Permit Number: D06-0002
Parcel: 13623009B

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D06-0002
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
02/05/2007 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: ESPERANZA EL ESCALANTE
D06-0002

Tucson Electric Power Company has reviewed and approved the development
plan submitted for review February 1, 2007.



In order to apply for electric service, call the New Construction
Department at (520) 918-8300. Submit a final set of plans including
approved site, offsite and electrical load plans. Include a CD with the
AutoCAD version of the plans. If easements are required, they will be
secured by separate instrument. Your final plans should be sent to:



Tucson Electric Power
Company

Attn: Ms. Mary Boice

New Business Project
Manager

P. O. Box 711 (DB-101)

Tucson, AZ 85702

520-917-8732





Please call me at (520) 917-8745, should you have any questions.


Liza Castillo, Right of Way Agent
Land Management
Tucson Electric Power Co.
Unisource Energy Gas & Unisource Energy Electric
PH: (520) 917-8745
lcastillo@tep.com <mailto:lcastillo@tep.com>
02/06/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approv-Cond Call out for 25' returns at the access point off of Calle Polar. Verify whether curb or a concrete header is going to be used.
02/16/2007 FRODRIG2 PIMA COUNTY WASTEWATER Denied February 15, 2007

TO: Steven Hill, P.E.
Leadstar Engineering

THRU: Patricia Gehlen, CDRC Manager
City of Tucson, Development Services Department

FROM: Chandubhai C. Patel, P.E., Civil Engg. Manager
Development Review Division (Wastewater)
Pima County Development Services Department

SUBJECT: Esperanza El Escalante
Development Plan – 2nd Submittal
D06-002


The proposed sewer collection lines to serve the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



SHEET 1. Delete General Note #8 or #14 as they are duplicates.

SHEET 1. Add a General Note that states:

A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT.

SHEET 4. Label the MH#1 as EXISTING PUBLIC MH # 4968-01, and provide its rim and invert elevations..

SHEET 4. Call out the sewer line north of the above MH as EXISTING PUBLIC SEWER.

SHEET 4. Call out the sewer line south of the MH # 4968-01 as EXISTING PRIVATE SEWER.

SHEET 4. Is the sewer line in the PAAL area existing? If so, label it as such and show its size, slope and length. If this is a new line as the drawing shows, how is the existing building receiving sewer service ?


SHEET 4. Label the 2 BCS from new buildings as NEW BCS and show their sizes.

SHEET 4. Show the rim and invert elevations of the proposed cleanouts.

We will require a revised set of drawings and a response letter addressing each comment. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 3rd submittal. A check for the review fee of this submittal in the amount of $78.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter.

For any questions regarding the fee schedule, please go to http://www.pimaxpress.com/SubDivision/Documents/Fees.PDF where you may find the appropriate wastewater review fees at the bottom of page 1. If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me.

Sincerely,




Chandubhai C. Patel, P.E.
Telephone: (520) 740-6563

Copy: Project File
02/21/2007 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D06-0002 ESPARANZA EL ESCALANTE/REVISED DEVELOPMENT PLAN
DATE: February 20, 2007



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:


1.) Please call to discuss use of building numbers and/or existing unit numbers prior to Final approval.










jg
02/26/2007 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 02/26/2007

TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: Esperanza El Escalante
D06-0002, T14S, R15E, SECTION 30

RECEIVED: Development Plan, Landscape Plan and Drainage Report on February 01, 2007

The subject project has been reviewed. We offer the following comments:

Drainage Report:

