Permit Number: D07-0003
Parcel: 141185530

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D07-0003
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
01/23/2007 JIM EGAN COT NON-DSD FIRE Approved
01/25/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: January 25, 2007

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov

CC:


SUBJECT: D07-0003 Horizon Turf and Irrigation: Development Plan(1/18/07)


Staff has no comments.
01/26/2007 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
D07-0003
DPA ARCHITECTS, INC.
HORIZON TURF AND IRRIGATION

--------------------------------------------------------


Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
01/31/2007 AVERA1 ENV SVCS REVIEW Denied * No known landfills with 1000 ft of development
* Trash enclosure detail per development standars requires side wall protection (bollards) with a inside clear of 10 ft between bollards
* Access and service to enclosure will work. Recommend that enclosure be constructed near the exit gate which will allow service vehicle to have a straight on approach and facility more available space for storage.
* No provisions discussed or provided for recycling.
02/07/2007 KAY MARKS PIMA COUNTY ADDRESSING Denied PIMA COUNTY ADDRESSING
201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D07-0003 HORIZON TURF AND IRRIGATION/DEVELOPMENT PLAN
DATE: 2/07/07



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1.) Delete "East" from Old Vail Road on sheets 1.1 and 1.2.

2.) Delete reference to sheets 1, 2 of Book 49, Page 34 in Legal Description.




es
02/07/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D07-0003 Horizon Turf and Irrigation 02/07/07

( ) Tentative Plat
(CCCC) Development Plan
(CCCC) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: Annexation C9-84-84

NEIGHBORHOOD PLAN: Esmond Station

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 02/14/07

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
(CCCC) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies with Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
( ) Resubmittal Required:
( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other

REVIEWER: drcorral 791-4505 DATE: 01/30/07
02/12/2007 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Transportation Information
Rezoning, Plat, and Development Plan Reviews Provided by:
Pima Association of Governments
Data Services Department
Kristen Zimmerman
kzimmerman@pagnet.org
www.pagnet.org
This information is provided to assess the impact of the proposed development on surrounding traffic and roads.
X City of Tucson, Development Services Department, Community Design Review Committee
City of Tucson, Development Services Department, Rezoning
Town of Marana Planning Department
Case Number
Date
The transportation impact of this plan cannot be determined at this time; more detailed information regarding the
nature of the development is required.
This project has no associated transportation impacts.
473 Average number of daily trips (ADT) forecasted as a result of the proposed development
46,600 2-way capacity on nearest existing major street
No data available Most recent (less than 3 years old) 2-way PAG traffic count on nearest existing major street
If the forecasted ADT is greater than 500 ADT, additional traffic and road considerations are noted below.
STREET IDENTIFICATION
Nearest existing major street
Is a road improvement planned as part of PAG's 5-Year Transportation Improvement Program? Yes No
(See http://www.pagnet.org/tip/ for more information on the PAG TIP program.)
VOLUME, CAPACITY, TRAFFIC GENERATION CONSIDERATIONS
(See http://www.pagnet.org/TPD/DataTrends/ for more information on local traffic volumes.)
2005 2030 2005 2030 2005 2030
TRANSIT AND BIKEWAYS CONSIDERATIONS
Existing bus service
(Route, frequency, distance from proposed development)
Existing bikeway
Number of Road Capacity Daily Traffic Volume (ADT)
D07-0003
2/2/2007
Estimated by PAG Traffic Model (ADT) Lanes
46,600
d07-0003.xls 2/2/2007
02/14/2007 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Add the CDRC case number and any related case numbers to the landscape and native plant preservation plans. DS 2-07.2.1.B

2) An unpaved planting area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree. Provide dimensions for the trees planters in and adjacent to the vehicular use area. LUC 3.7.2.3

3) Landscape proposed in right-of-way or MS&R areas must be approved by the City Engineer or designee and comply with the City Engineer's requirements on construction, irrigation, location, and plant type. Provide verification, in writing, of any approvals obtained. Contact Gary Wittwer, DOT Landscape Architect for specific requirements.

4) A separate native plant preservation plan or approval is required for construction in the public right-of-way. This plan is reviewed by the Department of Transportation in conjunction with right-of-way permits. LUC 3.8

5) Canopy trees must be evenly distributed throughout the vehicular use area. Every parking space shall be located within forty feet of a qualifying canopy tree. Revise the landscape plan as necessary. See LUC 6.2.3. for the definition of a canopy tree. LUC 3.7.2..3.A

6) The retention basin is required to include trees. The requirement is for a minimum of twenty trees per acre of basin area. DS 10-01.IV

7) Submit an irrigation plan. LUC 3.7.4.5.C

8) Submit a native plant preservation plan or application for exception per DS 2-15.

An application for exception for a site of this size needs to include a signed statement from a plant professional that no protected plants per LUC 3.8.5.occur on the site.

Resubmittal of all plans is required.
02/16/2007 ED ABRIGO PIMA COUNTY ASSESSOR Passed
02/16/2007 FRODRIG2 COT NON-DSD REAL ESTATE Approved No comment
02/16/2007 TIM ROWE PIMA COUNTY WASTEWATER Denied February 16, 2007

TO: John Szafran, AIA
DPA Architects , Inc.

