. This comment was not fully addressed. It appears that the sidewalk is flush with pavement the entire width of the handicapped parking area. If this is the case then per ICC/ANSI A117.1-2003 Sec. 406.13.1 the truncated domes shall be 24 inches minimum in the direction of travel and extend the full width of the flush surface. Revise the location of the truncated domes. D.S. 2-05.2.4.K It is unclear how the disabled access ramps at the disable parking will gain access to the sidewalk that runs to the main entrance. It appears that the sidewalk runs into the side of a proposed ramp, please clarify. Detectable warnings (truncated domes) will be required at all curb access ramps and anywhere the curb/sidewalk is flush with the pavement. ICC/ANSI A117.1-2003 Sec. 406.13 4. This comment was not addressed correctly, see comment 3 above. D.S. 2-05.2.4.P Show the Detectable warnings (truncated domes) on the handicapped parking space detail. 5. Zoning acknowledges that this comment was not completely clear. On the Class 2 bicycle parking detail show the minimum 30" clear between racks. Also it appears that there is some type of wall or planter at the south end of the proposed bicycle racks. Per D.S. 2-09.5.1.B a minimum thirty (30) inches will be provided between a bicycle parking space and a parallel wall or other obstruction as measured from the side of the rack. Provide a fully dimensioned layout of the proposed Class 1 and Class 2 bicycle parking spaces. D.S. 2-05.2.4.Q Per D.S. 2-09.5.1.A the minimum of thirty (30) inches is required between outer spaces of posts of racks, the 18" as shown on the detail is not correct. 6. This comment has not been fully addressed. Per LUC Sec. 3.3.3.5 If the calculation number of required bicycle parking spaces is less than two (2), the minimum number of required spaces is two (2), therefore two (2) Class 1 bicycle parking spaces are required. D.S. 2-05.2.4.Q The bicycle parking calculation is not correct. Per LUC 3.3.4 "Civic Use Group, Cultural Use, Fifteen (15) percent - five (5) percent Class 1 and ninety-five (95) percent Class 2, revise the calculation. 7. Ensure that all changes to the development plan are reflected on the landscape plans. 8. Additional comments may be forth coming depending on how each comment has been addressed. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956. C:\planning\cdrc\developmentplan\D07-0026dp-2nd.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents. |
| 10/24/2007 | JOSE ORTIZ | COT NON-DSD | TRAFFIC | Approved | |
| 10/31/2007 | FRODRIG2 | PIMA COUNTY | WASTEWATER | Denied | October 30, 2007 To: Robert Suarez RS Engineering Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department ___________________________ From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County Departments of Wastewater Management and Environment Quality Subject: The Mini Time Machine, Museum of Miniatures Dev. Plan - 2nd Submittal D07-026 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. 1. Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at: http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf. The development plan for this project cannot be approved until a copy of this letter has been received by this office. 2nd request. 2. Sheet 2: The private 4" BCS should be a minimum of 2% slope. 3. Sheet 2: Call out the private sewer easement east of project with the docket and page #. Do the same for the public sewer easement running north along the east edge of property. Also include the public sewer plan #. This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents. Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet. The next submittal of this project will be the third(3rd) submittal. A check for the review fee of this submittal in the amount of $39.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter. If the number of sheets changes, please adjust the review fee accordingly. If you have any questions regarding the above-mentioned comments, please contact me. |
| 10/31/2007 | FRODRIG2 | PIMA COUNTY | WASTEWATER | Denied | December 19, 2007 To: Robert Suarez RS Engineering Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department ___________________________ From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County Departments of Wastewater Management and Environment Quality Subject: The Mini Time Machine, Museum of Miniatures Dev. Plan – 2nd Submittal(rev) D07-026 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted. Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality. Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution. If you have any questions regarding the above-mentioned comments, please contact me. |
| 11/05/2007 | PETER MCLAUGHLIN | LANDSCAPE | REVIEW | Denied | For consistency revise the total number of parking spaces stated (62 spaces are indicated in the calculations) in the landscape calculations to match the number shown on the plan (63 total spaces). |
| 11/21/2007 | ANDY VERA | ENV SVCS | REVIEW | Denied | Sheet 1, Dumpster Plan - Detail must show all dimensions including 10 ft x 10 ft service area between wall protection and front gates, wall protection spacing and separation from CMU wall, overall outside dimensions etc... Recommend moving gate post to face of enclosure wall so do not restrict 12 ft gate opening. 2. Sheet 2 DP, Move enclosure further east so closer to PAAL and allows greater separation from parking spaces and 14 ft x 40 ft approach area, for safer operations. DS 6-01.4.1.J. Please provide corrections on resubmittal. If you have any questions you may contact Andy Vera at (520) 791-5543 ext 1212 or e-mail: Andy.Vera@tucsonaz.gov |
| 11/26/2007 | GLYNDA ROTHWELL | UTILITIES | TUCSON ELECTRIC POWER | Approved | 4350 E. Irvington Road, Tucson, AZ 85714 Post Office Box 711, Tucson, AZ 85702 WR#183961 November 26, 2007 Swaim Associates, LLT Attn: Kevin Barber 7350 E Speedway Blvd #210 Tucson, Arizona 85710 Dear Mr. Barber : SUBJECT: The Mini Time Machine - Resubmittal D07-0026 Tucson Electric Power Company has reviewed and approved the development plan submitted November 1, 2007. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer. In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to: Tucson Electric Power Company Attn: Ms. Mary Boice New Business Project Manager P. O. Box 711 (DB-101) Tucson, AZ 85702 520-917-8732 Should you have any technical questions, please call the area Designer Warren McElyea at (520) 918-8268. Sincerely, Elizabeth Miranda Office Support Specialist Design/Build lm Enclosures cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email) W. McElyea, Tucson Electric Power |
| 12/07/2007 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Approv-Cond | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES December 7, 2007 Kevin Barber Swaim Associate, LTD 7350 East Speedway Blvd. #210 Tucson, Arizona 85710 Subject: D07-0026 The Mini Time Machine Development Plan Dear Kevin: Your submittal of October 18, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed: ALL BLACKLINES MUST BE FOLDED 5 Copies Revised Development Plan (Zoning, Wastewater, Landscape, ESD, DSD) 3 Copies Revised Landscape Plan (Zoning, Landscape, DSD) Should you have any questions, please call me at 837-4919. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 326-1148 dp-resubmittal |
| 12/07/2007 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Approv-Cond | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES ***REVISED*** December 18, 2007 Kevin Barber Swaim Associate, LTD 7350 East Speedway Blvd., #210 Tucson, Arizona 85710 Subject: D07-0026 The Mini Time Machine Development Plan Dear Kevin: The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off. 1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). AND 1 Double Matte right-reading Océ or Photo Mylar of the Development Plan. AND 1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan. The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options. TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html. PRIOR TO SUBMITTAL TO THE CDRC OFFICE, THE MYLARS MUST BE REVIEWED AND APPROVED BY PIMA COUNTY WASTEWATER AND CITY OF TUCSON ENVIRONMENTAL SERVICES. THE APPROVALS MUST BE IN WRITING (E-MAIL IS OKAY). Should you have any questions, please call me at 837-4919. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 326-1148 dpapproved |