Permit Number: D07-0002
Parcel: 11451203C

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D07-0002
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
01/19/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: January 19, 2007

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov

CC:


SUBJECT: D07-0002 Ace Hardware - Bear Canyon Rd: Development Plan(1/172/07)


Staff has no comments.
01/22/2007 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Transportation Information
Rezoning, Plat, and Development Plan Reviews Provided by:
Pima Association of Governments
Data Services Department
Kristen Zimmerman
kzimmerman@pagnet.org
www.pagnet.org
This information is provided to assess the impact of the proposed development on surrounding traffic and roads.
X City of Tucson, Development Services Department, Community Design Review Committee
City of Tucson, Development Services Department, Rezoning
Town of Marana Planning Department
Case Number
Date
The transportation impact of this plan cannot be determined at this time: more detailed information regarding the
nature of the development is required.
This project has no associated transportation impacts.
1,030 Average number of daily trips (ADT) forecasted as a result of the proposed development
22,160 2-way capacity on nearest existing major street
9,501 Most recent (less than 3 years old) 2-way PAG traffic count on nearest existing major street
If the above value is greater than 500 ADT, additional traffic and road impacts are noted below.
STREET IDENTIFICATION
Nearest existing major street Bear Canyon Rd (Tanque Verde to Snyder)
Is a road improvement planned as part of PAG's 5-Year Transportation Improvement Program? Yes X No
(See http://www.pagnet.org/tip/ for more information on the TIP program.)
VOLUME, CAPACITY, TRAFFIC GENERATION CONSIDERATIONS
(See http://www.pagnet.org/TPD/DataTrends/ for more information on local traffic volumes.)
2005 2030 2005 2030 2005 2030
TRANSIT AND BIKEWAYS CONSIDERATIONS
Existing bus service Express 81, 2 AM and 2 PM trips, 0.25 mi
(Route, frequency, distance from proposed development)
Existing bikeway Bike route with striped shoulder
Number of Road Capacity Daily Traffic Volume (ADT)
D07-0002
1/22/2007
Estimated by PAG Traffic Model (ADT) Lanes
8,865 7,748 22,160 22,160 2 2
D07-0002.xls 1/22/2007
01/23/2007 JIM EGAN COT NON-DSD FIRE Approved
01/24/2007 AVERA1 ENV SVCS REVIEW Denied * No known landfills within 1000 ft of development.
* Page (3) detail, if a center post is utilized for support of the gates a 10ft clear will be required between the post and the side wall protection. Demonstrate within detail.
* Page (2) detail - access to enclosure and serviceability okay.
01/26/2007 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
D07-0002
DCC COMPANY
ACE HARDWARE - BEAR CANYON RD

--------------------------------------------------------


Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
02/01/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Denied February 1, 2007
ACTIVITY NUMBER: D07-0002
PROJECT NAME: Ace Hardware - Bear Canyon Rd
PROJECT ADDRESS: 2931 N Bear Canyon Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Development Plan; therefore a revised Development Plan is required for re-submittal.

The following items must be revised or added to the plat.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. The access points shall have 25' radius curb returns. (DS 3-01.0 figure 6) The development plan shows 24' returns. (not really worth commenting on but to avoid issues later please revise)

3. If applicable, dimension the width of all ingress/egress points (Tucson City Code, Chapter 25, section 39 & 40)

4. Bear Canyon is an Arterial roadway therefore the Sight Visibility Triangle (SVT) should be (20x345) for both existing and future SVTs (DS 2-03.2.4.M). Plans show 20' x 265'

5. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.


If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
02/02/2007 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#176498
February 2, 2007
DCC Company
Attn: Kevin Hall
2828 N. Country Club, Ste 100
Tucson, AZ 85716

Dear Mr. Lou Catalini:

SUBJECT: Ace Hardware – Bear Canyon Rd.
D07-0002

Tucson Electric Power Company has reviewed and approved the development plan submitted January 25, 2007 It appears there are no conflicts with the existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Please call the area Designer Nancy DiMaria at (520) 918-8267, should you have any questions.