THRU: Patricia Gehlen, CDRC Manager
City of Tucson, Development Services Department

FROM: Chandubhai C. Patel, P.E., Civil Engg. Manager
Development Review Division (Wastewater)
Pima County Development Services Department

SUBJECT: Horizon Irrigation and Turf Solutions
Development Plan – 1st Submittal
D07-003


The proposed sewer collection lines to serve the above-referenced development have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ), and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


ALL SHEETS. Add the project number, D07-003 to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Provide a letter from PCWMD Development Services Section, written within the past 90 days, stating that the treatment and conveyance system capacity for this project is available. A capacity request form may be found at http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf

SHEET 1.0. Add a General Note that reads:

THIS PROJECT HAS --------- PROPOSED AND--------- EXISTING WASTEWATER FIXTURE UNIT EQUIVALENTS, PER TABLE 13.20.040(F)(1) in PIMA COUNTY CODE 13.20.040(F)

and fill in the blanks.

SHEET 1.0. Add a General Note that reads:

MAINTENANCE AND OPERATION OF THE PRIVATE SANITARY SEWERS (BCS) TO ITS POINT OF CONNECTION TO THE PUBLIC SEWR IS THE REAPONSBILITY OF THE PROPERTY OWNER.

SHEET 1.0. Add a Permitting Note that reads:

A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT.

6. SHEET PG 1. In the Legend, show symbols for proposed BCS and the existing public sewer. Use different line types for existing and proposed sewers. These line types and the symbols should also match those used in the drawing .

7. SHEET PG 1. Show the size, slope, material and length of the proposed BCS.

8. SHEET PG 1. Show the invert elevation of the new BCS at its point of connection with the public sewer.

SHEET PG 1. Show the information pertaining to the point of connection of the new BCS to the public sewer under construction in East Old Vail Road . Show the Pima County plan number for this sewer with its size and slope, and show the necessary information about the existing manholes located immediately upstream and downstream of the planned connection point of the new sewer line.

10. SHEET 1.0. Add a General Note that reads:

ON-SITE SANITARY SEWERS WILL BE PRIVATEAND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON APRIVATE BASIS.

11. SHEET 1.0. Add a General Note that states:

MAINTENANCE AND OPERATION OF THE PRIVATE SANITARY SEWERS (BCS) TO ITS POINT OF CONNECTION TO THE PUBLIC SEWR IS THE REAPONSBILITY OF THE PROPERTY OWNER.

12. SHEET PG-1.Take note that the connection to the public sewer will not be available until the public sewer under construction in the Old Vail Road is completed and the new sewer line is accepted by the PCWMD in the public sewer system.

13. These drawings have two different names for this project. Please make sure they have the same project name on all drawings.

14. We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $100.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and the response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above comments, please do not hesitate to contact me.

Sincerely,



Chandubhai C. Patel, P.E.
Telephone: (520) 740-6563

Copy: Project file
02/16/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
02/20/2007 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
02/26/2007 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: D07-0003
Horizon Turf and Irrigation
Development Plan

TRANSMITTAL: 02/26/07

DUE DATE: 02/14/07

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is 02/13/08.

2. Because parts of the required information for a Development Plan are located on sheet A 1.0 and sheet A1.1, both sheets will be used for this review. Rename sheet A 1.1 to "Development Plan" not a Site Plan.

3. DS 2-05.2.1.K Provide in the lower right hand corner of all sheets the Annexation case #C9-84-84 and the Subdivision case #C12-95-33.

4. DS 2-05.2.2.B.2 This project has been assigned the case number D07-0003. List the case number in the lower right corner next to the title block of all plan sheets including the Landscape and NPPO sheets.

5. DS 2-05.2.2.B.3 List the proposed use as "Construction Wholesale "34" ". Per LUC Sec.2.7.2.2.J.2

6. DS 2-05.2.3.B List the recordation information (docket and page) for all easements located on the property.

7. DS 2-05.2.4.F Provide the future curb location along Old Vail Rd. On a MS&R with a right of way width of 90' the future curb location is 10' in front of the right of way line.

8. DS 2-05.2.4.K It appears that the sidewalk in front of the handicap parking space and access aisle is flush with the pavement. If this is the case a 24" strip of truncated domes is required where the sidewalk and the pavement meet and are flush with one another. Revise the plan and detail 2 of A1.2.

9. DS 2-05.2.4.O Provide as a note the number of required and provided loading zones.

10. DS 2-05.2.4.P Per LUC 3.3.4 under the Wholesaling Use Group, construction wholesaling is parked per the entire storage area including outdoor storage. In this case the total of outdoor and indoor storage is 32,798 square feet. One space per 2000 sq. ft. for the first twenty thousand sq. ft requires 10 parking spaces. The remaining 12,1798 sq. ft. is parked at one space per 10,000 sq. ft. thus requiring one parking space. The total parking spaces required for this project is 11. The plan indicates 11 parking spaces, revise the notes for the number of parking spaces required and the calculation portion of the notes..

