Permit Number: D06-0017
Parcel: 136313180

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D06-0017
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
08/28/2006 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The project is subject to the provisions of the Scenic Corridor Overlay Zone. LUC 2.8
A new Scenic Corridor Zone (SCZ) application is required for this project. Applications for projects within the Scenic Corridor Zone (SCZ) shall be reviewed in accordance with the DSD Full Notice Procedure, Sec. 23A-50 and 23A-51. Contact Patricia Gehlen-Zoning Manager for application information. The decision to approve or deny the project will be based on the purpose, intent, and specific regulations of LUC 2.8.2. Revise general note 5 on sheet 1 of the development plan by removing the portion of the last line that reads "per approved SCZ 02-05".

2) Remove the label on landscape plan sheet 1 of 3 regarding Landscape Border #1 stating that 10 feet in right-of-way was approved by SCZ 02-05 and revise the keynote 23 on the development plan (see comment 1). Within the 30' scenic route buffer area, indigenous plant material is to remain. If any disturbance occurs during construction or prior to permit application, the buffer area is to be revegetated with native plants indigenous to the site and the area reconstructed to look as natural as possible. DS 2-06.7.1.B

3) Landscape borders proposed in right-of-way or MS&R areas must be approved by the City Engineer or designee and comply with the City Engineer's requirements on construction, irrigation, location, and plant type. Provide verification, in writing, of any approvals obtained. Contact Gary Wittwer, DOT Landscape Architect for specific requirements.

4) Dimension the length and width of landscape borders on the landscape plan per DS 2-07.2.2.A.2.f. Include the dimensions for the portion of the required 30-foot SCZ border located to the north of the project entry drive along Houghton Road. There is no treatment shown for this area on the landscape plan. Revise to include dimensions and preservation of existing vegetation or include a revegetation plan.

5) Identify the location, purpose and dimensions on the landscape plan of all utility easements and facilities. DS 2-07.2.2.E

6) Revise the landscape plan to show the locations and note the height and materials used to construct any proposed or required screen walls. A 30" screen is required along Houghton Road. A 6-foot screen wall is required to screen the loading area and trash enclosure from the street and adjacent residentially zoned properties per LUC table 3.7.2-I. Include details regarding refuse screening. A 5-foot screen wall is required to screen the proposed use and parking lot from adjacent residentially zoned properties. Add the following required general note to the landscape plan: The height of screening materials is measured on the project side of the screen, at finish grade. DS 2-05.2.4.X, DS 2-06.3.7.A.1, DS 2-07.A.3, LUC Table 3.7.2-I

7) An unpaved planting area, which is a minimum of thirty-four (34) square feet in area and four
(4) feet in width, must be provided for each canopy tree. Dimension the unpaved areas of the parking lot planters on the landscape plan.

8) Revise the landscape plan for the Irvington Road landscape border. The screening plants are not calculated as part of the 50% vegetative groundcover requirement.

Revise the landscape plan to show the limits of grading.
The development plan appears to show a grade change in the scenic route buffer area, DP3, section K.

9) The development plan indicates a proposed 10' utility and pedestrian easement in the scenic route buffer area. The easement conflicts with LUC 2.8.2.4. which requires the buffer area to be preserved and maintained in its natural state or restablished with native vegetation.

RESUBMITTAL OF PLANS IS REQUIRED.
08/30/2006 JCLARK3 ENV SVCS REVIEW Denied * Response states that the enclosure have been updated with a 10 clear area. Clear area required between the side wall protection and between the rear wall protection and the gates per the Development Standards. Detail does not show this 10' clear area.
08/31/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D06-0017 Quik Mart @ Houghton/Irvington 08/30/06

() Tentative Plat
(XXXX) Development Plan
(XXXX) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-97-08, SCZ-02-05, C15-87-03, S02-043


NEIGHBORHOOD PLAN: South Pantano

GATEWAY/SCENIC ROUTE: Houghton

COMMENTS DUE BY: 09/21/06

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
(XXXX) No Additional Comments - Complies With Planning Comments Submitted on: 05/05/06
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER: D. Estolano 791-4505 DATE: 08/30/06
09/08/2006 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D06-0017
Quik Mart at Houghton/Irvington
Development Plan Resubmittal

TRANSMITTAL DATE: September 8, 2006

DUE DATE: September 21, 2006

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Revise general note 2. List the proposed use of the car wash as "Automotive Minor Service and Repair (Car Wash)"
DS 2-05.2.2.B.3

2. A handicap ramp is required at the south end of the indicated crosswalk to the sidewalk connecting to the pedestrian circulation path of Irvington RD.

