Permit Number: D06-0028
Parcel: 126070300

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D06-0028
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/20/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
06/20/2007 JIM EGAN COT NON-DSD FIRE Approved
06/25/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approv-Cond DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D06-0028 Lodge On The Desert 06/22/07

( ) Tentative Plat
() Development Plan
() Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other – color elevations, photos of homes in area

CROSS REFERENCE: C9-01-33

NEIGHBORHOOD PLAN: Alvernon-Broadway Area Plan

GATEWAY/SCENIC ROUTE: Alvernon is Gateway Route

COMMENTS DUE BY: July 18, 2007

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies With Plan Policies
() See Comment Attached – Conditionally Approved
() No Additional Comments - Complies With Planning comments submitted on 5/10/07 (subject to minor revisions)

() No Resubmittal Required – change LP mylars, sheets 2, 3, 9/12
( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other – see comments

REVIEWER: J. Hershenhorn 791-4505 DATE: 6/22/07

D06-0028
Lodge on the Desert


Regarding the screen wall along the eastern site boundary, the correct height of 6 feet is shown on the Development Plan (DP), and the DP is approved. The Landscape Plan (LP) is approved subject to the following revisions being made to the mylars:

LP Sheet 2/12 - Remove the “varies” from the wall height (leave the 6’); and
LP Sheets 3/12 and 9/12 – Please change the 5’ wall height to 6’.

No resubmittal is required.
07/11/2007 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D06-0028 LODGE ON THE DESERT/REVISED DEVELOPMENT PLAN
DATE: 7/10/07



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


1.) Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.


ES
07/12/2007 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. The 10-foot landscape border shown on the Landscape Plan (sheet 3 of 12) located near the loading zone and trash pick up area along Poe Street is labeled as being 10 feet but only scales to about 7 feet wide. If the width is enlarged to 10 feet as labeled, the 6' screen wall can extend farther to provide more screening for the loading area without conflicting with sight visibity triangles. Revise to show 10-foot landscape border as labeled.

2. Obtain approval for Alvernon Way, Poe Street and Holmes Street right-of-way improvements and landscaping from the Departrment of Transportation in compliance with the TDOT standard. Street landscape borders shall be a minimum of ten (10) feet wide as measured from the street property line, and located entirely on site. Written approval from the City Engineer is required to allow landscaping in the right-of-way per LUC 3.7.2.4.A.3 and landscape improvements proposed in public right-of-way areas must be approved by the City Engineer or designee and comply with the City Engineer's requirements on construction, irrigation, location, and plant type. Provide verification, in writing, of any approvals obtained. Contact Gary Wittwer, DOT Landscape Architect at (520) 791-5100 for specific requirements.
07/13/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Coordinator DATE: July 13, 2007

SUBJECT: Engineering review of the Lodge on the Desert Development Plan. The activity number is D06-0028.

SUMMARY: The Development Plan and Drainage Report were received by Engineering on June 19th, 2007. Engineering has reviewed the received items and does not recommend approval of the Development Plan or the Drainage Report.

RESUBMITTAL REQUIRED: DEVELOPMENT PLAN, DRAINAGE REPORT

The next submittal must address the following items:

DEVELOPMENT PLAN COMMENTS

1. For basins with a water depth of two feet or more, with slopes steeper than 4 to 1. Provide a security barrier for the north basin depicted on detail D found on sheet 4. It is acknowledged a barrier is provided on the south side of the basin however a barrier must be provided on the north side along the property line. Be advised the barrier must not be located within the SVT.

DRAINAGE REPORT COMMENTS

1. The drainage report provides discussion that the excess flow from the second basin (R2) will over top the basin and exit the site in it's natural path. The 10-year flow must be contained under the pedestrian circulation at all concentrated locations. Provide discussion and appropriate calculations to show the sidewalks/pedestrian circulation will remain flood free in a 10-year event.
07/18/2007 ANDY VERA ENV SVCS REVIEW Approv-Cond 1. The loading zone is now in conflict with the required 14' x 40' clear approach to enclosure area.
Service vehicle will be unable to maneuver to be perpendicular to the enclosure as shown on sheet 2 in turning radii detail.

Recommend positioning loading zone as in previous submittal at the west side of the structure perpendicular to the service entrance/driveway.
ES was able to demonstrate maneuverability of refuse service vehicle (36 ft long) within the loading zone without having to back into ROW. In addition, standard operating procedure for delivery/pick-up service vehicles call for backing into a loading zone. This eliminates backing into moving traffic or ROW since the service vehicle will be performing this action while already within the traffic lane.