1. Provide a detailed response letter to the Drainage Report comments.
2. Show all the concentration points for the combined flows in Tables 2.2 and 2.3.
3. Provide the Concentration Points numbers in the Hydrologic data Sheets.
4. Concentration Point 2 shown on Exhibits 1 and 2 are different and may cause confusion. Additionally, it appears that concentration Point 2 shown on Exhibit 1 does not have a Hydrologic Data Sheet. Revise as necessary.
5. Provide a hydrologic data sheet for Concentration Point 4 shown on Exhibit 2.
6. It is not clear the purpose of the synthetic hydrograph provided for existing and proposed conditions. Is the purpose for sizing the detention basin. Clarify the purpose.
7. Address in the report how the possibility of sedimentation in the bottom of the basin will be reduced/controlled in order to minimize future basin maintenance.
8. According to Section 3.3.5 "Low-Flow Channels" of the Stormwater Detention/Retention Manual, the proposed basins floors should be sloped to provide positive drainage. The section recommends a minimum of 0.5% floor slope and 0.2% low flow concrete channel slope. Please be advised that based on the City's experience with similar projects, 0.5% slope was difficult to construct and maintain which resulted in nuisance ponding in the basins. Show the provided positive drainage on the drainage exhibit.
9. Provide, on the drainage exhibits, the detention basin dimensions and any proposed sediment control measures.
10. Buildings set backs need to be determined from the proposed detention basin based on the recommendations of the Geotechnical Report. Submit a Geotechnical Report that addresses required setbacks.

Development Plan:

1. The existing channel and grate inlet south of Calle Polar shall be shown as required by D.S. 2-05.2.3.F.
2. The existing wall along the north side of the project appears to be in the public right of way. Address this issue and revise as necessary.
3. Show building setbacks from the proposed detention/retention basin as required by D.S. 2-05.2.4.I. Please be advised that detention basin setbacks shall be addressed in the Geotechnical Report.
4. The proposed sidewalk (i.e. Keynote 9) shall be connected to the existing Pedestrian Path D.S. 2-08.3.1.
5. The refuse collection areas will have the appropriate trash enclosures to provide the required screening. Show clearly the locations of dumpsters, screening location and materials and garbage collection vehicle accessibility and maneuverability, fully dimensioned. (D.S. 2-05.2.4.T. and D.S. 6-01.2.2.).
6. As per Federal ADA requirements, all wheel chair ramps shall have the Truncated Domes instead of the standard grooves, which are shown on City of Tucson Standard Detail 207. Aside from the Truncated Domes, the wheel chair ramps shall be constructed in accordance with the Standard Detail 207.

Landscape Plan:

1. Clarify where the proposed locations of water-harvesting basins. Call out the basins on the plan. Additionally, it appears that the retention basin detail is called out incorrectly on the plan.

Prepare a detailed response that explains the revisions that were made and references the exact location in the drainage report and on the Development Plan where the revisions were made.



RESUBMITTAL REQUIRED: Revised Development Plan, Landscape Plan and Drainage Report
02/26/2007 AVERA1 ENV SVCS REVIEW Denied * Must demonstrate and provide for safe access to enclosure area with required 14'x40' approach per section 6 of the development standards.
* No enclosure details provided.
02/28/2007 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Revise the plans to correct the erroneous rezoning case reference. DS 2-07.2.1.B.

2) Add a note to the landscape plan stating that the retention basin will be landscaped in accordance with LUC 3.7.4.3.A and Development Standard 10-01.0. in future phases.
Landscaping is required along retention basin side slopes, bottom and periphery. Plant materials used in basins shall withstand periodic inundation. A minimum of 20 trees per acre must be provided, 33% of tress shall be 24" box or larger. A minimum of 2 shrubs for each tree is required per DS 10.01.

3) The vehicular use area must be provided with post barricades or wheel stop curbing designed to prevent parked vehicles from extending beyond the property lines; damaging adjacent landscaping, walls, or buildings and to prevent vehicles from driving onto unimproved portions of the site per DS 3-05.2.3.C. Revise the plans as necessary.

4) Fences or walls shall extend into a street landscape border no more than the actual width of the fence or wall. Walls are to be located at the back or behind the street landscape border and shall not obscure visibility of the landscape border from the street. DS 2-06.3.7.B

5) Revise the landscape plan to corect the note regarding the landscape border requirement along the west property boundary. A border will be required as additional phases are developed per LUC Table 3.7.2-I

6) Revise the development plan to provide refuse storage locations with paved access. LUC 3.3.7.3, 6.2.22

7. Submit a native plant preservation plan that includes developed portions of the site per LUC 3.8.3. For example, improvements may be required to the area designated as Phase J.

