Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: D06-0022
Parcel: 12510003F

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D06-0022
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/21/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied May 23, 2006

TO: Pattie Davis
MMLA-Psomas

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: El Con Mall, Ross Store and Building G
Development Plan – 1st Submittal
D06-0022


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


SHEET 1. Revise General Note 44 as follows and fill in the blanks appropriately. It is highly unlikely that El Con Mall has 85 existing wastewater fixture unit equivalents. The purpose of this note is to keep an accurate count of all existing and all proposed wastewater fixture unit equivalents within El Con Mall.

THIS PROJECT HAS ____ PROPOSED AND ____ EXISTING WASTEWATER FIXTURE UNIT EQUIVALENTS, PER TABLE 13.20.045(E)(1) IN PIMA COUNTY CODE 13.20.045(E).

SHEET SP 1.7. As previously requested on May 23, 2006, the sewer layout shown on this sheet shall be such that streets, PAALs, buildings and landscaped areas are all shown as well, in order to verify accurate geographical location of sewer lines and geographical position of these in relation to the proposed project. Revise accordingly.

SHEETS SP 1.4, SP 1.5 & SP 1.7. Revise the sewer layout on this sheet so that the proposed private sewers and the existing public sewers match the symbols defined on sheet SP 1.3.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 3rd submittal. A check for the review fee of this submittal in the amount of $117.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
07/21/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied July 25, 2006

TO: Pattie Davis
MMLA-Psomas

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: El Con Mall, Ross Store and Building G (REVISED)
Development Plan – 1st Submittal
D06-0022


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

After further discussions with MMLA-Psomas, the following revised wastewater review comments are provided:

SHEETS SP 1.4, SP 1.5 & SP 1.7. Revise the sewer layout on this sheet so that the proposed private sewers and the existing public sewers match the symbols defined on sheet SP 1.3.

Subject to the above required revisions, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Department of Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.




If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
07/31/2006 PETER MCLAUGHLIN ZONING REVIEW Approved CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D06-0022
El Con - Ross and Space "G"
Development Plan Resubmittal

TRANSMITTAL DATE: July 19, 2006

DUE DATE: August 16, 2006

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The electrical easement detailed in keynote 11 on sheet SP 1.5 must be abandoned prior to issuance of a building permit (prior to approval of this development plan). Please provide documentation as to its abandonment.


If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550.

KAA C:\planning\cdrc\developmentplan\D06-0022dpr.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Requested documents

CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D06-0022
El Con - Ross Space "G"
Development Plan Revised Comments

TRANSMITTAL DATE: July 19, 2006

DUE DATE: August 16, 2006, Revised August 29, 2006

COMMENTS: The Zoning Review Section approves the development plan for this project. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550.

KAA C:\planning\cdrc\developmentplan\D06-0022dprev.doc
08/07/2006 JOSE ORTIZ ENGINEERING REVIEW Approv-Cond August 7, 2006
ACTIVITY NUMBER: D06-022
PROJECT NAME: El Conl-Ross Store/BLDG G
PROJECT ADDRESS: El Con Mall
PROJECT REVIEWER: Jose E. Ortiz PE, Civil Engineer

Engineering recommends a Conditional Approval for the proposed Development Plan. The following items must be revised or added to the plans for final approval to the Development Plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. Tie the referenced brass cap on Broadway to the Basis of Bearing referred to on Sheet SP 1.3 note 2. If applicable, please provide the information stamped onto the referenced brass cap

3. Provide additional dimensions in the east to west direction of the proposed improvement areas.



If you have any questions, I can be reached at 791-5640 x1191 or Jose.Ortiz@tucsonaz.gov
08/28/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D06-0022 El Con – Ross and Space “G” 08/25/06

( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-56-01, C9-74-34, C9-88-12

NEIGHBORHOOD PLAN: Alvernon-Broadway Area Plan

GATEWAY/SCENIC ROUTE: Broadway (Gateway)

COMMENTS DUE BY: August 16, 2006

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on: 6/12/06
( ) No Resubmittal Required:
() Tentative Plat
( ) Development Plan
( ) Landscape Plan
() Other







It should be noted that the applicant will include a note on the
plat to read “That although the western side of the Ross site is not part of this project, that the landscaping will be replaced once utilities are ran to the Ross site.”

This can be checked at Development Services, no need to resubmit.
08/30/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

August 30, 2006

Pattie Davis
MMLA Psomas
800 East Wetmore Road, Suite 110
Tucson, Arizona 85719

Subject: D06-0022 El Con - Ross and Space G Development Plan

Dear Pattie:

Your submittal of July 19, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

2 Copies Revised Development Plan (Wastewater, DSD)




Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 292-1290