Sincerely,


Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
Cc P. Gehlen, City of Tucson (Email)
N. DiMaria, Tucson Electric Power
02/05/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D07-0002 Ace Hardware - Bear Canyon Road 02/05/07

() Tentative Plat
(XXXX) Development Plan
(XXXX) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: Annexation C9-84-32

NEIGHBORHOOD PLAN: Bear Canyon Neighborhood Plan

GATEWAY/SCENIC ROUTE: Scenic Route/Bear Canon Road

COMMENTS DUE BY: 2/13/07

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
(XXXX) Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies with Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: drcorral 791-4505 DATE: 01/26/07
02/07/2007 KAY MARKS PIMA COUNTY ADDRESSING Denied PIMA COUNTY ADDRESSING
201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D07-0002 ACE HARDWARE BEAR CANYON RD/DEVELOPMENT PLAN
DATE: February 7, 2007



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:




1.) Delete Administrative/Site Address information and provide a "blank" Address Block (minimum size to be 3" x 5").

2.) Add recording Book and Page to Bear Canyon Shopping Center on Sheet 1.






jg
02/09/2007 JOE LINVILLE LANDSCAPE REVIEW Denied 1) All lettering and dimensions shall be the equivalent of twelve (0.12") point or greater in size per DS 2-05.2.1.A. Revise the native plant preservation plan and other sheet as applicable.

2) Revise the landscape plans to show the limits of grading. DS 2-07.2.2.B.5

3) Revise the native plant preservation plans to show the limits of grading. DS 2-15.3.4.A

4) Revise note 12 on the landscape plan to refer to the appropriate native plan preservation plan.

5) Revise the native plant preservation plan calculations to comply with LUC Table 3.7.2-I. See also DS 2-15.0 Exhibit 1. The calculations require significant correction.

6) The decision to approve or deny the project will be based on the purpose, intent, and specific regulations of LUC 2.8.2. Approval of the development plan/landscape plans is subject to approval of the SCZ application.

7) Within the 30' scenic route buffer area, indigenous plant material is to remain. If any disturbance occurs during construction or prior to permit application, the buffer
area is to be revegetated with native plants indigenous to the site and the area reconstructed to look as natural as possible. DS 2-06.7.1.B

8) Revise the landscape plan to propose an appropriate dust control treatment for the scenic route buffer area where it is not currently vegetated. Decomposed granite is not acceptable for scenic route buffer restoration. DS 2-06.7.1.B

9) Clarify if and where the seed mix shown on the landscape plan is to be used. The scenic route buffer area is to contain only indigenous plants. DS 2-06.7.1.B

10) A comprehensive list of native vegetation that exists on the site and in the immediate areas is required for the landscape plan. See DS 9-06.4.12.

11) Revise the landscape and native plant preservation plans to establish the limits of grading to preserve the scenic route buffer area. LUC 3.7.5.2.A

12) All areas between the MS&R right-of-way line and the street that are disturbed by development shall be revegetated with native vegetation. Add notes. LUC 3.7.5.2.D

13) Revise the landscape plan to provide screening per LUC Table 3.7.2-I along both street frontages. New screening may not be located in the scenic route buffer area, but is to be located behind the natural area.

14) Per LUC 2.8.2.6.A within the Scenic Corridor Zone all existing (viable) vegetation with a caliper of four (4) inches or greater and all saguaro cacti must be preserved or relocated on the site. Revise the landscape and native plant preservation plans to comply.

RESUBMITTAL OF ALL PANS IS REQUIRED.
02/12/2007 FRODRIG2 COT NON-DSD REAL ESTATE Approved No comment.
02/13/2007 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Ace Hardware - Bear Canyon Road
D07-0002
Development plan (1st Review)

TRANSMITTAL DATE: February 12, 2007

DUE DATE: February 13, 2007

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is January 16, 2008.