8) Revise the irrigation plan to correspond with revisions to the landscape plan and to include a symbols and line legend. DS 2-07.2.0

9) Within a vehicular use area, one (1) canopy tree is required to be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a. Revise the plans to provide the required trees.

10) Identify, by genus and species, all existing vegetation to remain in place. DS 2-07.2.2.A.1.e

11) Fifty (50) percent or more of the area of the street landscape border must be covered with shrubs or vegetative ground cover. The required ground coverage must be achieved within two (2) years from the date of planting. Revise the landscape plans to show individual plants, to include a plant legend including quantities, and to include calculations per DS 2-07.2.2.A.2.g., LUC 3.7.2.4.A.5

12) All disturbed, grubbed, graded, or bladed areas not otherwise improved shall be landscaped, reseeded, or treated with an inorganic or organic ground cover to help reduce dust pollution. Revise landscape plan to identify the type and locations proposed for inert ground cover materials or seeded areas for the proposed phase. LUC 3.7.2.7. DS 2-06.5.2.C

13) Screening is required for the vehicular use areas per LUC Table 3.7.2-I. Show the required screening on the development/landscape plans. Screening is to be located in accordance with the Land Use Code per comment #4 above.

14) Revise the caluclations for street landscape border trees. 38 are required for Calle Polar and 18 are required for Nicaragua Drive. Show the additional trees on the plans.

15) Provide a landscape plan at a minimum scale of 1"-40' due to the detailed information required to show compliance. DS 2-05.2.1.B

16) Revise the landscape plans to show the limits of grading for Phase A. Areas within the Phase A grading limits will be required to comply with the dust control requirements. See comment 12. DS 2-07.2.2.B.5

RESUBMITTAL OF ALL PLANS IS REQUIRED.
03/05/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approv-Cond DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D06-0002 Esparanza El Escalante 03/02/07

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: SE-03-08 Esperanza En Escalante-Calle Polar

NEIGHBORHOOD PLAN: South Pantano Area Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: 3/2/07

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies With Plan Policies
(X) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:








REVIEWER: msp 791-4505 DATE: 2/23/07

Department of Urban Planning and Design Comments
D06-0002 Esperanza El Escalante: Development Plan
February 23, 2007


At the time of development plan approval the applicant only proposes to construct Phase A. The current development plan submittal does not provide any substantial information on phases “B through M” to determine compliance with Special Exception SE-03-08.

Based on the above information, staff offers to release without further review of Phase A development, under the following condition; that the Department of Development Services accepts the following condition as approval of Phase A, with the understanding that the following information be added to a revised development plan with an additional general note as outlined below, prior to release of Phase A. The conditions reads as following:

Prior to any approvals within Phases B through M, a revised development plan shall be required. Revised development plan shall include an additional general note, which require Phases B through M to comply with Special Exception SE-03-08 requirements.
03/23/2007 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: D06-0002
Esperanza el Escalante
3700 S. Calle Polar

TRANSMITTAL DATE: March 23, 2007

DUE DATE: March 2, 2007

COMMENTS: PHASE I IS ALSO EXISTING, PROVIDE ON AT DETAIL LEVEL SHOWN ON SHEET 2 FOR PHASES A AND J. NOTE THAT FURTHER REVIEWS WILL HAVE TO BE DONE ON PHASE I FOR DEVELOPMENT DETAIL.

1. (last review) Per DS 2-05.2.1.D., add the following street names to the location plan: Stella, Mann, Nicaragua and Calle Polar.
RESPONSE: Thank you, please revise spelling of Stella.

2. (this review) Per DS 2-05.2.2.B.11, the gross area of the site is listed as 16.86 acres, yet the Special Exception report lists the site as being 19.02 acres. Please check.

3. (last review) Per DS 2-05.2.2.B.5, list lot coverage calculations - proposed for these phases A, J and I, and then list the maximum permitted for the site overall.
RESPONSE: This comment was not addressed. I acknowledge the table on sheet 1, however, that table shows Floor Area Ratio calculations, not Lot Coverage calcs. Lot Coverage consists of all building footprint and vehicular use areas - excluding ramadas.

4. (last review) Per DS 2-05.2.2.B.2, list SE-03-08 case requirements- see note 29.
RESPONSE: I see listed conditions, thank you. As it is unclear how criteria will be met, please provide a response letter advising how all conditions -future phases - will be met.

