Permit Number: D06-0014
Parcel: 105110700

Address:
4328 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D06-0014
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/10/2006 JOE LINVILLE LANDSCAPE REVIEW Approved
07/13/2006 JCLARK3 ENV SVCS REVIEW Approved
07/18/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied July 17, 2006

TO: Thomas Sayler-Brown, A.I.A.
Sayler-Brown Bolduc Lara Architects LLC

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Chandubhai C. Patel, P.E.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Corner Retail Center, Lot 9
Development Plan – 2nd Submittal, D06-0014


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Sheet DP2: Based on how the legends are shown for the existing and proposed sewers, it is not clear which sewers are existing and which are proposed. These sewers should be labeled as existing or proposed for the purpose of clarification.

We will require a revised set of drawings. Addtional comments may be made during the review of these documents.

The next submittal of this project will be the 3rd submittal. A check for the review fee of this submittal in the amount of $117.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines .

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions , please contact me.

Sincerely,


Chandubhai C. Patel, P.E.
Telephone: (520) 740-6563

Copy: Project
07/28/2006 FRODRIG2 COT NON-DSD REAL ESTATE Denied If any right of way needs to be dedicated per Special Exception conditions No. # 2 and 3, please submit to the Real Estate Division a legal description with sketch for the area of dedication.

Jim Stoyanoff
Real Estate Division, 6th Floor
Public Works Building
201 N. Stone Avenue
08/04/2006 JOSE ORTIZ ENGINEERING REVIEW Approv-Cond August 4, 2006
ACTIVITY NUMBER: D06-0014
PROJECT NAME: Corner Retail Center, Lot 9
PROJECT ADDRESS: Oracle Rd/Wetmore Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Civil Engineer


Resubmittal Required: Engineering recommends a conditional approval for the Development Plan.

The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. Provide an exhibit or illustrate on the plans the turning movements of loading/solid waste vehicles entering and exiting the proposed loading zones/refuse areas. The proposed parking garage poses maneuverability restrictions for loading vehicles entering and exiting the loading zones and refuse areas for buildings 9-11, & 13.

3. The 5-story garage will generate a high volume of daily trips and most likely will exceed 100 ADT; therefore a larger radius for the curb return entering the garage is warranted. Per D.S. 3-01.4.3 and D.S. 3-01 figure 6 an 18' return radius is required.

4. This comment can be addressed during the grading plan stages, but be advised that the close proximately of the retention basins to the structures will require a geo-tech report. The report shall address the type(s) of treatment(s) to the proposed structures and/or retention basins to prevent adverse conditions to the underlying foundations to the proposed structures.



If you have any questions, I can be reached at 791-4259x305 or Jose.Ortiz@tucsonaz.gov
08/30/2006 FRODRIG2 ZONING REVIEW Approved CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: D06-0014
Corner Retail, Lot 9
Development Plan Resubmittal

TRANSMITTAL DATE: July 7, 2006

DUE DATE: August 4, 2006

COMMENTS: The Zoning Review Section approves the development plan for this project. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.


If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550.

KAA C:\planning\cdrc\developmentplan\D06-0014dpr.doc
09/08/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

September 6, 2006

Thomas Saylor Brown, AIA
Sayler-Brown Bolduc, Lara Architects, LLC
1001 North Alvernon Way, Suite 105
Tucson, Arizona 85711-1019

Subject: D06-0014 Corner Retail, Lot 9 Development Plan

Dear Thomas:

Your submittal of July 7, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval of the Development Plan is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed.

ALL BLUELINES MUST BE FOLDED

3 Copies Revised Development Plan (Real Estate, Wastewater, DSD)





Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 620-0535