3. The pedestrian path provided running north and south from the access PAAL from Houghton Road, running in front of the car wash to the proposed retail building 2 is not designed as a safe route. Much of the pedestrian path is cross walk that is parallel to a PAAL. The pedestrian path shown running to the west of the car wash appears to be a safer route. Staff would recommend that the applicant remove path running along the east of the car wash. A five foot pedestrian refuge area which includes a four (4) foot sidewalk must be provided between the storage room and the PAAL south and remove the access ramp east of the storage room, and the ramp connecting to the removed path at the northeast corner of the building 2.
DS 2-08.4.1.B & DS 3-05.2.2.B.1

4. Access ramps at crosswalks connecting to sidewalks must be provided. In addition Truncated Dome (early warning systems) must be added to all access ramps where transitioning from the pedestrian area to the vehicular use area or at HC access aisles transitioning to the sidewalk area. Please revise keynote 9 adding the use of truncated domes.
ANSI 406.12, ANSI 705

5. Please clearly indicate the "vacuum bay" and the required stacking space and the required stacking space for the automated car wash. The length of a stacking space is eighteen (18) feet.
LUC 3.3.4 Commercial Services Use Group & DS 3-05.2.1.C.2.d

6. Please add verbiage to the handicap signage "DO NOT BLOCK" and "$518 FINE". Revise note 1 to state "the sign to be less than seven (7) feet above finish grade" as per TDOT requirements.

7. Depending on changes to the plan and responses to the above comments further comments may be forth coming.

If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550.

KAA S:\zoning review\karol\planning\cdrc\developmentplan\D06-0017dpr.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents.
09/18/2006 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D06-0017 QUIK MART @ HOUGHTON/IRVINGTON/REVISED DEVELOPMENT PLAN
DATE: September 18, 2006



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.




jg
09/22/2006 JOSE ORTIZ COT NON-DSD TRAFFIC Denied September 22, 2006
ACTIVITY NUMBER: D06-0017
PROJECT NAME: Quik Mart-Houghton/Irvington
PROJECT ADDRESS: 10265 E Irvington Road
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Development Plan; therefore a revised Development Plan is required for re-submittal.

The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. The raised diverter at the southeast driveway needs to be modified to force motorist to make a right turn. The diverter needs to be called out and a detail maybe warranted to provide needed dimensions for the construction of this diverter.


If you have any questions, I can be reached at 791-4259 x305 or Jose.Ortiz@tucsonaz.gov
09/25/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied September 23, 2006

TO: Joe Zeman
EEC

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: R S Engineering (Contract Reviewer)
Chandubhai Patel, P.E.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Quik Mart (Houghton & Irvington)
Development Plan – 2nd Submittal
D06-0017


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



SHEET 2. A sewer line identified as “4” BLDG. SEWER” is shown at the top of the plan on page 2 of 3. The line is coming from the proposed car wash and has CO #2 on it. Where does this sewer line go and what does it connect to? Provide length, slope, and any other relevant details. This line was not shown on the first submittal.


We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.


The next submittal of this project will be the 3rd submittal. A check for the review fee of this submittal in the amount of $39.00 per sheet, made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.


For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Chandubhai Patel, P.E.
Telephone: (520) 740-6586

Copy: RSE Job# 0432.55
10/06/2006 LOREN MAKUS ENGINEERING REVIEW Denied DATE: October 6, 2006

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Loren Makus, EIT
Engineering Division


SUBJECT: Quik Mart at Houghton/Irvington
Development Plan D06-0017 (Second Review)
T14S, R15E, Section 35

RESUBMITTAL REQUIRED: Revised Development Plan, ,

DEVELOPMENT PLAN

1. As previously commented, show sight visibility triangles for the intersection of Houghton Road and Irvington Road. Provide and label both existing and future SVTs.
2. As previously commented, provide and label future SVTs for the PAALs at Houghton Road.
3. As previously commented, clarify the right-of-way dimension for both Houghton Road and Irvington Road. Revise the dimension for Irvington Road to indicate that the future width of Irvington is 150 feet for the first 300 feet from the intersection centerline (intersection widening).
4. As previously commented, clarify the existing conditions in the right-of-way adjacent to this project location. New sidewalks within the right-of-way must be 6 feet wide. Curbs are required. If the Department of Transportation has provided instructions to complete the project in a different configuration, provide copies of communications that clarify their instructions.
5. As previously commented, provide truncated dome tactile warning at each curb access ramp. Truncated domes are required wherever pedestrian use areas and vehicle use areas abut without a vertical separation.


If you have any questions, I can be reached at 791-5550 x1161 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate
10/17/2006 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: October 16, 2006

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov

CC:


SUBJECT: D06-0017 Quik Mart@Houghton-Irvington: Development Plan(8-23-06)


Approved.
10/20/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

October 20, 2006

Joe Zeman
Engineering & Environmental Consultants, Inc.
4625 East Fort Lowell Road
Tucson, Arizona 85712

Subject: D06-0017 Quik Mart at Houghton and Irvington Development Plan

Dear Joe:

Your submittal of August 23, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

7 Copies Revised Development Plan (Environmental Services, Wastewater, Engineering, Landscape, Zoning, Traffic, DSD)

4 Copies Revised Landscape Plans (Zoning, Landscape, Engineering, DSD)





Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 321-0333