Permit Number: D07-0016
Parcel: 12417229A

Address: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D07-0016
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/18/2007 FRODRIG2 PIMA COUNTY WASTEWATER Approved October 2, 2007

To: Steve Wollerman, Southwestern Consulting Engineers

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: M & B Mechanical
Development Plan – 2nd Submittal rev
D07-0016

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.



If you have any questions regarding the above mentioned comments, please contact me .
10/29/2007 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: October 29, 2007
SUBJECT: M&B Mechanical Development Plan - Engineering Review
TO: Patricia Gehlen
LOCATION: 1101 S Santa Rita Ave, T14S R14E Sec 18, Ward 5
REVIEWER: Bianca Ramirez, CFM
ACTIVITY: D07-0016 (3rd Review)

RESUBMITTAL REQUIRED: Revised Development Plan

SUMMARY: The Engineering Division of Development Services Department has received and reviewed the proposed development plan and Drainage Statement (Southwestern Consulting Engineers, LLC, 04APR07). Engineering does not recommend approval of the development plan. The drainage statement was reviewed for development plan purposes only. The following items need to be addressed prior to approval:


DEVELOPMENT PLAN:

1. DS Sec.11-01.9: Clarify in cross-section (K) that minimum 2-foot setback from property lines to the proposed limits of grading and proposed water harvesting area fill slopes are labeled as undisturbed area. Current dimension shows 2% slope and does not indicated if the slope reflects existing or future conditions. Call out 2-foot setback as undisturbed area.
2. Refer to zoning for comments in reference to truncated domes.

GRADING PLAN:

1. Provide area of disturbance on sheet one and include area located within right-of-way. Be advised that all construction disturbances are to be included in the area calculation.

2. Arizona Pollutant Discharge Elimination System (AZPDES) requirements may be applicable to this project. Stormwater Pollution Prevention Plans (SWPPP) and text addressing stormwater controls for all areas affected by construction activities related to this development will be required with a grading plan submittal. For further information, visit www.adeq.state.az.us/environ/water/permits/stormwater.html.


For any questions, or to schedule a meeting call me at 837-4928.


Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
10/31/2007 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond Revise the landscape and development plans to specify a 6' high wall to screen the loading area per LUC Table 3.7.2-I.
11/01/2007 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D07-0016
M&B Mechanical
Development Plan Resubmittal

TRANSMITTAL DATE: October 30, 2007

DUE DATE: November 16, 2007

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Previous Comment: A sidewalk will be provided adjacent to any parking space accessed by a PAAL where the space is located on the same side of the PAAL as any building. A DSMR would be required to substitute a striped pedestrian refuge for a four (4) foot sidewalk.
DS 2-08.4.1.C

Once the DSMR is approved please add the DSMR case number in the lower right corner of all sheets of the development plan, landscape plan, and NPPO. As a note provide the DSMR case number, conditions of approval if any, and date of approval. The development plan cannot be approved until the DSMR has been approved.

2. The truncated domes provided are to be installed so that the domes are placed in the direction of travel and extend the full width of the access aisle. The domes shall be located so the edge nearest the edge of the access aisle is six (6) inches to eight (8) inches from edge pedestrian path to indicate that a person is leaving the pedestrian path and entering onto the vehicle use area. Please revise the DP plan view and detail E/3 adding truncated domes.
ANSI 406.12, ANSI 705

3. Please demonstrate that a delivery vehicle can maneuver in and out of the required off-street loading space on site. The loading space shall be designed so that the delivery vehicle can be maneuvered in and out of the loading space. The size of the maneuvering area shall be based on national standards for turning radii required of the vehicles for which the loading space is designed. By the proposed location it does not appear that this can be accomplished.
LUC 3.4.4.2.C

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

KAA S:\zoning review\karol\planning\cdrc\developmentplan\D07-1116dpr1.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, architectural elevations, and additional requested documents.
11/06/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D07-0016 M&B Mechanical

() Tentative Plat
(XXXX) Development Plan
(XXXX) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-89-05-09

NEIGHBORHOOD PLAN: Greater South Park

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 11/16/07

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies with Plan Policies
() See Additional Comments Attached
(XXXX) No Additional Comments - Complies With Planning Comments Submitted on: 09/25/07
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other – Sign Details

REVIEWER: drcorral 791-4505 DATE: 11/05/07
11/21/2007 ANDY VERA ENV SVCS REVIEW Approved
11/21/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

November 21, 2007

Steve Wollerman
Southwestern Consulting Engineers
435 East 9th Street
Tucson, Arizona 85705

Subject: D07-0016 M&B Mechanical Development Plan

Dear Steve:

Your submittal of October 18, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Development Plan ( Zoning, Landscape, Engineering, DSD)

4 Copies Revised Landscape Plan (Zoning, Landscape, Engineering, DSD)









Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 628-1063