Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/17/2007 FRODRIG2 PIMA COUNTY WASTEWATER Approved October 17, 2007

To: Bruce Wilson, Landmark Engineering

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Tom Porter (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Lucky Wishbone Restaurant
Development Plan – 4th Submittal
D06-0039

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
10/23/2007 KAROL ARAGONEZ ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D06-0039
Lucky Wishbone
Development Plan Resubmittal

TRANSMITTAL DATE: August 28, 2007

DUE DATE: September 14, 2007

COMMENTS:

The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

1. The tentative plat may not have final approval prior to Overlay Zone application approval.

2. Please revise plan view and detail H/4 placing truncated domes in the direction of travel into the access aisle as warning that an individual is leaving the pedestrian path and entering the vehicle use area. The area covered by the truncated domes shall be twenty-four (24) inch deep and extend the full width of the access aisle, preceding the access aisle in the direction of pedestrian travel.


If you have any questions about this transmittal, please call Karol Aragonez, (520) 837-4960.

KAA S:\zoning review\karol\planning\cdrc\developmentplan\D06-0039dpr1.doc
10/29/2007 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Projects subject to the provisions of LUC 2.8, Overlay Zones (SCZ, ERZ, WASH) are reviewed in accordance with the procedures of TCC 23A-51. The DSD full notice procedure requires a separate application and review.
Note the SCZ, ERZ/WASH case # and date of approval on the Development plan.

2) Revise the 5' High decorative masonry wall call-out on the landscape plan so that the leader points to the wall.

3) Per LUC 3.7.3.7.D "Nonwood fences, such as chain link, may not be used along a street frontage along a Gateway Route or within the SCZ". In addition, basins with 4:1 slopes do not require fencing per the Development Standard. In fact the stormwater manual presents requirements and guidelines designed to preclude the need for fencing in most instances.
DS 10-01(p.81)

4) The site is impacted by the floodplain of the West Branch of the Santa Cruz River which is an ERZ wash. The project site contains riparian habitat regulated by the ERZ overlay zone and the floodplain regulations. Approval of the ERZ application is required prior to Development Plan approval. LUC 2.8.6
11/06/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved TO: Patricia Gehlen; CDRC Coordinator DATE: November 6, 2007

SUBJECT: Engineering review of the Lucky Wishbone Development Plan. The activity number is D06-0039.

SUMMARY: The Development Plan and Drainage Report were received by Engineering on October 12th 2007.

DEVELOPMENT PLAN APPROVED
11/06/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

November 6, 2007

Bruce Wilson
Landmark Engineering, Inc.
4625 East Fort Lowell Road
Tucson, Arizona 85712

Subject: D06-0039 Lucky Wishbone Development Plan

Dear Bruce:

Your submittal of October 12, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

2 Copies Revised Development Plan (Landscape, DSD)

2 Copies Revised Landscape Plan (Landscape, DSD)



THE REVIEW PERIOD FOR THIS PROJECT HAS EXPIRED PLEASE CONTACT ME PRIOR TO RESUBMITTAL.


Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 321-0333