Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: D07-0017
Parcel: 11003081C

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D07-0017
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/25/2007 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond July 25, 2007

To: Bruce Paton, P.E.
Rick Engineering

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________
From: Tom Porter, Sr. Civil Eng. Assistant (520-740-6706), representing the Pima County
Departments of Wastewater Management and Environmental Quality


Subject: Tentative Plat/Development Plan
Puente Nuevo Plaza
2nd Submittal, D07-017


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



Sheet 6: The manhole#1 is now located outside of the property. Why is there a proposed 10’ x 20’ sewer easement still shown on plan?

Sheet 6: Revise the plan to show the sewer flow direction over each segment of all existing sewers.

Sheet 6: 6-inch BCSs connecting directly to an 8-inch line are not allowed (4-inch BCS is okay). However if the plan requires 6” BCSs, they have to connect through a manhole on the proposed 8” private sewer (see comments Nos.14-20). Revise the plan to agree with such requirements. This is the 2nd request.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the tentative or preliminary plat. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above mentioned comments, please do not hesitate to contact me.

CC: Project file
08/07/2007 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D07-0017 PUENTE NUEVO PLAZA/REVISED DEVELOPMENT PLAN
DATE: 8/07/07



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.



ES
08/08/2007 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D07-0017
Puente Nuevo Plaza
Development Plan Resubmittal

TRANSMITTAL DATE: August 3, 2007

DUE DATE: August 21, 2007

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Please provide the contour interval with the north arrow on all applicable sheets (3-7) of the development plan.
DS 2-05.2.1.H

2. Please dimension Qwest easement on sheet 3 of 8.

3. A five (5) foot wide pedestrian refuge must be maintained between a PAAL and building. This refuge area will also include a four (4) foot wide sidewalk and be physically separated from the PAAL with a vertical curb. This is required between the west side of building 4 and the entrance PAAL.
DS 3-05.2.2.B.1 & DS 2-08.4.1.B

4. Please show the end of the sidewalk along the north side of building 1 at the Alvernon Entrance.

5. Previous Comment: The placement of dumpsters and off-street loading that require access and maneuvering within the main entrances from Alvernon Way and Ft. Lowell would appear to create an unsafe situation for pedestrians using the crosswalks placed behind these areas and for incoming traffic where trucks would potentially block access into and out of the project site. Please verify with Engineering and Environmental Services if the placement meets their standards.

This comment remain until revised refuse layout is approved by Environmental Services and Engineering.


6. Please add to proposed use under medical service that Rehabilitation and physical therapy are not permitted.
2003 IBC Sec. 1106.4

7. Per DS 2-09.4.1 Class 2 bicycle parking facilities will be located no more than fifty (50) feet from the main building entrance(s) and will be along the front side of the building as well as along other sides of the building that has an entrance. The size and configuration of the buildings would suggest multiple suites and with different entrances. Please provide rough location of all entrances to separate suites and provide Class 2 parking accordingly.


If you have any questions about this transmittal, please call Karol Aragonez, (520) 837-4960.

KAA S:\zoning review\karol\planning\cdrc\developmentplan\D07-0017dpr.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents.
08/10/2007 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond The following changes are required on the mylars. Resubmittal not required if no other revisions are made to the development plans.

1) Section I on sheet 2 of the Develoment plan does not appear to accomodate the landscaping proposed on sheet 3 of the landscape plan.

Provide detail(s) for landscape plantings proposed along the northern part of the site in the drainage ditch. DS 2-07.2.2.D

2) Identify the location(s) where Section L on sheet 2 of the development plan applies.
08/21/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D07-0017 Puente Nuevo Plaza 08/20/07

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-06-31

NEIGHBORHOOD PLAN: Northside Area Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: August 21, 2007

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies with Plan Policies
() See Additional Comments Attached
(X) No Additional Comments - Complies With Planning Comments Submitted on: 5/15/07








REVIEWER: msp 791-4505 DATE: August 17, 2007
08/22/2007 FRODRIG2 COT NON-DSD REAL ESTATE Approv-Cond Alvernon Wash is shown on the plans as Pima County owned. It is not. This is a City owned wash and the bridge crossing at the north/west corner of the development on to Alvernon Way will need to be processed as a Bridge Easement. We will process this request under the file RES 2008-004. By City Policy the Real Estate Division will have to sell this easement to the developer. The Alternate Sales Policy will be used to value this easement and the value will be based on the Pima County Assessors land values for parcel 110-03-081C. Please submit to the Real Estate Division a legal description and sketch of the area of the bridge structure. Please include the square footage of the foot print of the bridge structure.
08/22/2007 FRODRIG2 COT NON-DSD REAL ESTATE Approv-Cond Conditional approval upon recordation of the bridge easement.
08/23/2007 LOREN MAKUS ENGINEERING REVIEW Approved DATE: September 11, 2007

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Loren Makus, EIT
Engineering Division


SUBJECT: Puente Nuevo Plaza
Development Plan D07-0017 (Second Review)
T13S, R14E, Section 27

RESUBMITTAL REQUIRED: None
The development plan has been reviewed by the Engineering Division and we recommend approval at this time.
If you have any questions, I can be reached at 520.837.4927 or loren.makus@tucsonaz.gov.
Loren Makus, EIT
Senior Engineering Associate
08/23/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
08/24/2007 ANDY VERA ENV SVCS REVIEW Denied 1. Does not have a sufficient number of enclsoures to adequately service development.
Recommend replacing the enclosure at the SW corner of bldg 3 as shown on previous drawing. Also, add an additonal refuse enclosure to the NE corner of development by bldg 3.

Please correct on resubmittal.
09/13/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

September 13, 2007

Tri Miller
Rick Engineering Company, Inc.
1745 East River Road, Suite 101
Tucson, Arizona 85718

Subject: D07-0017 Puente Nuevo Plaza Development Plan

Dear Tri:

Your submittal of July 24, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

6 Copies Revised Development Plan (Zoning, Landscape, Real Estate, ESD, Wastewater, DSD)

3 Copies Revised Landscape Plan (Zoning, Landscape, DSD)

DUE TO THE COMPLEXITY OF SEVERAL OF THE "CONDITIONAL APPROVALS", AN ADDITIONAL SUBMITTAL IS REQUESTED.


Should you have any questions, please call me at 837-4919.


Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 322-6956
dp-resubmittal