Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - CDRC - DEV PLAN
Permit Number - D07-0016
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/04/2007 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 12/07/2007 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | DATE: December 7, 2007 SUBJECT: M&B Mechanical Development Plan - Engineering Review TO: Patricia Gehlen LOCATION: 1101 S Santa Rita Ave, T14S R14E Sec 18, Ward 5 REVIEWER: Bianca Ramirez, CFM ACTIVITY: D07-0016 (4th Review) RESUBMITTAL REQUIRED: Revised Development Plan SUMMARY: The Engineering Division of Development Services Department has received and reviewed the proposed development plan and Drainage Statement (Southwestern Consulting Engineers, LLC, 04APR07). Engineering does not recommend approval of the development plan. The drainage statement was reviewed for development plan purposes only. The following items need to be addressed prior to approval: DEVELOPMENT PLAN: 1. Complied 2. See zoning comments. GRADING PLAN: 1. Provide area of disturbance on sheet one and include area located within right-of-way. Be advised that all construction disturbances are to be included in the area calculation. 2. Arizona Pollutant Discharge Elimination System (AZPDES) requirements may be applicable to this project. Stormwater Pollution Prevention Plans (SWPPP) and text addressing stormwater controls for all areas affected by construction activities related to this development will be required with a grading plan submittal. For further information, visit www.adeq.state.az.us/environ/water/permits/stormwater.html. Provide area of disturbance in order to determine whether or not SWPPP will be required. For any questions, or to schedule a meeting call me at 837-4928. Bianca C. Ramirez Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1193 office (520) 879-8010 fax |
| 12/13/2007 | KAROL ARAGONEZ | ZONING | REVIEW | Approv-Cond | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Karol Aragonez Planner PROJECT: D07-0016 M&B Mechanical Development Plan Resubmittal TRANSMITTAL DATE: December 11, 2007 DUE DATE: January 3, 2008 COMMENTS: The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements. 1. The truncated domes provided for the ramp west of the handicap parking space are to be installed so that the domes are placed in the direction of travel and extend the full width of the access aisle. The domes shall be located so the edge nearest the edge of the access aisle is six (6) inches to eight (8) inches from edge pedestrian path to indicate that a person is leaving the pedestrian path and entering onto the vehicle use area. ANSI 406.12, ANSI 705 If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. KAA S:\zoning review\karol\planning\cdrc\developmentplan\D07-1116dpr2.doc |
| 12/18/2007 | JOE LINVILLE | LANDSCAPE | REVIEW | Approved | |
| 12/19/2007 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Approv-Cond | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES December 19, 2007 Steve Wollerman Southwestern Consulting Engineers 435 East 9th Street Tucson, Arizona 85705 Subject: D07-0016 M&B Mechanical Development Plan Dear Steve: The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off. 1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). AND 1 Double Matte right-reading Océ or Photo Mylar of the Development Plan. AND 1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan. The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options. TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html. Should you have any questions, please call me at 837-4919. Sincerely, Patricia Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 628-1063 dpapproved |