Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: D07-0020
Parcel: 11451218A

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D07-0020
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/05/2008 HEATHER THRALL ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: D07-0020
Commercial Bldg for Mead Investments
Development Plan

TRANSMITTAL DATE: March 05, 2008

DUE DATE: March 3, 2008

CONDITIONAL APPROVAL GRANTED - subject to the following:

COMMENTS: Please resubmit revised drawings to address the following:

1. Next to detail for handicapped sign on sheet DP 2, provide a larger text size for the note that states illegal parking per T.C.C. 20-222 is a $518.00 fine. Increase type size to a minimum of 12 point.

2. If you have any questions on the resubmittal process, contact Patricia Gehlen at Patricia.Gehlen@tucsonaz.gov or at 837-4919. My contact information is Heather.Thrall@tucsonaz.gov or 520-837-4951.



C:\Heather\planning\development plans\D07-0020 Mead 4 ka.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan.
03/10/2008 ANDY VERA ENV SVCS REVIEW Approved Enclsoure detail good and fully diemensioned with proper spacing of bollards.

** Review done at DSD due to mailling issues.
03/10/2008 FRODRIG2 PIMA COUNTY WASTEWATER Approved March 7, 2008

To: Sam Robison, Robison Associates Architects

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Commercial Building for Mead Investments, Inc.
Development Plan – 4th Submittal
D07-0020

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.
The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above mentioned comments, please contact me .
03/14/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approv-Cond TO: Patricia Gehlen; CDRC Coordinator
DATE: March 14, 2008
REVIEWER: Bianca Ramirez, CFM, Engineering Associate

SUBJECT: Engineering review of the Commercial building for Mead Investments Development Plan. The activity number is D07-0020.

SUMMARY: The Development Plan and Drainage Report were received by Engineering on November 8th, 2007. Engineering has reviewed the received items and does not recommend approval of the Development Plan or the Drainage Report.

RESUBMITTAL REQUIRED: DEVELOPMENT PLAN

GENERAL COMMENTS

1. The Drainage Report was reviewed for Development Plan purposes only.

2. A Grading Plan review and Permit will be required.

3. Proposed fills in excess of two feet above existing grade at any location in the outer one hundred feet of the developing site adjacent to residentially zoned property require the procedure outlined in Development Standards 11-01.8.1. This process must be complete prior to Grading Plan approval.

4. Provide detailed response letter with next submittal.


The next submittal must address the following items:

DEVELOPMENT PLAN

1. Complied.

2. Complied

3. Complied

4. Complied

5. Complied

6. Label the 75' half ROW, "Existing/Future 75' half ROW", since existing and future right of way are apparently the same.. DS 2-05.2.4.D.4.

7. Complied

8. Complied

9. Complied

10. Complied.
03/17/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES


March 17, 2008

Sam H. Robison, Architect
Robison Associates Architects
759 West Panorama Road
Tucson, Arizona 85704

Subject: D07-0020 Commercial Building for Mead Investments, Inc. Development Plan

Dear San:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

Should you have any questions, please call me at 837-4919.


Sincerely,



Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 742-1285
dpapproved