Please correct for final approval.
07/20/2007 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Heather Thrall, Senior Planner

PROJECT: D06-0028, Development Plan, 3rd Review
The Lodge on the Desert expansion, 306 N. Alvernon Way

TRANSMITTAL DATE: July 19, 2007

DUE DATE: July 18, 2007

COMMENTS:

1. Per DS 2-05.2.4.A, Please record lot combination and lot combination covenants that were provided to staff. Provide a copy of them, and a copy of the recordation receipt. Provide note on plan with Docket/Page indicating lot combination/covenant performed.

2. Future right of way widening removes a portion of existing building 17, at corner of Poe and Alvernon. Note on plan, next to right of way line going through building, that states "See agreement for future dedication, dated April 3, 1989 -remains in effect. No further improvements can be constructed on the subject area to be dedicated."

3. Per DS 2-05.2.4.K, Staff agrees with your assessment that a pedestrian/accessible route from Holmes to the building site is not required - because the site is designed with criteria meeting DS 2-08.4.1A (continuous wall/emergency access only).

4. Per DS 2-05.2.4.K, with regards to other pedestrian issues -
A) Provide accessible route from Poe to the development per DS 2-08. Per Glenn Moyer, apply for a DSMR to modify sidewalk, or variance to delete it.
B) Provide sidewalk between the existing/future buildings and parking, per DS 2-08. Per Glenn Moyer,- apply for a DSMR to modify sidewalk, or variance to delete it.
C) Provide sidewalks between existing/future buildings and PAALs, per DS 2-09. Per Glenn Moyer,- apply for a DSMR to modify sidewalk, or variance to delete it.
D) Keynote entries to existing buildings and show sidewalk to entries. Sidewalk access is not clear to existing buildings. This is full code compliance - which requires that a continuous pedestrian path is provided to each building on the site.
E) provide truncated domes where transitioning from vehicular to pedestrian use area -even if a ramp is not needed - between buildings 7 & 8 and 4 & 5

5. Per DS 2-05.2.4.M, provide square footage of all buildings and their specific use.
A) What are buildings 16 and 17 use for and what are their square footages?
B) Clarify difference in restaurant size on parking calcs versus square footage on building 15, sheet 6. Additional restaurant facilities are not permitted per rezoning condition 4.

6. (last review) Per DS 2-05.2.4.N, dimension bldg footprint/heights -grade to top of wall
A) provide for buildings 16 & 17 please

7. (last review) Per DS 2-05.2.4.O, Per City Attorney, former variances for loading zones are not applicable to the loading zones needed for NEW development. Provide a second loading zone at 12x35, per LUC 3.4.5.5 and LUC 3.4.5.3.

8. Per DS 2-05.2.4.P, and DS 3-05, with regards to parking:
A) dimension back up spur near building wall 17 (must be 3' deep)
B) (Per last review) Please correct detail drawing D as well (Sheet 2) to show a 2'6" overhang from wheel stop barrier face

9. Per DS 2-05.2.3.B, Provide docket/page, recordation of all easements on the plan.

10. Provide length of all site walls and how they will meet condition 19 of rezoning case.
A) the 12' tall wall proposed at the west property line is over the maximum height allowed per the LUC 3.2.5.2.H, and is not a height required through the rezoning conditions. Revise to meet the LUC 3.2.5.2.H or seek a DDO up to 8' or variance over that height. (The response indicating the variance was granted for this is not applicable, as it is a new wall.)

11. Please be advised, further expansions of the property in the future would be subject to applicable code requirements, and expansions are cumulative towards future full code compliance requirements.

12. Please note, depending upon the responses provided, further review comments may be forthcoming. Should you have any questions, please contact me at Heather.Thrall@tucsonaz.gov or 837-4951.

If you have any questions about this transmittal, please call (520) 791-5608.

C:\planning\cdrc\developmentplan\D06-0028 306 n alvernon lodge on desert 3.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, and additional requested documents.
07/30/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 30, 2007

Dan Elder
Engineering and Environmental Consultants
4625 East Fort Lowell Road, Suite 200
Tucson, Arizona 85712

Subject: D06-0028 Lodge on the Desert Development Plan

Dear Dan:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 321-0333