5 (last review). Per DS 2-05.2.3.G, advise if existing buildings will be kept, provide floor plans to determine number of bedrooms. (Number of bedrooms determines number of parking spaces.)
RESPONSE: Provided a breakdown of number of clients per phase, thank you. Please clarify the number of bedrooms per unit and the number of clients per unit - for each phase, to support the proposed number of clients listed for each phase.

6. (last review) Per DS 2-05.2.3.G, Dimension distance between ALL existing buildings, buildings to ADJACENT property lines AND ADJACENT proposed PAALs.
RESPONSE: This comment was partially addressed. Please provide above -and use page 2 to address comment. Several buildings are existing, this is a full code compliance project which requires the site to be brought up to code, and this document will serve as the continued full resource document for further reviews and for new construction.

7. (last review) Per DS 2-05.2.4.C, provide development information - such as lot coverage, floor area ratio, building footprints, number of units/bedrooms, parking calculations, setbacks, building heights, etc. for each phase of the development. Note, as each phase is completed, the development must be able to stand alone - i.e. enough parking must be provided with each phase, etc. Use of any vacant portions of the site is not permitted.
RESPONSE: This comment was partially addressed.
A) Please provide lot coverage calculations in the chart on sheet 1.
B) building footprints -existing and proposed - need to be dimensioned
C) give setbacks from all buildings to adjacent lot lines and or PAALs

8. (last review) Per DS 2-05.2.4.K, continuous pedestrian access must be provided from all streets abutting this site connecting all buildings on site. Revise the drawing to show pedestrian access, noting it is also required for all existing buildings.
RESPONSE:
A) Per SE case, only one sidewalk to site from Calle Polar, however, a sidewalk needs to be provided from Nicaragua per DS 2-08.
B) Sidewalks must be provided between PAALs and buildings per DS 2-08 (existing buildings)
C) Provide a sidewalk on between parking spaces and buildings - 4' wide, DS 2-08
D) Sidewalks must connect all buildings and parking areas throughout site, DS 2-08
E) Provide 5' wide sidewalk along PAALs, 4' elsewhere - dimension - per DS 2-08.
F) The crosswalk in east parking lot near the existing canopy in Phase A needs to be re-designed to ensure a parking space does not back out over the cross walk - straighten.
G) On detail 10 on sheet 6, handicapped sign impedes 4' clear area on sidewalk, move
H) On detail 10, sheet 6 and on detail 12, the sidewalk is 6" above the asphalt, need handicapped ramps shown to allow handicapped access aisle to access sidewalk. Provide handicapped ramps, with truncated domes, in detail & keynote sheets 2 & 3.
I) Provide a typical detail drawing for a van accessible access aisle - 8' wide minimum or an 11' space with 5' access aisle required.
J) Review plan further and once more sidewalks are added between buildings and PAALs, provide handicapped ramps where applicable to ensure safe crossing between phases across PAALs.
K) Further review comments may be forthcoming on these elements

9. (last review) Per DS 2-05.2.4.M, clarify use of each building, give labeled floor plans.
RESPONSE: This comment was not addressed. identify the use of new buildings- are they units, counseling facilities, work facilities - what? I also do not see floor plans for the buildings proposed. Floor plans for the existing buildings can be drawn in, provide.

10. Per DS 2-05.2.4.N, label heights of all buildings, provide dimensions on all building footprints (existing buildings if they are to remain).
RESPONSE: I see the general notes for the buildings on sheet 1, comment 9. For issuance of building permits, provide the specific height of each new building proposed on sheet 3. I do not see elevation drawings with this submittal package. Dimension all building footprints, this is for lot coverage verification and records.

