Permit Number: D07-0014
Parcel: 13612001N

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D07-0014
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2008 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith ALshami, Engineering and Floodplain Review, 01/08/2008

TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: Sorrento Square Retail Center
D07-0014, T14S, R15E, SECTION 26

RECEIVED: Development Plan and Drainage Report on November 21, 2007

The subject submittal has been reviewed. We offer the following comments. Prepare a detailed response that explains the revisions that were made and references the exact location on the Development Plan where the revisions were made:

1. Show and call out Basin's "B" access ramp on the Development Plan.
2. Submit the Scenic Route Overlay Zone submittal for review and approval. The Development Plan shall be approved after the approval of the Overlay Zone submittal approval.



RESUBMITTAL REQUIRED: Revised Development Plan and Overlay Zone Submittal
01/08/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

January 8, 2008

Thomas Sayler-Brown
SBBL Architecture and Planning
1001 North Alvernon Way, Suite 105
Tucson, Arizona 85711

Subject: D07-0014 Sorrento Square Retail Center Development Plan

Dear Thomas:

Your submittal of November 21, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Development Plan (Wastewater, Engineering, Zoning, DSD)

3 Copies Revised Landscape Plan (Engineering, Zoning, DSD)







Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 620-0535
01/08/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied April 28, 2008

Thomas Sayler-Brown
Sayler-Brown Bolduc Lara Architects, L.L.C
1001 North Alvernon Way, Suite 105
Tucson, AZ 85711-1019


SUBJECT: CLOSURE OF CDRC FILE


Development Plan

Per Section 5.3.8.2.A, Expiration Dates, of the Land Use Code, "an applicant has one (1) year from the date of application to obtain approval of a development plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A development plan application that has been in review for a period of one (1) year which has not been approved is considered denied. To continue the review of a development plan for the property, a new development plan which complies with regulations in effect at that time must be submitted. The new submittal initiates a new one (1) year review period."

Case # Case Name DSD Transmittal Date

D07-0014 Sorrento Square Retail Center April 11, 2007

Please note that this case has been closed and that, in order to continue review of the project, new development plan/tentative plat application is required which comply with regulations in effect at the time of the new submittals. CDRC members should be advised of their ability to review the new applications per the current regulations.

Thank you for your assistance.

Sincerely,



Patricia Y. Gehlen
CDRC Manager


xc: CDRC file D07-0014
11/21/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
11/23/2007 CDRC1 PIMA COUNTY WASTEWATER Denied November 21, 2007

To: Thomas Saylor-Brown, SBBL Architecture & Planning

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Sorrento Square Retail Center
Development Plan - 3rd Submittal
D07-0014

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

1. Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The development plan for this project cannot be approved until a copy of this letter has been received by this office. 3rd request.

2. The DP mylars may not be approved until after the public sewer easement is recorded and the recording information is shown on the DP mylars.

3. Provide a copy of an archeological clearance letter for the archeological site. 2nd Request.


This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the 4th submittal. A check for the review fee of this submittal in the amount of $39.00(made out to PIMA COUNTY TREASURER) must accompany the revised set of blue lines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please contact me .
12/04/2007 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D07-0014
Sorrento Square Retail Center
Development Plan

TRANSMITTAL DATE: December 4, 2007

DUE DATE: December 20, 2007

COMMENTS:

1. Once the DSMR has been approved please add the DSMR case number in the lower right corner of all sheets of the DP, landscape plan, and NPPO. As a note provide the case number, date of approval, what was approved and any conditions applied to the modification.

2. The tentative plat/development plan cannot be approved until the overlay zone review has been approved.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

KAA S:\zoning review\karol\planning\cdrc\developmentplan\D07-0014dpr1.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat/development plan and additional requested documents.
12/11/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D07-0014 Sorrento Square Retail Center 12/10/07

( ) Tentative Plat
( X ) Development Plan
( X ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( X ) Other - Elevations

CROSS REFERENCE: C9-06-03

NEIGHBORHOOD PLAN: South Pantano

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: December 20, 2007

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies with Plan Policies
( ) See Additional Comments Attached
( X ) No Additional Comments - Complies With Planning Comments Submitted on: 9/17/07
( X ) No Resubmittal Required:
( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other

REVIEWER: JBeall 791-4505 DATE: December 6, 2007
12/17/2007 JOE LINVILLE LANDSCAPE REVIEW Approved
12/20/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
12/20/2007 ANDY VERA ENV SVCS REVIEW Approved