2. List the D06-060 case number in the lower left-hand corner of the sheet next to the title block.

3. D.S. 2-05.2.2.B.3 General Note #3 the proposed use should be listed as "General Merchandise Sales "28", Subject to: Sec. 3.5.9.2.C, revise the note.

4. D.S. 2-05.2.2.B.10 Add a note stating that the project is designed to meet the overlay zones criteria: LUC Sec. 2.8.2, Scenic Corridor Zone (SCZ) and LUC Sec. 2.8.3, Major Streets & Routes (MS&R).

5. D.S. 2-05.2.3.C Provide a dimension from the centerline of Bear Canyon Road to the future curb.

6. D.S. 2-05.2.4.D.3 Per D.S. 3-05.2.2.D Provide dimensions for the backup spur located at the southwest corner of the property.

7. D.S. 2-05.2.4.D.3 Per D.S. 3-05.2.1.3.a when PAALs area designated a fire lanes or are used as access lanes for refuse collection or loading zones, a minimum unobstructed radius of eighteen (18) feet is required where they intersect another PAAL. Show that these radii exist for access to the refuse area and loading zones.

8. D.S. 2-05.2.4.D.3 Dimension all radii for all curbs shown on the plan. Per D.S. 3-05.2.1.3.b a minimum unobstructed radius of five (5) feet is required for all other PAAL intersections.

9. D.S. 2-05.2.4.D.3 Provide a dimension for the Parking Area Access Lane (PAAL) located north of the proposed refuse location and the two (2) curbed landscaped areas located to the northeast and northwest.

10. D.S. 2-05.2.4.F Show the location of the future sidewalk on the plan.

11. D.S. 2-05.2.4.I Zoning acknowledges that the proposed buildings will meet the minimum setbacks. The setback shown to the street property line is shown incorrectly. This dimension should be measured from the back of future curb.

12. D.S. 2-05.2.4.I Under the DEVELOPMENT CRITERIA, MS&R STREET PERIMETER YARD: the setback is listed incorrectly. Per LUC 3.2.6.5.B the required setback is twenty-one feet or the height of the proposed exterior building wall, revise. Also based on LUC Sec 2.8.2.5 with a building height of 30' the minimum setback from the street future right-of-way line would be 90',

13. D.S. 2-05.2.4.K Provide dimensions for the sidewalk along the east side of the building.

14. D.S. 2-05.2.4.M The DEVELOPMENT CRITERIA shows the building square footage as 20,075 and on the development plan it shows 19,700, please clarify. Additional comments may be forth coming.

15. D.S. 2-05.2.4.P It appears that there are two (2) post barricades located near the sidewalk scupper at the north end of the parking area. These post barricades will prevent vehicles from fully pulling into these parking spaces. These parking spaces area designed so that the vehicle will overhang the curb. Zoning acknowledges that there is adequate space for the vehicle. Show the striping and dimension the minimum eighteen (18) foot depth of the parking spaces from the curb. D.S. 3-05.0 Table 1.

16. D.S. 2-05.2.4.P Per D.S. 3-05.2.3.C.3 when wheel stop curbing is used, it is to be located two and one-half (2 ½) feet from the front of the parking space. The parking space details and the dimension shown along the south property so a dimension of three (3) feet, revise. The overhang Keynote 12 should also be two and one-half (2 ½) feet.

17. D.S. 2-05.2.4.P Once comment 14 is address the parking calculation can be verified. Additional comments may be forth coming.

18. D.S. 2-05.2.4.P Provide a typical parking space detail for a standard vehicle parking space.

19. D.S. 2-05.2.4.Q Per D.S. 2-09.4.1 the Class 2 bicycle parking facilities will be located no more than fifty (50) feet from the main building entrance. Based on the location of Keynote #1 the Class 2 bicycle parking appears to be more than fifty (50) feet from the main entrance. Show the building entrance and provide a dimension to the Class 2 bicycle parking.

20. D.S. 2-05.2.4.Q On the bicycle parking details provide the layout for the parking showing the minimum dimensions as called out in D.S. 2-09.5.0.

