Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: D07-0012
Parcel: 134234240

Address:
251 S WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D07-0012
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
09/26/2007 FRODRIG2 PIMA COUNTY WASTEWATER Approved September 26, 2007

To: Pattie Davis, PSOMAS, Inc.

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Hampton Inn
Development Plan – 3rd Submittal
D07-0012

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted.
Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above mentioned comments, please contact me .
10/04/2007 KAROL ARAGONEZ ZONING REVIEW Approved CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D07-0012
Hampton Inn
Development Plan Resubmittal

TRANSMITTAL DATE: October 12, 2007

DUE DATE: October 19, 2007

COMMENTS:

The Zoning Review Section approves the development plan for this project. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

If you have any questions about this transmittal, please call Karol Aragonez, (520) 837-4960.

KAA S:\zoning review\karol\planning\cdrc\developmentplan\D07-0012dpr1.doc
10/04/2007 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond The Landscape Section recommends approval subject to approval of the WASH application.
10/17/2007 ANDY VERA ENV SVCS REVIEW Approved
10/22/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approv-Cond Provide the following note to the development plan.

In-lieu fees shall be considered for the required deceleration lane along Wilmot Road. The timing of construction for the required deceleration lane shall be coordinated with the City of Tucson's Department of Transportation to determine if the deceleration lane is to be included under the Park Place/Wilmot intersection improvements project, Plan no. I-2007-???, and funded through in-lieu fees.


If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
10/26/2007 STANTEC ENGINEERING REVIEW Passed
10/26/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: October 26, 2007

TO: DSD_CDRC@ tucsonaz.gov

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov


SUBJECT: D07-0012 Hampton Inn: Development Plan(9-24-07)


Approved.
10/29/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES


October 29, 2007

Pattie Davis
PSOMAS
800 East Wetmore Road, Suite 110
Tucson, Arizona 85719

Subject: D07-0012 Hampton Inn Development Plan

Dear Pattie:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

PLEASE NOTE THAT THE MYLARS MAY NOT BE SUBMITTED UNTIL STANTEC HAS APPROVED THE DEVELOPMENT PLAN AND PROVIDED A STAMPED COPY OF THE PLAN TO THE CDRC OFFICE AND THE WASH OVERLAY PROCESS HAS BEEN COMPLETED.

Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 292-1290