11. Per DS 2-05.2.4.P, provide parking calculations per LUC 3.3.4 residential care service criteria - phased and overall. Parking for each building is to be noted.
RESPONSE:
A) parking location does not adequately serve existing buildings - provide more parking closer to these units off new PAALs - including more handicapped parking
B) parking is to be provided at 1 space for every 2 beds, and each phase must stand alone
C) parking provided per number on plan is 78, correct sheet 1 to read 78, not 77 provided
D) parking calculations in the chart need to be revised to list required and proposed for each phase
E) where did the maximum parking number of 191 come from? SE case mentions 203
F) provide a curb or temporary fencing around undeveloped land to prevent use
G) dimension wheel stop barrier to be fully within 2'6" from front of parking space
H) dimension distance between back up spur and unit 57.
I) Further review comments on parking may be forthcoming

12. Per DS 2-05.2.4.Q, provide bicycle parking calculations and typical rack/locker detail drawings.
RESPONSE:
A) bicycle rack proposed does not meet requirements of DS 2-09, revise. See internet.
B) Bike racks should be provided evening throughout development, not grouped
C) Bike racks should have lighting and should be seen visibly from PAALs
D) Bike parking to be provided is based upon a 4% requirement of vehicle spaces provided. 78 vehicles provided needs 3 bike spaces - revise plan to read 3, not 2 required.
E) Provide 5' pedestrian area clear around each bike rack
F) Provide access to bike racks per DS 2-09 - see internet www.tucsonaz.gov/dsd codes, Development Standards.

13. Per condition 1 of the Special Exception SE-03-08, provide documentation the development plan submitted was presented to neighboring property owners within 15 days of submittal to CDRC.
RESPONSE: I am sorry, I did not find a copy of this. Please provide.

14. Condition 7 of the SE case does not appear to be met with this submittal. This condition, as shown on the preliminary development plan showing 4 phases of construction, stipulates that a common outdoor rec center/passive activity facility is to be provided for each of the 4 phases - and must be constructed prior to occupancy of each phase. Demonstrate compliance with this condition, for the 4 phase areas shown on the preliminary plan. It is acknowledged that 9 phases are shown for this project under the current submittal.
RESPONSE: PER DISCUSSION WITH ZONING ADMINISTRATOR, passive recreation areas (benches, ramadas, BBQs, etc.) must be provided for each phase of the development. THIS SUBMITTAL SHOWS 13 PHASES, EACH OF THESE 13 PHASES MUST PROVIDE A PASSIVE RECREATION AREA- BE ADVISED FOR FUTURE REFERENCE. Please demonstrate compliance with this requirement on the plan for phases A, I and J as currently proposed.

15. Provide a written response letter advising how each condition of the special exception case has been - or will be- met.
RESPONSE: The references you are providing to DUPD staff are too general to meet this response (i.e. - see landscape plan), and do not individually list the condition, and the specific action to be taken to meet the condition.

16. Depending upon the responses provided, further review comments may be forthcoming. Should you have questions on this review, contact me at Heather.Thrall@tucsonaz.gov or at 791-4541x1156. If you want to meet with me, I would welcome that, prior to a resubmittal. I would like to ensure any questions you have are addressed prior to resubmittal.

If you have any questions about this transmittal, please call (520) 791-5608.


C:\planning\cdrc\developmentplan\D06-0002 esperanza el escalante 2 revised.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, additional requested documents.
03/27/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 27, 2007

Steve Hill
Leadstar Engineering
1010 North Finance Center Drive, Suite 200
Tucson, Arizona 85710

Subject: D06-0002 Esperanza El Escalante Development Plan

Dear Steve:

Your submittal of February 1, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter for each agency explaining how each outstanding requirement has been addressed:

ALL BLUELINES MUST BE FOLDED

8 Copies Revised Development Plan (ESD, Addressing, Wastewater, Traffic, Landscape, Zoning, Engineering, DSD)

4 Copies Revised Landscape Plans (Zoning, Landscape, Engineering, DSD)

2 Copies NPPO Plans (Landscape, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)

2 Copies Neighborhood Notification (Zoning, DSD)

THE ONE (1) YEAR REVIEW PERIOD FOR THIS DEVELOPMENT PLAN EXPIRED 1/17/2007. PRIOR TO RESUBMITTAL OF THIS PLAN, A WRITTEN REVIEW EXTENSION REQUEST MUST BE SUBMITTED TO AND APPROVED BY THE CDRC OFFICE.


Should you have any questions, please call me at 791-5608, ext. 1179.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 571-1961