Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D06-0024
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
08/16/2007 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: D06-0024
Hemisphere Corporate Center
Development Plan

TRANSMITTAL: August 03, 2007

DUE DATE: August 31, 2007

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is 06/05/08.

2. The language appears to be OK. Exhibit C was not provided with the agreement therefore zoning could not verify if the area is described correctly, please provide Exhibit C. DS 2-05.2.4.A, Based on your response to comments a cross access agreement is to be provided, provide docket and page recordation information on the plans as well as a copy of the agreement at next submittal.

3. It appears that there are truncated domes located near the entrance to Building 2, if so please indicate with keynote 18. It is unclear if there are bollards, if you indicate by note. This comment has not been addressed. It appears that there are bollards or some type of barrier shown indicate what type it is. If the concrete is flush with the pavement then Detectable Warnings (truncated domes) are required. Clearly indicate the required physical separation for sidewalks in several areas: The main entrances to buildings 2,3 & 4 (no curbs, barriers or handicap ramps are indicated)

4. This development can not be approved until the Wash Overlay Zone review has been approved.

5. Depending on changes to the plan and responses to the above comments further comments may be forth coming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\cdrc\developmentplan\D06-0024dp-3rd.doc
08/17/2007 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The project is subject to the provisions of the Watercourse, Amenities, Safety, and Habitat Ordinance, TCC 29. A separate application and review is required prior to development plan approval. If approval is granted, add the file number and approval date to the development plan in the general notes.

2) The project includes encroachments that are beyond the scope of "necessary development"as described in DS 2-13.2.5.B.2. A DSMR or variance will be necessary for this level of impact to the PRA.


RESUBMITTAL OF ALL PLANS IS REQUIRED
08/20/2007 JASON GREEN ENGINEERING REVIEW Denied DATE: August 20, 2007
SUBJECT: Hemisphere Corporate Center Development Plan-3rd Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 6300 S Palo Verde Road, T15S R14E Sec09 Ward 5
REVIEWERS: Jason Green, CFM
ACTIVITY: D06-0024


SUMMARY: Engineering Division of Development Services Department has received, Sheets 1 through 10 of the revised proposed development plan and landscape plan. Engineering Division has reviewed the submitted development plan and does not recommend approval of the development plan at this time. The following items need to be addressed:


Development Plan: Per a meeting with DSD Landscaping and Engineering on August 14, 2007 a DSMR and a new revised Development Plan is required to be submitted showing a slightly wider channel with undulating side slopes and more vegetation. This meeting took place after this Development Plan submittal (August 2, 2007) and does not reflect what was discussed at the later meeting. A new revised Development Plan with an approved DSMR is required prior to approval.

1) The proposed parking lot area and trash enclosure within the 50' W.A.S.H. overlay zone is not approved at this time until approval of the W.A.S.H. Ordinance Report through CDRC. The development plan will not be approved until approval of the DSMR and the W.A.S.H. Ordinance Report.

2) Revise Sheets 3 and 4 to provide the recordation information for the cross access agreement that is shown on both sheets. The cross access agreement must be recorded prior to Development plan approval.

3) Revise Sheet 5 to provide the 20-foot dimension for the "Enhanced Landscape Area" that is shown on this sheet.

4) Revise Sheets 7 and 8 to provide cross sections with details for both the proposed channel along the north portion of the lot and for the new driveway entrance and the proposed 3 cell 8' x 3' RCBC.

5) Revise Sheet 9 to provide the following required improvements that satisfy TDOT requirements, the W.A.S.H. Ordinance Report, and the August 6, 2007 meeting with Development Services Engineering Division.

a) Revise the outlet bleeder pipe from the retention basin to meet the minimum TDOT requirements for culverts and pipes into a public right-of-way. An 18" RCP with a 6" orifice at the inlet and a flap gate at the outlet is required. Provide approval from TDOT that this design is acceptable.

b) Clarify within the drainage report the new proposed spillway reference into the Rodeo Wash. Per the W.A.S.H. Ordinance Report a new spillway is not proposed for this project.

c) Per the meeting with Elizabeth Eberbach, PE and Matt Flick, PE of DSD Engineering a minimum 1% slope is required within the bottom of both retention/detention basins to assure positive drainage. The proposed Development Plan calls out only 0.5% longitudinal basin bottom slopes, revise.

6) Revise Sheet 10 to provide the cross section locations or detail call out for the retention/detention basin located along the eastside of the property. Verify that handrails are installed along the entire length of basin and channel at the 1:1 slope locations.

7) It is understood that a DSMR will be required for this project due to the disturbance within the protected riparian area. The DSMR must be approved prior to Development Plan approval. All exhibits and discussion must reflect any changes made by the approved DSMR.

8) Per the meeting with DSD Landscaping and Engineering on August 14, 2007 provide cross sections with details for the depressed planting areas along the Rodeo Wash, south side of site and east side of site.


DRAINAGE REPORT:

9) DS Sec.10-02.2.3.1.6.B.1-3: Revise the drainage report to meet the minimum standards for development within a Critical Basin. On Page 7, Section C, Onsite Runoff for existing and Developed Conditions, with Retention Table shows that the 2- and 10-year flow events are not reduced by the required 15%. Development within a critical basin must provide a 15% reduction in the developed conditions for the 2-, 10-, and 100-year flow events relative to the existing conditions. Revise the calculation, design layout and tables to show that these requirements have been met. Per DS Sec.10-01.1.4 and 2.3 stormwater detention requirements may not be waived if the proposed development is located within a critical basin.

10) Revise the drainage report to accurately reflect the required DSMR and the W.A.S.H. Ordinance Report. The drainage report discussion does not match the discussion within the W.A.S.H. Report. Specifically the project does not call for a proposed spillway into the Rodeo Wash. The spillway discussion must be omitted form the drainage report.

11) Revise the drainage report exhibits and discussion to meet the minimum TDOT requirements for culverts and pipes into a public right-of-way. An 18" RCP with a 6" orifice at the inlet and a flap gate at the outlet is required.

12) Per the August 6, 2007 meeting with Elizabeth Eberbach, PE and Matt Flick, PE of DSD Engineering a minimum 1% slope is required within the bottom of both retention/detention basins to assure positive drainage. The proposed Development Plan calls out only 0.5% longitudinal basin bottom slopes, revise.


GENERAL COMMENTS:

Provide an approved DSMR, a revised development plan, a revised drainage report, and an approved landscape plan that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

Further comments may be generated upon resubmittal of the DSMR, development plan, drainage report, and landscape plan, reviews.

If you have questions or would like to set up a meeting, call me 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services
08/31/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

August 31, 2007

Tri Miller
Rick Engineering Company
1745 East River Road, Suite 101
Tucson, Arizona 85701

Subject: D06-0024 Hemisphere Corporate Center Development Plan

Dear Tri:

Your submittal of August 3, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

5 Copies Revised Development Plan (Landscape, Traffic, Engineering, Zoning, DSD)

4 Copies Revised Landscape Plans (Zoning, Landscape, Engineering, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)

2 Copies Cross Access Agreement (Zoning, DSD)


Should you have any questions, please call me at 837-4919.




Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 322-6956
08/31/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approv-Cond The development plan does not accurately illustrate the recommended striping as indicated in the TIA. Revise plans and schematically illustrate the recommended striping per the TIA. Final approval of the striping will be provided during the PIA review process.