21. D.S. 2-05.2.4.W If applicable indicate the locations and types of proposed signs (wall, freestanding, pedestal & billboard) on the plan.

22. The distance shown for the east property line appears to be incorrect, clarify.

23. Clarify what the proposed fenced area, located at the southwest corner of the building, will be used for. Per LUC Sec. 2.5.3.6.B All land use activities except vehicular use areas shall be conducted entirely within an enclosed building unless specifically provided otherwise. Storage is not allowed outside within a fenced area.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\cdrc\developmentplan\D07-0002dp.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, and additional requested documents.
02/14/2007 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
02/14/2007 ED ABRIGO PIMA COUNTY ASSESSOR Passed
02/14/2007 ROBERT YOUNG PIMA COUNTY PIMA CTY - DEV REVIEW Passed
02/16/2007 TIM ROWE PIMA COUNTY WASTEWATER Denied February 16, 2007

To: Kevin Hall, DCC Company

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Michael J. Harrington (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Ace Hardware at Bear Canyon Road
Development Plan - 1st Submittal
D07-0002

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project will be tributary to the Ina Road Water Pollution Control Facility via the North Rillito Interceptor. Per written guidance provided by the PCWMD Development Services Section, sufficient conveyance and treatment capacity exists in the downstream public sewerage system for this small project, and a formal capacity response letter from the PCWMD will not be required.

All Sheets: Add the case number, D07-002, to the title block of each sheet. This number should be shown larger or bolder than any cross reference numbers. No wastewater review fees will be charged for sheets where this is the only required revision.

Revise General Note #9 so that it states:

THE ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE PLAN, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT.

Sheet 1: Delete General Note #10.

Sheet 2: Revise the site plan to show the invert elevation at the point of connection to the public sewer.

Sheet 2: Revise the plan by showing arrows over the existing sewer that indicate the direction of flow.

Sheet 2: Revise the plan to show any required pavement patch in the N. Bear Canyon Road right of way.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
03/07/2007 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: March 7, 2007
CDRC/Zoning Manager

SUBJECT: Ace Hardware Store, 2931 N. Bear Canyon Rd.
Development Plan D07-0002 (First Review)
T13S, R15E, Section 34

RESUBMITTAL REQUIRED: Development Plan and Drainage Report.

The Development Plan (DP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. Please provide property description per D.S. 2-02.2.1.3.
3. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
4. A retention basin is required for any site larger than 1 acre. See DR comment below.
5. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DP.
6. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
7. Location and orientation of existing major physical features, such as railroad tracks and drainageways per D.S. 2-02.2.1.22.
8. Complete Development plan number (D07-0002) on all sheets per D.S. 2-02.2.1.29.
9. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
10. "A grading permit and Stormwater Pollution Prevention Plans (SWPPP's) will be required for this project. Submit 4 sets of grading and SWPPP's with text, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans".

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. A Drainage report is required for any site greater than one acre in size or for any site subject to detention requirements…..per S.M.D.D.F.M., chap. II, 2.1.2.
3. The content and format of the Drainage Report should follow S.M.D.D.F.M., chap. II, 2.2.
4. Show the project address or administration address on the cover sheet of the DR.
5. If applicable, add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DR.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/ 2931 N. Bear Canyon Rd.CDRC
03/08/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 8, 2007

Kevin Hall
DCC Company
2828 North Country Club, Suite 100
Tucson, Arizona 85716

Subject: Ace Hardware - Bear Canyon Development Plan

Dear Kevin:

Your submittal of January 17, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

8 Copies Revised Development Plan (ESD, Traffic, Addressing, Landscape, Zoning, Wastewater, Engineering, DSD)

4 Copies Revised Landscape Plan (Landscape, Zoning, Engineering, DSD)

2 Copies Revised NPPO Plan (Landscape, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)


Should you have any questions, please call me at 791-5608 extension 1179.

Sincerely,


Patricia Gehlen
CDRC Manager