Permit Number: D06-0032
Parcel: 13342001F

Address:
1925 N KOLB RD

Review Status: Completed

Review Details: REVISION - DEV PLAN

Permit Number - D06-0032
Review Name: REVISION - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/02/2007 JIM EGAN COT NON-DSD FIRE Approved
07/10/2007 CDRC1 PIMA COUNTY WASTEWATER Approv-Cond July 10, 2007

To: Craig A. Hunt, P.E.
Engineering and Environmental Consultants, Inc.

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

From: Chandubhai C. Patel, P.E., Civil Eng. Manager
Development Review Division (Wastewater)
Pima County Development Services Department

Subject: First Magnus Bank Building
Amended Development Plan - 1st Submittal
D06-032

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

You are proposing, as part of this project, to connect the proposed sewer line into the 8-inch public sewer G-2004-027. This public sewer G-2004-027 is now being formally accepted for service by the PCWMD .

The Pima County Department of Environmental Quality and the Wastewater Management Department hereby approve the above referenced submittal of the Development Plan received by us on June 25, 2007.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to
the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality Department.

Also, air quality activity permits must be secured by the developer or prime contractor from Pima County Department of Environmental Quality before constructing, operating, or engaging in any activity which may cause or contribute to air pollution.

If you have any question regarding the above comments, please do not hesitate to contact me.

Sincerely,





Chandubhai C. Patel, P.E
520-740-6563.


Copy: Project file
07/10/2007 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D06-0032 FIRST MAGNUS NATIONAL BANK/REVISED DEVELOPMENT PLAN
DATE: July 10, 2007



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

1.) Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.




jg
07/17/2007 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#184080 July 17, 2007




Dear Mr.Hunt:

SUBJECT: FIRST MAGNUS NATIONAL BANK - REVISION
D06-0032


Tucson Electric Power Company has reviewed and approved the development plan submitted July 3, 2007 It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. The electrical design has been competed for this project, see attached drawing. Depending on the footers for the drive in teller bays, TEP my need to reroute the duct to the TEP transformer to the east side. The engineer and TEP can discuss this prior to construction to determine if the construction drawing needs to be revised.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Please call the area Designer Nancy DiMaria at (520) 918-8267 should you have any questions.


Sincerely,



Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
cc: D. Elder, EEC
N. DiMaria, TEP
07/25/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approv-Cond July 25, 2007
ACTIVITY NUMBER: D06-0032
PROJECT NAME: First Magnus National Bank Office
PROJECT ADDRESS: 1925 N Kolb Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering recommends a Conditional-approval of the Development Plan. Address the following comments prior to mylar.

1. Call out all curb return radius. Along Kolb Road the access points shall have 25' radius curb returns. All other shall have a minimum 18' radius curb return.(DS 3-01.0 figure 6)

2. Illustrate the schematic striping required along Calle La Paz, and note that dimensions will be provided on the grading plan.


If you have any questions, I can be reached at 791-4259 x305 or Jose.Ortiz@tucsonaz.gov
07/27/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D06-0032 First Magnus National Bank (Revised Dev.Plan)

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-06-24 Alta Vista Communities - Kolb Rd.

NEIGHBORHOOD PLAN: General Plan

GATEWAY : Yes

COMMENTS DUE BY: July 24, 2007

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:
() No Annexation or Rezoning Conditions, Not an RCP
() Proposal Complies with Rezoning Conditions
() RCP Proposal Complies With Plan Policies
(X) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
( ) Tentative Plat
(X) Development Plan
(X) Landscape Plan
( ) Other



REVIEWER: msp 791-4505 DATE: July 24, 2007

Department of Urban Planning & Design Comments
D06-0032 - First Magnus National Bank
July 24, 2007


Staff offers the following comments:

1. Compliance to rezoning case C9-06-24 requires a specific percentage of vegetation within detention basins (rezoning condition # 12) and requires additional landscape material to screen drive thru lanes(rezoning condition # 14). These rezoning conditions need to addressed in the development plan (revised) submittal. Development plan submitted does not include a landscape plan to address these landscape/rezoning requirements.
07/30/2007 WILLDAN ENGINEERING REVIEW Passed
07/30/2007 WILDAN LANDSCAPE REVIEW Passed
07/30/2007 WILDAN ZONING REVIEW Passed
07/31/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 31, 2007

Craig Hunt
Engineering and Environmental Consultants, Inc.
4625 East Ft. Lowell Road
Tucson, Arizona 85712

Subject: D06-0032 First Magnus National Bank Office Building Development Plan

Dear Craig:

Your submittal of June 26, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

3 Copies Revised Development Plan (Traffic, DUPD, DSD)

2 Copies Revised Landscape Plan (DUPD, DSD)

PLEASE NOTE THAT THE ENGINEERING, ZONING, AND LANDSCAPE REVIEWS ARE GOING THIRD PARTY REVIEW (WILDAN). THE ABOVE RESUBMITTAL REQUIREMENTS DO NOT INCLUDE ITEMS NEEDED FOR THOSE REVIEWS.



Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager


All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 321-0333
dp-resubmittal
07/31/2007 ANDY VERA ENV SVCS REVIEW Approved