Permit Number: D06-0007
Parcel: 11202034C

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D06-0007
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
05/26/2006 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1) Calculate the percentage of oasia area and note on the plan. PAD 11 3.5.3.1.b

2) There is an inaccessible dumpster shown in water harvesting basin near the southeast corner of the project area. Revise landscape and NPP plans.

3) Revise the NPPP to clarify the limits of grading. The lines on the plan do not correspond with the line legend.
DS 2-15.3.4.A

4) Revise the NPPP to incorporate the new sewer line and asphalt path shown on the development plan. These were not included in the NPPP for the adjacent UMC site.
DS 2-15.3.4.A

5) The minimum required text size is 12 point (12"). Revise the right-of-way dimensions in the aerial photo on sheet N-1 to meet this minimum standard.
DS 2-03.2.1.C

6) Per UMC PAD document section 3.5.3.5.b, a 6-foot screen is required to screen the loading zone from adjacent street frontage.

7) It is not clear on the landscape plan what the enclosure is intended for at the end of the truck turnaround spur near the southeast corner of the site. This enclosure does not appear on the development plan. Clarify, revise or remove this feature. The landscape plan should match the development plan as far as all structural elements, including buildings, vehicluar use area, walls and fences, being shown. Revise where necessary.

8) Reference the previous development plan (D05-0035) on all sheets of the development plan, landscape plan and NPP Plan.
DS 2-07.2.1.B.h
05/31/2006 FRODRIG2 PIMA COUNTY WASTEWATER Denied May 31, 2006

TO: Ray Allan Brown, P.E.
Tetra Tech, Inc.

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: The Ronald McDonald House
Development Plan – 2nd Submittal
D06-007


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


A Sewer Service Agreement for the proposed number of wastewater fixture unit equivalents has been sent to your office. After three original Sewer Service Agreements have been signed by the Owner of Record, the three originals should be returned to Pima County Wastewater Management in order to satisfy the necessary requirements needed to approve of the development plan.

SHEETS 3 & 4. Show the rim and invert elevations for all newly proposed cleanouts/manholes.

SHEETS 3 & 4. Revise the proposed private sewer design so that the distance between proposed cleanouts does never exceed one hundred feet.

SHEETS 3 & 4. Show the size, six-digit Pima County manhole numbers and Pima County plan number for the existing public sewer in a clear and large enough font so it can be easily read.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 3rd submittal. A check for the review fee of this submittal in the amount of $78.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
06/05/2006 JCLARK3 ENV SVCS REVIEW Approv-Cond * THe enclosure location can be serviced. The conditional comment is because the enclosure does not have ten feet of clear area between the wall protection. No wall protection is shown for the side walls.
06/16/2006 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends approval of this Development plan.
06/22/2006 JOSE ORTIZ ENGINEERING REVIEW Approv-Cond June 22, 2006
ACTIVITY NUMBER: D06-0007
PROJECT NAME: Ronald McDonald
PROJECT ADDRESS: 3838 N CAMPBELL AVE
PROJECT REVIEWER: Jose E. Ortiz PE, Civil Engineer



Engineering recommends a CONDITIONAL APPROVAL for this project. The following items must be revised or added to the plan.

1. Sheet 3: Curb and Gutter should be used along Allen Road versus the proposed vertical curb called out in keynote 17.

2. Sheet 3: Cannot locate keynotes 5, 7, and 8 in plan view.

3. To prevent delay with the approval of the Development Plan and confusion during construction remove the Grading Plan and SWPPP sheets from this set. The Grading Plans and SWPPP will be reviewed under activity number T06BU01321.



If you have any questions, I can be reached at 791-5640 x1191 or Jose.Ortiz@tucsonaz.gov
06/26/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D06-0007 Ronald McDonald House 06/22/06

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: UMC North Medical Park (PAD-11)

NEIGHBORHOOD PLAN: Northside Area Plan

GATEWAY-ROUTE: Yes

COMMENTS DUE BY: 6/22/06

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
(X) No Additional Comments - Complies With Planning Comments Submitted on: 3/06/06








REVIEWER: msp 791-4505 DATE: 6/22/06
06/27/2006 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: David Rivera
Principal Planner

PROJECT:
D06-007
Ronald McDonald House
A portion of the UMC Medical Park PAD District
2nd review

TRANSMITTAL: June 27, 2006
DUE DATE: June 22, 2006

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Label the location of bicycle parking clearly on the plan with a keynote and dimension the bicycle parking fully with a detail per DS 2-09. DS 2-05.2.4.Q

2. In situations where required parking is to be located off-site, a site plan of the off-site parking area, a lease agreement for the parking and a letter of intent (Parking Agreement) are required. The site plan must contain calculations to indicate compliance for the adjacent existing project/development. The off-site parking spaces may be applied towards meetinf required parking only if there is a sufficient surplus on the adjacent site to allow these spaces to be used for the new proposal. Submit plan w/parking calculations demonstrating compliance along with the required lease agreement and parking agreement. DS 2-05.2.1.K

3. All lettering and dimensions must be a minimum of twelve point (0.12 inches) in size. Revise all text in the maps on sheet 1 of 7 to meet this minimum archiving standard DS 2-05.2.1.C

4. The building area stated on the drawing on sheet 3 of 7 read 10,246 square feet but general note 6 on sheet 2 of 7 reads 24,250 square feet.
PAD Sec. 3.4.2.7
DS 2-05.2.4.N

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791
07/13/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 13, 2006

Ray Brown
Tetra Tech Inc.
33 North Stone Avenue, Suite 1500
Tucson, Arizona 85701-1413

Subject: D06-0007 Ronald McDonald House Development Plan

Dear Ray:

Your submittal of May 24, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

6 Copies Revised Development Plan (Environmental Services, Wastewater, Landscape, Zoning, Engineering, DSD)

4 Copies Revised Landscape Plans (Zoning, Landscape, Engineering, DSD)

2 Copies Revised NPPO Plans (Landscape, DSD)


Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/