Permit Number: D06-0005
Parcel: 13824078A

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D06-0005
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
05/12/2006 JIM EGAN COT NON-DSD FIRE Approved
05/15/2006 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond Verify that 5' wall along eastern property boundary provides required screening above finished grade of vehicular use area on construction and grading plans.
05/16/2006 FRODRIG2 PIMA COUNTY WASTEWATER Approved May 16, 2006

TO: Kevin Hall
DCC Company

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Merit Foods
Development Plan – 2nd Submittal
D06-005


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project is hereby approved as submitted.


If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
05/25/2006 JCLARK3 ENV SVCS REVIEW Approved * Talked with Kevin Hallof DDC. Land Use Code does not supercede Section 6 of the Development Standards for requirements of an enclosure for the metal dumpster.
July 18, 2006
* Architect submitted a detail of the enclosure that showed doors and sidewall protection. Detail meets development standards. ES has no objections with the enclosure.
06/15/2006 LOREN MAKUS ENGINEERING REVIEW Approved DATE: June 15, 2006

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Loren Makus, EIT
Engineering Division


SUBJECT: Merit Foods
Development Plan D06-0005 (Second Review)
T15S, R13E, Section 15

RESUBMITTAL REQUIRED: None

The Engineering Division has reviewed this Development Plan and recommends approval.
If you have any questions, I can be reached at 791-5550 x1161 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate
07/11/2006 FRODRIG2 ZONING REVIEW Approved CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: D06-0005
Merit Foods
Development Plan

TRANSMITTAL: 07/11/06

DUE DATE: 05/22/06

COMMENTS:


1. The Zoning Review Section approves the development plan for this project. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.


If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.

TLS C:\planning\cdrc\developmentplan\D065-0005dp.doc
07/12/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 12, 2006

Kevin Hall
DCC Company
2828 North Country Club Road, #100
Tucson, Arizona 85716

Subject: D06-0005 Merit Foods Development Plan

Dear Kevin:

Your submittal of May 8, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

2 Copies Revised Development Plan (Environmental Services, DSD)

2 Copies Revised Landscape Plans (Environmental Services DSD)





Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/