Per City of Tucson standards the minimum distance from grade to the bottom of the handicap parking sign (detail 3 of A1.2) is seven (7) feet not four (4) feet as indicated in the detail.

11. DS 2-05.2.4.Q Provide a dimensioned detail of the class two bicycle parking space including the required access aisle. See DS 2-09.5.1 and Figure 9. FYI: per LUC Sec. 3.3.7.8.A Class two bicycle parking spaces may be substituted for class one spaces providing there are less than 50 vehicle parking spaces being provided. If you should decide to keep the class one bicycle parking spaces provide a detail of the locker and a dimensioned layout showing clearances per DS 2-09.

The bicycle parking calculations are based on the number of provided vehicular parking spaces provided. Eleven spaces provided times 8% requires 0.88 bicycle parking spaces. Per LUC Sec 3.3.3.5 The minimum number of required spaces is two (2). Revise calculation and notes.

12. DS 2-05.2.4.R The indicated future sight visibility triangles are not in the correct location. See comment number seven (7) for the location of the future curb which determines the location of the future sight visibility triangles.

13. DS 2-05.2.4.W If applicable provide location, type, height and size of existing or proposed signage including billboards.

14. DS 2-05.2.4.V If applicable provide location and type of postal service to assure there are no conflicts with other requirements, such as pedestrian accessibility, utilities and landscaping.

15. Per LUC Sec. 2.8.5.8.C.1.b For building with in the ADC-3 overlay zone. The maximum Floor Area Ratio (FAR) for this use is limited to .20 not .40 as indicated in the notes. Revise notes.


16. Depending on changes to the plan and responses to the above comments further comments may be forth coming.

If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.

TLS C:\planning\cdrc\developmentplan\D07-0003dp.doc
03/01/2007 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#176502 March 1, 2007




Dear Mr. Szafran :

SUBJECT: Horizon Turf and Irrigation
D07-0003


Tucson Electric Power Company has reviewed and approved the development plan submitted January 25, 2006. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development. Any relocation costs will be billable to the customer.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Please call the area Designer Todd Stocksdale at (520) 917-8715, should you have any questions.


Sincerely,



Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
cc: P. Gehlen, City of Tucson (Email)
T. Stocksdale, Tucson Electric Power
03/13/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 13, 2007

John Szafran, AIA
Contact: R. Allan Johns, R.A.
DPA Architects, Inc.
7272 East Indian School Road, Suite 214
Tucson, Arizona 85251

Subject: D07-0003 Horizon Turf and Irrigation Development Plan

Dear John:

Your submittal of January 18, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

7 Copies Revised Development Plan (ESD, Addressing, Landscape, Wastewater, Zoning, Engineering, DSD)

4 Copies Revised Landscape Plan (Landscape, Zoning, Engineering, DSD)

2 Copies Revised NPPO Plan (Landscape, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)


Should you have any questions, please call me at 791-5608 extension 1179.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (480) 941-3888
dp-resubmittal
03/13/2007 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: March 13, 2007
CDRC/Zoning Manager
SUBJECT: Irrigation & Turf Supply, 9337 E. Old Vail Rd. CDRC
Development Plan D07-0003 (First Review)
T15S, R15E, Section 27

RESUBMITTAL REQUIRED: Development Plan and Drainage Report.

The Development Plan (DP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. There is a discrepency between the x-sections and details of the basin with the plan view on the plans. Revise as required.
3. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
4. Show the standard H/C ramps used at a curb return per COT standards at the project entrance.
5. Show a detail of all the drainage structures, such as, but not limited to curb openings, weirs, wall opening etc. shall be shown on the plans.
6. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. The fut. SVT's are not shown correctly. Revise as required.
7. Fully-dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14.
8. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15.
9. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
10. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
11. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19. Contact the City of Tucson Transportation dept. for the correct width of the future MS & R for Old Vail Road.
12. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DP.
13. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
14. Location and orientation of existing major physical features, such as railroad tracks and drainageways per D.S. 2-02.2.1.22.
15. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
16. Show all fences, walls, or vegetation for screening and sight visibility by type, material, height, location and spacing per D.S. 2-02.2.1.27.
17. Show Development plan number (D07-0003) on all sheets per D.S. 2-02.2.1.29.
18. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The must be able to reverse 50' straight back in a clear area. Revise as required.
19. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
20. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
21. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
22. List the consulting engineer and the owner/developer on the plans with the pertinent information.
23. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
24. "A grading permit and Stormwater Pollution Prevention Plans (SWPPP's) will be required for this project. Submit 3 sets of grading and SWPPP's with text, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans".

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. This review was performed for Tentative Plat purposes only. Final review and acceptance will be at the grading plan stage.
3. Show the details of the retention basin w/ plan view and x-sections, wall openings, curb openings, weirs and/or all drainage structures.
4. Show all calculations that were used for sizing all of the drainage structures.
5. Include/Show efforts made to maximize stormwater harvesting in/on the DR.
6. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
7. Show the project address or administration address on the cover sheet of the DS.
8. Add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DR.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/9337 E. Old Vail Rd. CDRC