Permit Number: D06-0004
Parcel: 141185520

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D06-0004
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
01/27/2006 JIM EGAN COT NON-DSD FIRE Denied Provide a General Note on th eplan stating: " Additional fire hydrants shall be provided by the Developer in accordance with the Tucson Fire Code."
02/03/2006 JCLARK3 ENV SVCS REVIEW Approved * No known landfill with in 1000 feet of this development.
* Shown dumpster enclosure OK for metal service.
* No provisions shown or stated for recycling.
* Access to enclosures is OK.
02/07/2006 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D06-0004 RITA RANCH COMMERCE CENTER/DEVELOPMENT PLAN
DATE: February 7, 2006



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

1: Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved
Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima
County Addressing prior to assignment of addresses.

2: All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.














jg
02/10/2006 RICHARD WILLIAMSON TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approv-Cond Conditioned upon meeting Tucson Water requirements for water service.
02/17/2006 PMCLAUG1 LANDSCAPE REVIEW Denied 1. Add the development plan case number (D06-004) to the lower right hand corner of all sheets of the Development Plan, Landscape Plan and NPPO Plan.
DS 2-03.2.2.B.1

2. Revise the height of the screen wall for the dumpster to be 6 feet. A 6' wall to screen the loading area from the adjacent MS&R right-of-way is also required per LUC Table 3.7.2-I. Identify the wall location on the landscape plan.

3. Within vehicular use areas, one (1) canopy tree is required for each 10 motor vehicle parking spaces or fraction thereof, and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a. Revise landscape plan drawing accordingly and revise the parking lot tree calculation note. For a total of 35 spaces provided, four (4) canopy trees are required to meet code requirements.

4. Both the proper and common name of each type of plant material must be listed. The common names "hardy" and "compact" are not recognized.

5. Dimension all landscape areas on the landscape plan drawing per DS 2-07.2.2.A.2. An unpaved planting area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree per LUC 3.7.2.3.A.1.c. and DS 2-06.3.3.C

6. Label the name of the adjacent street and dimension its existing and future right-of-way on the landscape plan drawings.

7. Refer to DS 2-07.2.2 and DS 2-06.5.4 for the specific content required in required grading information. Revise landscape plan to include required content and specifications. Grading information on the landscape plan shall include contour lines, spot elevations, percent slope across the site and direction of slope of paved areas, depths and slopes of basins, existing grades on adjacent rights-of-way and adjacent sites, and the methods by which water harvesting/ storm runoff is used to benefit planting areas on the site. DS 2-07.0, LUC 3.7.4.3.B

8. Add a calculation of the percentage of landscape area coverage per DS 2-07.2.2.2.g.

9. Add the future sight-visibility triangles (SVTs) to the landscape plan. LUC 3.7.2.8 & DS 2-06

10. The square footage of the building is inconsistent between the development plan, which reads 5,637 square feet and the landscape plan, which reads 5,682 square feet. Clarify and revise calculations for consistency.

11. The tax parcel number as given in the legal description on the landscape plan sheet 1 of 3 and the NPPO exception plan sheet 1 is incorrect. The parcel code should read: 141-18-5520.

12. The address on the landscape plan is incomplete. Place the project address number (9367 E. Old Vail Road) in general landscape note 2 on sheet 1 of 3.

13. Provide a signed statement from a plant professional who has visited the site and verified that viable protected native plants are not located on the subject property.
DS 2-15.2.D
02/17/2006 PETER MCLAUGHLIN ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Center
Plans Coordination Office

FROM: Peter McLaughlin
Senior Planner

FOR: David Rivera
Principal Planner

PROJECT:
D05-011
Rita Ranch Commerce Center
Lot #36
Development Plan

TRANSMITTAL: February 17, 2006
DUE DATE: February 24, 2006

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for full CDRC review. The one year expiration date for this development plan is January 25, 2007.

2. Place the development plan number (D06-004) along with on each sheet of the development plan, landscape plan and NPPO plans in the lower right hand corner near the title block.
DS 2-02.2.1.A.38

3. If applicable, list the conditions of development for annexation case number C9-84-84, from zoning ordinance 6143 on the d.p.
DS 2-05.2.2.B.7

4. The square footage of the building is inconsistent between the development plan, which reads 5,637 square feet and the landscape plan, which reads 5,682 square feet. Clarify and revise calculations for consistency.
DS 2-05.2.4.M

5. A 5-foot pedestrian refuge, including a 4-foot sidewalk is required between the building and the PAAL. The pedestrian refuge must be physically separated from the PAAL by means of raised concrete curbing, bollards, or some other vehicle barrier. However, if the areas along the back and sides of the building are for employee access and loading only, a 5-foot wide striped area may be painted around the perimeter of the building in these areas in lieu of the requirement for a pedestrian refuge area. Show the 5-foot pedestrian refuge area on the plan.
DS 3-05.2.2.B.1

6. All requested changes must be made to the Development Plan and Landscape Plan.
DS 2-07.2.1.A

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING ITEMS IS REQUIRED: revised development plan, landscape plan.
02/22/2006 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Estimated daily traffic in 24 hr period - 28
02/27/2006 LOREN MAKUS ENGINEERING REVIEW Denied DATE: January 19, 2006

