Permit Number: D06-0042
Parcel: 141185500

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D06-0042
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
02/16/2007 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: March 21, 2007
CDRC/Zoning Manager

SUBJECT: 9417 E. Old Vail Rd CDRC
Development Plan D06-0042 (Second Review)
T15S, R15E, Section 27

RESUBMITTAL REQUIRED: Development Plan.

The Development Plan (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. The future SVT's must also be shown. The FOC is 10' from the future right-of-way.
3. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. Per previous comment.
4. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. The future face of curb is 10' in from the future right-of-way line. Dimension the future sidewalk area.
5. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. There seems to be a discrepancy between the basis of bearing in the "Survey Notes" and the "Horizontal and Vertical control……Points". Revise as necessary.
6. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The dumpster enclosure must have an inside 10'x10' clear area from bollard to bollard, side to side and front to rear.
Drainage Report:
1. The DR has been accepted for DP purposes only.
If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax, C/9417 E. Old Vail Rd CDRC 2
03/01/2007 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D06-0042
Rita Ranch Commerce Centre
Development Plan Resubmittal

TRANSMITTAL DATE: March 1, 2007

DUE DATE: March 16, 2007

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The following items found in the parking calculations are to be corrected/revised:

a) Remove "Parking No Spaces Required" from Development Criteria 4.
b) Correct total parking required to "57" in Development Criteria 4.
c) The required bicycle parking calculations are to be based on provided motor vehicle parking for general merchandise use only. Based on twenty-one (21) spaces the amount of required bicycle parking is two (2) spaces, one (1) Class 1 and one (1) Class 2. The provided amount can exceed required.
d) Remove off-street loading calculation for commercial storage from Development Criteria 6.
e) Correct the off-street loading space size for automotive- major service and repair to "twelve (12) feet by thirty-five (35) feet" in Development Criteria 6.
f) Correct the number of required van accessible spaces from "every 8" to "every 6".

2. Please label the work bays within the building 1 as "Not for Public Access". This will allow the striped five (5) foot pedestrian refuge area to remain as shown on the plan for Building 1.

If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550, ext. 1197.

KAA S:\zoning review\karol\planning\cdrc\developmentplan\D06-0042dpr.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents.
03/09/2007 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D06-0042 RITA RANCH COMMERCE CENTER/REVISED DEVELOPMENT PLAN
DATE: 3/08/07



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE: Approved with the following condition:

1.) Correct Centre to Center (Lot 8, Lot 9) on sheet 1 of mylar.

Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.



es
03/12/2007 ANDY VERA ENV SVCS REVIEW Denied * Enclosure has been repositioned from previous drawing so that the 14'x40' clear approach required is in conflict with curb access ramp. Reposition as previosly shown and it will work.
* Enclosure detail does not meet the required 10ft clear between the side wall protectors per DS. Also, the wall protector needs to demonstrate separation from the wall with a recommended minimum of 6 inches.
03/16/2007 JOE LINVILLE LANDSCAPE REVIEW Denied 1) A vehicular use area must be provided with post barricades or wheel stop curbing (as indicated per keynote 8 on the Development Plan) designed to prevent parked vehicles from extending beyond the property lines; damaging adjacent landscaping, walls, or buildings and to prevent vehicles from driving onto unimproved portions of the site. DS 3-05.2.3.C. Revise the plans as necessary to include a sufficient barrier at the edge of the paved area at the northeast portion of the site. at the perimeter of the repair stalls or whever the pavement terminates.

2) Grading, hydrology, and landscape structural plans are to be integrated to make maximum use of site
storm water runoff for supplemental on-site irrigation purposes. Revise the development and grading plans to comply and show specific water harvesting areas on the landscape plan. The development plan does not currently indicate drainage flow to landscape areas other than the retention/detention basin. LUC 3.7.4.3

3) Revise the landscape plan plant legend and the NPP Mitigation Calculations to conform to the NPP Inventory Totals. The planting plan indicates that 4 barrel cactus are TOS, but the NP Inventory indivcates 12 total. The infornation for Ocotillos is similarly inconsistent. Show all of the native plants on the landscape plan. DS 2-15.3.4.B.


RESUBMITTAL OF ALL PLANS IS REQUIRED.
03/21/2007 FRODRIG2 PIMA COUNTY WASTEWATER Denied March 21, 2007

To: Wayne Royce, Urban Engineering

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________
From: Tom Porter (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Rita Ranch Commerce Centre Lot #34
Development Plan - 2nd Submittal
D06-0042

The proposed final plat for the above-referenced project has been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The development plan for this project cannot be approved until a copy of this letter has been received by this office. This is the 2nd request.

Sheet 1: Item 3 of the 1st review letter sent 12/11/06 has not been addressed. Do not submit for a third review until you can provide the FUE count.

Sheet 2: Revise inverts for the BCS for FUTURE BLDG.#2 to demonstrate required gravity flow

Sheet 2: Revise the plan to show the rim & invert elevations for NEW MANHOLE 1 PER PLAN #G-2006-169

Sheet 2: Revise the plan so that it shows the length and slope of the proposed off-site 10” public sewer, G-2006-169

Sheet 2: Label the future sewer main that you intend to discharge into so that it states something like:

10” SEWER LINE PER PLAN #G-2006-044 TO BE CONSTRUCTED BY OTHERS

Sheet 2: Revise the label at future MH No. 3 so that you add the phrase:

TO BE CONSTRUCTED BY OTHERS

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the 3rd submittal. A check for the review fee of this submittal in the amount of $78 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
03/23/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
03/29/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 29, 2007

Wayne A. Royce
Urban Engineering
877 South Alvernon Way Suite 200
Tucson, Arizona 85705

Subject: D06-0042 Rita Ranch Commerce Center Development Plan

Dear Wayne:

Your submittal of February 15, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

6 Copies Revised Development Plan (Landscape, ESD, Zoning, Wastewater, Engineering, DSD)

4 Copies Revised Landscape Plan (Landscape, Zoning, Engineering, DSD)

2 Copies Revised NPPO Plan (Landscape, DSD)




Should you have any questions, please call me at 791-5608 extension 1179.

Sincerely,


Patricia Gehlen
CDRC Manager