Permit Number: D06-0048
Parcel: 141113950

Review Status: Completed

Review Details: REVISION - DEV PLAN

Permit Number - D06-0048
Review Name: REVISION - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2011 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
01/26/2011 DAVID MANN COT NON-DSD FIRE Approved
01/28/2011 DAVID RIVERA ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: D06-0048
Lot 32
Development Plan (Revised)

TRANSMITTAL DATE: January 28, 2011

DUE DATE: February 07, 2011

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is February 06, 2012.

2. Zoning acknowledges all the changes but cannot approve the plan at this time. Please address the following comments and resubmit for review.

3. An additional work area of 7,570 square feet is being added as work area. It is not clear what the specific use will be for this lot so it is not clear how many additional parking spaces are needed to ensure that there is sufficient parking based on the additional work area expansion.

4. The additional work area will not require an additional loading zone but additional parking spaces will be required. The parking spaces should be based on the most intense use listed on the approved DP in order to ensure that the applicable number of parking spaces is provided. Additional H.C. parking may also be required due to the expansion.

5. Revise the parking calculations as required. Keep in mind that additional vehicular parking will trigger additional bicycle parking. If additional bicycle parking is required draw and label the locations and revise the bicycle parking calculations.

6. The relocation of the loading zone will diminish the required width of the two-way PAAL to less than 24 feet. This cannot be approved without a board of adjustment variance.

7. No vehicular access or use may occur on the unpaved portions of the newly expanded work area. Add a note stating the no vehicular use is allowed on unpaved work area except forklifts.

8. For clarity and to evaluate the site after the revisions are made I am requesting that a clean site plan without any of the revision info be added to this set.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
DGR C:\planning\cdrc\developmentplan\D06-0045dp.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan
01/31/2011 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
02/01/2011 RONALD BROWN ZONING HC REVIEW Denied GENERAL:
1. Verify the need for additional accessible parking. Redesign and resubmit as required.
SHEET C.1
2. Delete the detectable warnings at the accessible parking aisle.
3. Delete the detectable warnings located at the East side of the marked crossing at the North and South sides. Retain the detectable warning located in the direction of travel.
4. Show location of accessible parking signage.
SHEET C-1.3
5. Detail "B": Add the "Van Accessible" signage.
6. Detail "C":
a. Delete the detectable warning strips.
b. The slope of the entire accessible parking area including the aisle is to be no more than 2%.
END OF REVIEW
02/01/2011 PAUL MACHADO ENGINEERING REVIEW Approved
02/08/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

February 8, 2011

Steve Wollerman
Southwestern Consulting Engineers
2342 W. Monet Way
Tucson, Arizona 85741

Subject: D06-0048 LOT # 32 Brown/Rita Ranch Development Plan Revision

Dear Steve:

Your submittal of January 24, 2011 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 4 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Development Plan (Zoning, HC Site, Landscape, PDSD)

3 Copies Revised Landscape Plan (Zoning, Landscape, PDSD)

Should you have any questions, please call me at 837-4893.


Sincerely,





John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (520) 300-7300
02/08/2011 JOE LINVILLE LANDSCAPE REVIEW Denied Revise the landscape plans to correspond with the proposed site plan revisions.