To: Patricia Gehlen
CDRC/Zoning Manager
FROM: Loren Makus, EIT
Engineering Division


SUBJECT: Rita Ranch Commerce Center Lot 36
Development Plan D06-0004 (First Review)
T15S, R15E, Section 27

RESUBMITTAL REQUIRED: Revised Development Plan, Revised Drainage Report,
GENERAL COMMENTS
1. The Drainage Report was reviewed for Development Plan purposes only.
2. A Grading Plan and Permit will be required. Development Standard 11-01.4.1.C. 3. A Stormwater Pollution Prevention Plan must be submitted with the grading plan and permit application. Submit a completed Construction SWPPP Checklist with the SWPPP. The checklist is available from the ADEQ stormwater web site.

DEVELOPMENT PLAN

1. Label Old Vail Road as an MS&R arterial. Indicate that the existing and future right-of-way width are 90 feet.
2. Revise the sight visibility triangles to provide the correct dimensions. The near side triangles should be 20 ft x 345 ft and the far side triangles should be 20 ft by 125 ft. (DS 3-01.5.3.)
3. Provide truncated dome tactile warning along the whole length of the sidewalk that is flush with the pavement. Truncated domes are required whereever pedestrian use areas and vehicle use areas abut without a vertical separation.
4. Provide a notation that the basin will be graded to drain to the low flow pipe.

DRAINAGE REPORT COMMENTS

5. Although the basin provides sufficient retention and detention volumes, it does not provide sufficient capacity to contain the whole discharge from a 100-year event. Provide a discharge structure to accommodate the addituional volume. The discharge structure should be designed to distribute the flow over a wide area to approximate the existing sheet flow.

If you have any questions, I can be reached at 791-5550 x1161 or loren.makus@tucsonaz.gov.

Loren Makus, EIT
Senior Engineering Associate
02/27/2006 TIM ROWE PIMA COUNTY WASTEWATER Denied February 25, 2006

TO: Larry Click
Larry J. Click & Associates

THRU: Patricia Gehlen
City of Tucson, Development Services Department

FROM: Dickie Fernández, E.I.T.
Pima County Development Services Department
Development Review Division (Wastewater)

SUBJECT: Rita Ranch Commerce Center Lot 36
Development Plan – 1st Submittal
D06-004


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


Provide a letter from PCWWM Planning Services, written within the past 90 days, stating that treatment and conveyance system capacity for this project is available. A capacity request form may be found at http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

ALL SHEETS. Add the project number, D06-0004, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers.

Based on the evaluation of the proposed sewer design, this project qualifies for Standard sewer connection fee rates.

Only one sheet has been received for this review, however, this sheet indicates that there are three sheets on this development plan. Please supply the remaining two sheets in your next submittal.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $100.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me. Sincerely,





Dickie Fernández, E.I.T.
Telephone: (520) 740-6947

Copy: Project
02/27/2006 FRODRIG2 COT NON-DSD REAL ESTATE Approved No comment
02/27/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D06-0004 Rita Ranch Commerce Center 2/26/06

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-84-84, C12-95-33

NEIGHBORHOOD PLAN: Esmond Station

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: 2/24/06

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
(X) Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:







REVIEWER: msp 791-4505 DATE: 2/23/06
03/03/2006 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: RITA RANCH COMMERCE CENTER, Lot 36

D06-0004



Tucson Electric Power Company has reviewed and approved the development
plan submitted January 26, 2006.



In order to apply for electric service, call the New Construction
Department at (520) 918-8300. Submit a final set of plans including
approved site, offsite and electrical load plans. Include a CD with the
AutoCAD version of the plans. If easements are required, they will be
secured by separate instrument. Your final plans should be sent to:



Todd Stocksdale

Design/Build - DB 102

Tucson Electric Power
Company

P. O. Box 711

Tucson, AZ 85702



Please call me at (520) 917-8745, should you have any questions.


Liza Castillo
Right of Way Agent
Land Management
Tucson Electric Power Co.
(520) 917-8745
lcastillo@tep.com
03/03/2006 DALE KELCH COT NON-DSD TRAFFIC Denied Traffic Engineering REJECTS this DP:

1. The access points shall have 25' radius curb returns. (DS 3-01.0 figure 6)

2. The SVTs are incorrectly sized. Old Vail Road is an arterial roadway according to the current MSRP.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
03/03/2006 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: March 1, 2006

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov



SUBJECT: D06-0004 Rita Ranch Commerce Center: Development Plan Review

Staff has no comments.
03/08/2006 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 8, 2006

Larry Click
Larry J. Click & Associates
3444 North Country Club Road, Suite 105
Tucson, Arizona 85716

Subject: D06-0004 Rita Ranch Commerce Center Lot #36 Development Plan

Dear Larry:

Your submittal of January 26, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

7 Copies Revised Development Plan (Fire, Wastewater, Traffic, Landscape, Zoning, Engineering, DSD)

4 Copies Revised Landscape and NPPO Plans (Zoning, Landscape, Engineering, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)




Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 327-8816
03/08/2006 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Passed