Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D07-0003
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/11/2007 CDRC1 PIMA COUNTY WASTEWATER Approv-Cond July 11, 2007

TO: John Szafran, AIA
DPA Architects , Inc.

THRU: Patricia Gehlen, CDRC Manager
City of Tucson, Development Services Department

FROM: Tom Porter., Civil Eng.Asst.
Development Review Division (Wastewater)
Pima County Development Services Department

SUBJECT: Horizon Irrigation and Turf Solutions
Development Plan - 3rd Submittal
D07-003

The proposed sewer collection lines to serve the above-referenced development have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ), and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

1. Sheet DP-1: The 10" sewer line plan #G-2006-044 is not existing and should be labeled as PUBLIC SEWER PROPOSED BY OTHERS. Also the proposed public manholes shown on property should be numbered.

2. Sheet DP-1: The IMS# for the existing public manhole that you are proposing to connect to is still not shown. This is the 2nd request. Also the rim and invert elevations for the two proposed by others sewer manholes are the same. Please revise or explain.

3. Sheet DP-1: The construction note #5 does not correspond w/ what is shown on the plan for the size of BCS.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above comments, please do not hesitate to contact me.

Sincerely,



Tom Porter
Telephone: (520) 740-6579

Copy: Project file
07/11/2007 CDRC1 PIMA COUNTY WASTEWATER Approv-Cond >>> "Chandubhai Patel" <Chandubhai.Patel@dsd.pima.gov> 10/11/2007 9:02 AM >>>

I have checked the Mylar and found that the conditions of our approval
have been taken care of.

C.C. Patel, P.E.
Pima County DSD ( Wastewater)
07/12/2007 PAUL MACHADO ENGINEERING REVIEW Approv-Cond To: Patricia Gehlen DATE: September 12, 2007
CDRC/Zoning Manager

SUBJECT: Irrigation & Turf Supply, 9337 E. Old Vail Rd. Development Plan D07-0003 (Third Review)
T15S, R15E, Section 27

The Development Plan (DP) has been conditionally approved. Please address the following review comments prior to the submittal of the mylars for signature (inquire with the zoning division for mylar requirements).

Development Plan:

1. No grading shall be allowed on adjacent properties. A 2' bench along length of the property lines is required. This comment was also made on the grading plan.
2. The refuse enclosure shall have a 10'x10' clear area within the bollards from side to side and front to back. Include on the detail of the enclosure the dimension line with shows 10' from back to front.

Drainage Report:
1. The DR has been accepted for DP purposes only.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/9337 E. Old Vail Rd. CDRC 2
09/12/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES


September 12, 2007

John Szafran, AIA
Contact: R. Allan Johns, R.A.
DPA Architects, Inc.
7272 East Indian School Road, Suite 214
Phoenix, Arizona 85251

Subject: D07-0003 Horizon Turf and Irrigation Development Plan

Dear John:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

PRIOR TO SUBMITTING THE MYLARS TO THE CDRC OFFICE, THEY MUST BE REVIEWED AND APPROVED BY PIMA COUNTY WASTEWATER. WRITTEN APPROVAL FROM PIMA COUNTY WASTEWATER MUST BE PROVIDED (E-MAIL IS SUFFICIENT).

Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: (480) 941-3888