Permit Number: D05-0036
Parcel: 13323102D

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D05-0036
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2005 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
11/16/2005 JOE LINVILLE LANDSCAPE REVIEW Approved
11/18/2005 RBABBIT1 LANDFILL ENVIRONMENTAL SERVICES Approved
11/22/2005 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond November 22, 2005

To: Aaron Katz, Swaim Associates

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Tim Rowe, P.E. (520-740-6563), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: 7350 Professional Office Complex - 7350 E. Speedway Blvd.
Development Plan - 2nd Submittal
D05-036

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



Sheet 2: A clean-out or manhole will need to be installed where the 6" sewer line from Building 2 joins the 6" sewer line from Building 1.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
11/22/2005 DALE KELCH COT NON-DSD TRAFFIC Approved Traffic Engineering recommends APPROVAL of this DP.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
11/22/2005 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: D05-0036 7350 PROFESSIONAL OFFICE COMP / REVISED DEVELOPMENT PLAN
DATE: November 21, 2005



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE:

1: Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved
Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima
County Addressing prior to assignment of addresses.

2: All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
11/23/2005 PAUL MACHADO ENGINEERING REVIEW Approved To: Patricia Gehlen DATE: November 23, 2005
CDRC/Zoning Manager
SUBJECT: 7350 E. Speedway Blvd, Prof. Ofc. Complex
Development Plan D05-0036 (Second Review)
T14S, R15E, Section 08

RESUBMITTAL REQUIRED: Development Plan and Drainage Report.

The Development Plan (DP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. Per our conversations and meeting on this project the TP does not reflect any of the revisions agreed on for the grading plan. The re-submittal should show all changes agreed upon.
3. Show all drainage facilities on the TP.
4. Call out surface paving material.
5. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15.2.1.16. Per previous comment.
6. Det./Ret. basin shall not be located in the 50' linear park easement. Revise as required. Per previous comment.
7. Provide a cross-section of the proposed improvements for the river park per rezoning condition no. 12 on the plans.
8. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. Per previous comment.
9. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. The service vehicle does not meet the turning radius standards and exceeds the max. "back-up" distance allowed. Also include a dumpster enclosure detail. The TP has not been revised as required per previous comment. Obtain approval from Environmental Services, John Clark, 791-5543 x1136, include the approval with the re-submittal.

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. As agreed upon with Swaim and associates the retention basin will be replaced a smaller rip-rap splash pad and be placed outside the 100-year flood plain and park improvements along with drainage scuppers under the park path.
3. A Flood Plain Use permit will be required for any construction or disturbance in the floodplain.
4. Show the 100-year W.S.E.L. on figure 3 of the DR.


If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/7350 E. Speedway Blvd CDRC 2
11/23/2005 PAUL MACHADO ENGINEERING REVIEW Approved An over the counter review was done to approve the minor revisions needed for approval.

Paul Machado.
11/30/2005 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: November 30, 2005

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov



SUBJECT: D05-0036 Professional Office Complex: Development Plan(11-16-05)


Approved
11/30/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approved The consultant/property owner have not completed the required dedication of the Pantano River Park Corridor which is condition #11 of the re-zoning. Without the dedication completed I can not give an approval or even a conditional approval of this development plan.
11/30/2005 FRODRIG2 COT NON-DSD REAL ESTATE Approved We now have signed documents for the dedication of the Pantano Linear Park, Real Estate has no further objection.
12/01/2005 DAN CASTRO ZONING REVIEW Approv-Cond The Zoning Review Section approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

1.
Under the vehicle parking calculation on sheet 1 of 2, revise the parking ratio for the first floor to (1:200) and the second floor to (1:250).

2.
Provide the parking sign required by rezoning condition 12i. Indicate the location and provide a detail.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180.
12/09/2005 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

December 9, 2005

Aaron S. Katz, AIA
Swaim Associates Ltd.
3936 East Fort Lowell Road, Suite 202
Tucson, AZ 85712

Subject: D05-0036 7350 Professional Office Complex Development Plan

Dear Aaron:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per Community Planning, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blueline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from Reproductions, Inc. and billed to you. If you do not already have an account at Reproductions, Inc., please contact them at (520) 622-7747 to arrange for payment. If you are located in Tucson, Reproductions, Inc. will deliver the mylar and two (2) blueline copies to your office. If you are out of town you will need to arrange to pick them up at the CDRC office of Development Services.

Should you have any questions, please call me at 791-5608.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/


Via fax: 326-1148